ES-6610 Rev.5

60F

Field Network Modules 60-UNIT Series

ANALOG I/O MODULE

(Fuji Electric T-Link use)
Functions & Features
• Interfacing analog I/O signals from/to 10-RACK or 18-RACK modules with T-Link
• Saving power and I/O wiring inside an instrumentation panel

MODEL: 60F-16[1]-[2][3]

ORDERING INFORMATION

• Code number: 60F-16[1]-[2][3]
Specify a code from below for each of [1] through [3].
  (e.g. 60F-161-K/Q)
• Specify the specification for option code /Q
  (e.g. /C01/S01)

NO. OF CHANNELS

16: 16 points

[1] I/O TYPE

1: Input
2: Output

[2] POWER INPUT

AC Power
K: 85 – 132 V AC
(Operational voltage range 85 – 132 V, 47 – 66 Hz)
DC Power
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)

[3] OPTIONS

blank: none
/Q: With options (specify the specification)

SPECIFICATIONS OF OPTION: Q (multiple selections)

COATING (For the detail, refer to our web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating
TERMINAL SCREW MATERIAL
/S01: Stainless steel

RELATED PRODUCTS

•Special cable (model: MCN34)

GENERAL SPECIFICATIONS

Construction: Plug-in
Connection
  T-Link
: Euro type connector terminal (applicable wire size:
  0.2 to 2.5 mm2, stripped length 7 mm)
  I/O: 34-pin connector (Omron XG4A-3434)
  Power input: M3.5 screw terminal
Screw terminal: Chromated steel (standard) or stainless steel
Housing material: Flame-resistant resin (black)
Isolation: I/O to T-Link to power to FG1
Power indicator: Green LED turns on with power supplied.

T-Link SPECIFICATIONS

Configuration: Multi-drop
Communication: Half-duplex
Baud rate: 500 kbps
Transmission media/distance:
  KPEV-SB 0.75 mm2 × 1 pair, 700 m
  T-KPEV-SB, 1.25 mm2 × 1 pair, 1000 m
Station No.: Rotary switch; 00 - 99
(Factory default setting: 00)
L RUN indicator: Red LED ON at normal communication
L ERR. indicator: Red LED ON/blinking at communication abnormality
L I/O indicator: Red LED blinking at normal I/O
L COM indicator: RED LED blinking at T-Link normal communication
■ NUMBER OF CONNECTABLE UNITS WITH T-Link
Up to a maximum of 32 T-Link devices can be connected in a single T-Link system. There is a limit of 100 words in processor memory. Make sure that the configured word area to be occupied does not exceed the 100-word range.
(According to the Fuji Electric MICREX-F Users Manual)
It is necessary to consider these criteria when connecting to this device.
The below describes the number of words occupied per device by number of modules.
• For input 16 / output 16 modules: 16

INPUT SPECIFICATIONS

■ Analog Input
Input range
: 1 – 5 V DC 
Input resistance: ≥ 1 MΩ
10-RACK and 18-RACK I/O modules must be isolated types. Non-isolated modules such as 10BW and 18BW are not usable.
A/D conversion output: Signed binary
Signal range 0 – 100 % is converted into hexadecimal 0000 – 2710 (0 – 10000). -15 to 0 % is a negative range represented by 2's complements.
Overall range is represented by hexadecimal FA24 – 2CEC
(-1500 – +11500), for -15 – +115 %.

OUTPUT SPECIFICATIONS

■ Analog Output
Output must be isolated with signal conditioners.
When the transmission line is open, the last value sampled before failure is held.
Output range: 1 – 5 V DC
Load resistance: 20 kΩ minimum
10-RACK and 18-RACK I/O modules must be isolated types. Non-isolated modules such as 10BW and 18BW are not usable.
D/A conversion output: Signed binary
Signal range 0 – 100 % is converted into hexadecimal 0000 – 2710 (0 – 10000). -15 to 0 % is a negative range represented by 2's complements.
Overall range is represented by hexadecimal FA24 – 2CEC
(-1500 – +11500), for -15 – +115 %.

INSTALLATION

Power consumption
•AC: Approx. 3 VA
•DC: Approx. 4 W (160 mA)
Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Surface or DIN rail
Weight: 450 g (0.99 lb)

PERFORMANCE in percentage of span

A/D conversion: ±0.1 %
D/A conversion: ±0.1 %
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)
Permissible power failure duration (AC power): ≤ 10 msec.
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute (input or output to T-Link to power)
2000 V AC @ 1 minute (input or output or T-Link or power to FG1)

EXTERNAL VIEW

EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM