ES-6604 Rev.17

60D

Field Network Modules 60-UNIT Series

ANALOG I/O MODULE

(DeviceNet)
Functions & Features
• Interfacing analog I/O signals from/to 10-RACK or 18-RACK modules with DeviceNet
• Saving power and I/O wiring inside an instrumentation panel

MODEL: 60D-[1][2]-[3][4]

ORDERING INFORMATION

• Code number: 60D-[1][2]-[3][4]
Specify a code from below for each of [1] through [4].
  (e.g. 60D-161-K/Q)
• Specify the specification for option code /Q
  (e.g. /C01/S01)

[1] NO. OF CHANNELS

04: 4 points
08: 8 points
16: 16 points

[2] I/O TYPE

1: Input
2: Output

[3] POWER INPUT

AC Power
K: 85 – 132 V AC
(Operational voltage range 85 – 132 V, 47 – 66 Hz)
(CE not available)
DC Power
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)

[4] OPTIONS

blank: none
/Q: With options (specify the specification)

SPECIFICATIONS OF OPTION: Q (multiple selections)

COATING (For the detail, refer to our web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating
TERMINAL SCREW MATERIAL
/S01: Stainless steel

RELATED PRODUCTS

•Special cable (model: MCN34)
• Programming Unit (model: PU-2x)

GENERAL SPECIFICATIONS

Construction: Plug-in
Connection
  DeviceNet
: Euro type connector terminal (applicable
  wire size: 0.2 to 2.5 mm2, stripped length 7 mm)
  I/O: 34-pin connector (Omron XG4A-3434)
  Power input: M3.5 screw terminal
Screw terminal: Chromated steel (standard) or stainless steel
Housing material: Flame-resistant resin (black)
Isolation: I/O to DeviceNet to power to FG1
Power indicator: Green LED turns on with power supplied.

DeviceNet COMMUNICATION

Transmission cable: Approved for DeviceNet
Node address setting: DIP switch; 00 – 63
Baud rate setting: DIP switch
MS (Module Status) indicator: Bi-color (green/red) LED indicates device status.
NS (Network Status) indicator: Bi-color (green/red)
LED indicates status of the communication link.

INPUT SPECIFICATIONS

■ Analog Input
Input range
: 1 – 5 V DC 
Input resistance: ≥ 1 MΩ
10-RACK and 18-RACK I/O modules must be isolated types. Non-isolated modules such as 10BW and 18BW are not usable.
A/D conversion output: 16-bit binary
Signal range 0 – 100 % is converted into hexadecimal 0000 – 1770 (0 – 6000). -15 to 0 % is represented by 2’s complements.
Overall range is represented by hexadecimal FC7C – 1AF4
 (-900 – +6900), for -15 – +115 %.
Note: In the firmware version 3.00 or later, analog input range 0 – 100% can be converted into hexadecimal 0000 – 2710 (0 – 10000).
In addition, negative values of analog input range -15 to 0% can be converted into signed absolute values.
Refer to the instruction manual for details.

OUTPUT SPECIFICATIONS

■ Analog Output
Output must be isolated with signal conditioners.
When the transmission line is open, the last value sampled before failure is held.
Output range: 1 – 5 V DC
Load resistance: 20 kΩ minimum
10-RACK and 18-RACK I/O modules must be isolated types. Non-isolated modules such as 10BW and 18BW are not usable.
D/A conversion output: 16-bit binary
Signal range 0 – 100 % is converted into hexadecimal
0000 – 1770 (0 – 6000). -15 to 0 % is represented by 2’s complements.
Overall range is represented by hexadecimal FC7C – 1AF4
(-900 – +6900), for -15 – +115 %.
Note: In the firmware version 3.00 or later, analog output range 0 – 100% can be converted into hexadecimal 0000 – 2710 (0 – 10000).
In addition, negative values of analog output range -15 to 0% can be converted into signed absolute values.
Refer to the instruction manual for details.

INSTALLATION

Power consumption
•AC: Approx. 4 VA
•DC: Approx. 4 W (160 mA)
Supply voltage to network: 11 – 25 V DC supplied through the network terminal block
Supply current to network: 60 mA max. @  24 V
Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Surface or DIN rail
Weight: 450 g (0.99 lb)

PERFORMANCE in percentage of span

A/D conversion: ±0.1 %
D/A conversion: ±0.1 %
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)
Permissible power failure duration (AC power): ≤ 10 msec.
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute (input or output to DeviceNet to power)
2000 V AC @ 1 minute (input or output or DeviceNet or power to FG1)

STANDARDS & APPROVALS

EU conformity:
EMC Directive 
  EMI EN 61000-6-4
  EMS EN 61000-6-2
RoHS Directive

EXTERNAL VIEW

EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM

Note: In order to improve EMC performance, bond the FG1 terminal to ground.
Caution: FG1 terminal is NOT a protective conductor terminal.