ES-7913 Rev.11
M6NPS1
Screw Terminal Ultra-Slim Signal Conditioners M6N Series
POWER SUPPLY MODULE
Functions & Features
• Supplies power to the M6N modules mounted on the Installation Base
• High-density mounting
• Power indicator LED
MODEL: M6NPS1–R[1]
ORDERING INFORMATION
• Code number: M6NPS1-R[1]
Specify a code from below for [1].
(e.g. M6NPS1-R/UL/Q)
• Specify the specification for option code /Q
(e.g. /C01)
POWER INPUT
DC Power
R
: 24 V DC
(Operational voltage range 22 – 27 V, ripple 10 %p-p max.)
[1] OPTIONS (multiple selections)
Standards & Approvals
blank
: CE marking
/UL
: UL approval, CE marking
Other Options
blank
: none
/Q
: Option other than the above (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
GENERAL SPECIFICATIONS
Connection
:
M3 screw terminal (torque 0.5 N·m)
Recommended solderless terminal
: Max. 5.8 mm (0.23”)
wide; Ones with insulation sleeve do not fit.
Applicable wire size: 0.2 – 2.5 mm
2
Housing material
: Flame-resistant resin (black)
Power indicator LED
: Green LED turns on when the power is supplied.
■Recommended solderless terminal (unit: mm [inch])
INSTALLATION
Power input
: 2 A (Total current consumed by signal conditioners on the base must be 2 A or less.)
Operating temperature
: -20 to +55°C (-4 to +131°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Mounting
: Installation Base (model: M6NBS)
Weight
: 60 g (2.1 oz)
PERFORMANCE
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 2000 V AC @ 1 minute (power to ground)
STANDARDS & APPROVALS
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
Approval
:
UL/C-UL nonincendive Class I, Division 2,
Groups A, B, C, and D hazardous locations
(ANSI/ISA-12.12.01, CAN/CSA-C22.2 No.213)
UL/C-UL general safety requirements
(UL 61010-1, CAN/CSA-C22.2 No.61010-1)
CURRENT CONSUMPTION
In order to operate signal conditioners, it is required that the total maximum current consumption of the signal conditioners is not more than 2 A.
If the total current consumption exceeds 2 A, change the combination of signal conditioners or reduce the number of them mounted.
M6xCTC 25 mA
M6xDY 50 mA
M6xPA 25 mA
M6xPP 50 mA
M6xVF 30 mA
M6xVS 25 mA
M6xWVS 30 mA
M6xXAP 50 mA
M6xXAR 25 mA
M6xXAS 25 mA
M6xXAT 25 mA
M6xXF1 25 mA
M6xXF2 25 mA
M6xXF3 25 mA
M6xXM 25 mA
M6xXR 25 mA
M6xXT 25 mA
M6xXU 25 mA
M6xXV 25 mA
M6xYV 21 mA
EXTERNAL VIEW
(With the cover open)
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM