ES-8005-G Rev.0

R7F4HEIP-DA16-M

Remote I/O R7F4HEIP Series

EtherNet/IP I/O MODULE

(NPN/PNP discrete input, 16 points, tension clamp terminal block)
Functions & Features
• 16 points NPN/PNP discrete input module for EtherNet/IP
• Supports DLR (Device Level Ring) to form a ring topology
 

MODEL: R7F4HEIP-DA16-M-R[1]

ORDERING INFORMATION

• Code number: R7F4HEIP-DA16-M-R[1]
Specify a code from below for [1].
  (e.g. R7F4HEIP-DA16-M-R/Q)
• Specify the specification for option code /Q
  (e.g. /C01)

I/O TYPE

DA16: NPN/PNP discrete input, 16 points

TERMINAL BLOCK

M: Tension clamp terminal block for power supply
    RJ-45 Modular jack for communication
    Tension clamp terminal block for I/O
    (applicable wire size: 0.2 - 1.5mm2)

POWER INPUT

DC power
R: 24 V DC
(Operational voltage range: ±10 %; ripple 10 %p-p max.)

[1] OPTIONS

blank: none
/Q: With options (specify the specification)

SPECIFICATIONS OF OPTION: Q

COATING (For the detail, refer to our web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating

RELATED PRODUCTS

• PC Configurator cable (model: MCN-CON or COP-US)
• PC configurator software (model: R7CFG)
• EDS file
The EDS files and configurator software are downloadable at our web site.

GENERAL SPECIFICATIONS

Connection
 EtherNet/IP
: RJ-45 Modular Jack
 Power supply, exc. supply, input: Tension clamp terminal
Housing material: Flame-resistant resin (gray)
Isolation: Input or exc. supply to EtherNet/IP or FE to power
Status indicator LED: PWR, LNK1, LNK2
(Refer to the instruction manual)
Discrete input status indicator LED: Green LED turns on with input ON
Read rate: Selectable with R7CFG

EtherNet/IP COMMUNICATION

Communication Standard: IEEE 802.3u
Transmission: 10BASE-T, 100BASE-TX
Baud rate: 10/100 Mbps (Auto Negotiation function)
Protocol: EtherNet/IP
Max. number of socket connections: 3
Connection type: Exclusive owner / Listen only / Input only 
Transmission media: 10BASE-T (STP, Category 5), 100BASE-TX (STP, Category 5e)
Network topology: Line, star and ring
Max. length of fieldbus segment: 100 meters
IP address: 192.168.0.250 (factory setting);
Only host address in IP address is configurable via rotary switches, the other items via PC configurator software (model: R7CFG)
DLR supported
Port No.: 2222, 44818 
I/O data size: One (1) word
Status indicator LEDs: MS, NS (Refer to the instruction manual for details)

INPUT SPECIFICATIONS

Common: Positive or negative common (NPN/PNP),
16 points per common
Numbers of input: 16
Maximum inputs applicable at once: No limit (at 24 V DC)
Sensor excitation: 24 V DC ±10 %; ripple 5 %p-p max.,
≤ 2 A (including discrete input load charge)
ON voltage / current: ≥ 15 V DC (X0 to X15 input terminal to COM) / ≥ 3.5 mA
OFF voltage / current: ≤ 5 V DC (X0 to X15 input terminal to COM) / ≤ 1.0 mA
Input current: ≤ 5.5 mA per point at 24 V DC
Input resistance: Approx. 4.4 kΩ
ON delay: ≤ 0.2 msec.
OFF delay: ≤ 0.5 msec.

INSTALLATION

Current consumption
DC: Approx. 70 mA
 (contact I/O load charge is not included)
Operating temperature: -10 to +55°C (14 to 131°F)
Storage temperature: -20 to +65°C (-4 to +149°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Surface or DIN rail (35 mm rail)
Weight: 170 g (0.37 lb)

PERFORMANCE

Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute
(input or exc. supply to EtherNet/IP or FE to power)

STANDARDS & APPROVALS

EU conformity:
EMC Directive 
  EMI EN 61000-6-4
  EMS EN 61000-6-2
RoHS Directive

PC CONFIGURATOR

The following parameters can be set with using PC Configurator Software (model: R7CFG)
Refer to the users manual for the R7CFG for detailed operation of the software program.

EXTERNAL VIEW

TERMINAL ASSIGNMENTS

■ SENSOR EXC. / INPUT CONNECTION
■ POWER SUPPLY TERMINAL ASSIGNMENT

I/O DATA DESCRIPTIONS

EXTERNAL DIMENSIONS unit: mm [inch]

MOUNTING REQUIREMENTS unit: mm [inch]

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM

Note: In order to improve EMC performance, bond the FE terminal to ground.
Caution: FE terminal is NOT a protective conductor terminal.