ES-5956 Rev.15
R1C-GH
Remote I/O R1X Series
THERMOCOUPLE & DC INPUT MODULE
(16 points; CC-Link Ver.1.10/Ver.2.00)
Functions & Features
• 16-point thermocouple or DC inputs
• CC-Link interface
• CC-Link Version 1.10 and 2.00 can be switched at the startup
MODEL: R1C-GH2T-[1][2]
ORDERING INFORMATION
• Code number: R1C-GH2T-[1][2]
Specify a code from below for each of [1] and [2].
(e.g. R1C-GH2T-M2/Q)
• Specify the specification for option code /Q
(e.g. /C01)
• Use Ordering Information Sheet (No. ESU-5956). Default setting will be used if not otherwise specified.
Factory default setting
Input type: DC Voltage ±5 V
Burnout protection: No burnout
Cold junction compensation: No
FIELD TERMINAL TYPE
T
:
M3 screw terminals
[1] POWER INPUT
AC Power
M2
: 100 – 240 V AC (Operational voltage range 85 – 264 V,
47 – 66 Hz)
DC Power
R
: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
[2] OPTIONS
blank
: none
/Q
: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
RELATED PRODUCTS
• Resistor module (model: REM3-250)
• PC Configurator cable (model: MCN-CON or COP-US)
• R1X configurator software (model: R1CON)
Downloadable at our web site.
PACKAGE INCLUDES...
• Terminating resistor (110 Ω, 0.5 W)
GENERAL SPECIFICATIONS
Connection
Power input, CC-Link
: Euro type connector terminal
(applicable wire size: 0.2 to 2.5 mm
2
(AWG24 to 12), stripped length 7 mm)
Input
: M3 screw terminals (torque 0.6 N·m)
Configurator
: 2.5 dia. miniature jack; RS-232-C level
Screw terminal
: Nickel-plated steel
Housing material
: Flame-resistant resin (gray)
Isolation
: Input to CC-Link (FG) to power
PWR indicator
: Green LED blinks in normal conditions.
CC-Link COMMUNICATION
Protocol
: CC-Link V1.10 / V 2.00
Cable for comm. link
: Specified by Mitsubishi Electric
Required nodes
V. 1.10
: 4
V. 2.00
: 1 (cyclic expansion: 4)
Station No. setting
: Rotary switch
V. 1.10
: Rotary switch; 1 – 61
V. 2.00
: Rotary switch; 1 – 64
Baud rate setting
: Rotary switch
L RUN indicator
: Red LED turns on in normal conditions.
L ERR. indicator
: Red LED turns on or blinks in an
abnormality.
SD indicator
: Red LED turns on when transmitting.
RD indicator
: Red LED turns on when receiving.
INPUT SPECIFICATIONS
■
Thermocouple or DC input, 16 points
(Common negative for DC input)
• Measuring range ±20 V, ±5 V, ±1 V: Atten. SW ON (3)
• Measuring range ±0.8 V, ±0.2 V, ±50 mV, ±10m V: Atten. SW OFF (1)
Input resistance
: 300 kΩ
Thermocouple types
: PR, K, E, J, T, B, R, S, C, N, U, L, P
Sampling rate
: 150 millisec./16 points
■
A/D conversion output
: 16-bit signed binary (negative range represented by 2’s complements)
Engineering unit value is converted into A/D conversion data as shown below.
Input type & range
:
A/D data (decimal
)
±20 V: ±20000
±5 V: ±5000
±1 V: ±10000
±0.8 V: ±8000
±0.2 V: ±20000
±50 mV: ±5000
±10 mV: ±10000
Thermocouples: Temperature × 10
In order to change input type and range after shipment, the R1X configurator software (model: R1CON) is required.
CC-Link version selector input
:
Ver. 1.10 with OFF at the startup.
Ver. 2.00 with ON at the startup.
Dry contact input (ON at detect. level ≤ 1.5 V)
Sensing: approx. 5 V DC, 1 mA
Valid only at the moment of the power supplied to the
module. Firmware version 0B.00 or higher required.
Confirm the firmware version using the R1X configurator
software (model: R1CON) or consult us.
INSTALLATION
Power consumption
•
AC
: Approx. 10 VA
•DC
: Approx. 7 W
Operating temperature
: -5 to +60°C (23 to 140°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Mounting
: Surface or DIN rail
Weight
: 400 g (0.88 lb)
PERFORMANCE (% of measuring range)
Accuracy
DC input
: ±0.3 %
Thermocouple input
: See the table on the end of this section.
Cold junction compensation error
: ±3°C or ±5.4°F max.
(at 20°C ±10°C or 68°F ±18°F)
Temp. coefficient
: ±0.015 %/°C (±0.008 %/°F)
±0.05 %/°C (±0.03 %/°F) for 10 mV range and T/C B (RH)
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 2000 V AC @ 1 minute (input to CC-Link [FG] to power to ground [FG1])
EXTERNAL VIEW
CONNECTION DIAGRAM
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]