ES-7745-A Rev.0
R7I4DEIP-DA32A-1
Remote I/O R7I4D Series
EtherNet/IP I/O MODULE
(NPN discrete input, 32 points, e-CON connector)
Functions & Features
• 32 points NPN discrete input module for EtherNet/IP
• Supports DLR (Device Level Ring) to form a ring topology
MODEL: R7I4DEIP-DA32A-1-R[1]
ORDERING INFORMATION
• Code number: R7I4DEIP-DA32A-1-R[1]
Specify a code from below for [1].
(e.g. R7I4DEIP-DA32A-1-R/Q)
• Specify the specification for option code /Q
(e.g. /C01/SET)
I/O TYPE
DA32A:
NPN discrete input, 32 points
TERMINAL BLOCK
1
: Tension clamp terminal block for power supply
RJ-45 Modular jack for communication
e-CON connector for input
POWER INPUT
DC Power
R
: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
[1] OPTIONS
blank
: none
/Q
: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
EX-FACTORY SETTING
/SET
: Preset according to the Ordering Information Sheet
(No. ESU-7745-A)
RELATED PRODUCTS
• PC configurator software (model: R7CFG)
• EDS file
The EDS files and configurator software are downloadable at our web site.
For connecting to PC, use commercially available Mini-B type USB cable. (provided by user)
GENERAL SPECIFICATIONS
Connection
EtherNet/IP
: RJ-45 Modular Jack
Power & Sensor excitation
: Separable screwless spring
terminal
Input:
e-CON connector
Housing material
: Flame-resistant resin (gray)
Isolation:
Input or exc. supply to EtherNet/IP or FE to power
Status indicator LED
: PWR, LNK1, LNK2
(Refer to the instruction manual)
Discrete input status indicator LED
: Green LED turns on with input ON
Read rate:
Selectable with R7CFG
EtherNet/IP COMMUNICATION
Communication Standard
: IEEE 802.3u
Transmission
: 10BASE-T, 100BASE-TX
Baud rate
: 10/100 Mbps (Auto Negotiation function)
Protocol
: EtherNet/IP
Max. number of socket connections
: 3
Connection type
: Exclusive owner / Listen only / Input only
Transmission media
: 10BASE-T (STP, Category 5), 100BASE-TX (STP, Category 5e)
Network topology
: Line, star and ring
Max. length of fieldbus segment
: 100 meters
IP address
: 192.168.0.250 (factory setting);
Only host address in IP address is configurable via rotary switches, the other items via PC configurator software (model: R7CFG)
DLR supported
Port No
.: 2222, 44818
I/O data size
: Two (2) words
Status indicator LEDs
: MS, NS (Refer to the instruction manual for details)
INPUT SPECIFICATIONS
Common
: Positive common (NPN) per 32 points
Maximum inputs applicable at once:
No limit (at 24V DC)
Sensor excitation
: 24 V DC ±10 %; ripple 5 %p-p max.,
≤ 5 A (including discrete input load charge); rated current
8 A
ON voltage / current
: ≥ 18 V DC (X0 through X1F to +24V) / ≥ 2.0 mA
OFF voltage / current
: ≤ 9 V DC (X0 through X1F to +24V) / ≤ 1.0 mA
Input current
: ≤ 3.0 mA per point at 24 V DC
Input resistance
: Approx. 8.6 kΩ
ON delay
: ≤ 0.5 msec.
OFF delay
: ≤ 0.5 msec.
INSTALLATION
Current consumption:
Approx. 50 mA (rated current 8 A)
Operating temperature
: -10 to +55°C (14 to 131°F)
Storage temperature
: -20 to +65°C (-4 to +149°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Atmosphere
: No corrosive gas or heavy dust
Mounting
: Surface or DIN rail (35 mm rail)
Weight
: 180 g (0.40 lb)
PERFORMANCE
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength:
1500 V AC @ 1 minute
(input or exc. supply to EtherNet/IP or FE to power)
STANDARDS & APPROVALS
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
PC CONFIGURATOR
The following parameters can be set with using PC Configurator Software (model: R7CFG)
Refer to the users manual for the R7CFG for detailed operation of the software program.
EXTERNAL VIEW
TERMINAL ASSIGNMENTS
■ INPUT TERMINAL ASSIGNMENT
I/O DATA DESCRIPTIONS
EXTERNAL DIMENSIONS unit: mm [inch]
MOUNTING REQUIREMENTS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
Note: In order to improve EMC performance, bond the FE terminal to ground.
Caution: FE terminal is NOT a protective conductor terminal.