ES-7913 Rev.11

M6NPS1

Screw Terminal Ultra-Slim Signal Conditioners M6N Series

POWER SUPPLY MODULE

Functions & Features
• Supplies power to the M6N modules mounted on the Installation Base
• High-density mounting
• Power indicator LED
 

MODEL: M6NPS1–R[1]

ORDERING INFORMATION

• Code number: M6NPS1-R[1]
Specify a code from below for [1].
  (e.g. M6NPS1-R/UL/Q)
• Specify the specification for option code /Q
  (e.g. /C01)

POWER INPUT

DC Power
R: 24 V DC
(Operational voltage range 22 – 27 V, ripple 10 %p-p max.)

[1] OPTIONS (multiple selections)

Standards & Approvals
blank: CE marking
/UL: UL approval, CE marking
Other Options
blank: none
/Q: Option other than the above (specify the specification)

SPECIFICATIONS OF OPTION: Q

COATING (For the detail, refer to our web site.)
/C01: Silicone coating
/C02: Polyurethane coating

GENERAL SPECIFICATIONS

Connection: M3 screw terminal (torque 0.5 N·m)
Recommended solderless terminal: Max. 5.8 mm (0.23”)
wide; Ones with insulation sleeve do not fit.
Applicable wire size: 0.2 – 2.5 mm2
Housing material: Flame-resistant resin (black)
Power indicator LED: Green LED turns on when the power is supplied.
■Recommended solderless terminal (unit: mm [inch])

INSTALLATION

Power input: 2 A (Total current consumed by signal conditioners on the base must be 2 A or less.)
Operating temperature: -20 to +55°C (-4 to +131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Installation Base (model: M6NBS)
Weight: 60 g (2.1 oz)

PERFORMANCE

Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 2000 V AC @ 1 minute (power to ground)

STANDARDS & APPROVALS

EU conformity:
EMC Directive 
  EMI EN 61000-6-4
  EMS EN 61000-6-2
RoHS Directive
Approval:
  UL/C-UL nonincendive Class I, Division 2,
  Groups A, B, C, and D hazardous locations
  (ANSI/ISA-12.12.01, CAN/CSA-C22.2 No.213)
  UL/C-UL general safety requirements
  (UL 61010-1, CAN/CSA-C22.2 No.61010-1)

CURRENT CONSUMPTION

In order to operate signal conditioners, it is required that the total maximum current consumption of the signal conditioners is not more than 2 A.
If the total current consumption exceeds 2 A, change the combination of signal conditioners or reduce the number of them mounted.
M6xCTC  25 mA
M6xDY  50 mA
M6xPA  25 mA
M6xPP  50 mA
M6xVF  30 mA
M6xVS  25 mA
M6xWVS  30 mA
M6xXAP  50 mA
M6xXAR  25 mA
M6xXAS  25 mA
M6xXAT  25 mA
M6xXF1  25 mA
M6xXF2  25 mA
M6xXF3  25 mA
M6xXM  25 mA
M6xXR  25 mA
M6xXT  25 mA
M6xXU  25 mA
M6xXV  25 mA
M6xYV  21 mA

EXTERNAL VIEW

(With the cover open)

EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM