ES-5542 Rev.0
W2YPD
Space-saving Dual Output Signal Conditioners
Mini-MW Series
RS-422 PULSE ISOLATOR
Functions & Features
• Converts RS-422 line driver pulse to open collector pulse
• High-density mounting
MODEL: W2YPD–J[1][2][3][4]-[5][6]
ORDERING INFORMATION
• Code number: W2YPD-J[1][2][3][4]-[5][6]
Specify a code from below for each of [1] through [6].
(e.g. W2YPD-J26RN-M2/CE/Q)
• Specify the specification for option code /Q
(e.g. /C01/S01)
INPUT
J
: RS-422 line driver pulse
[1] OUTPUT 1
1
: Open collector (max. frequency 100 kHz)
2
: 3.3 V pulse (max. frequency 200 kHz)
3
: 5 V pulse (max. frequency 200 kHz)
4
: 10 V pulse (max. frequency 200 kHz)
5
: 12 V pulse (max. frequency 200 kHz)
[2] OUTPUT 2
Y
: None
1
: Open collector (max. frequency 100 kHz)
2
: 3.3 V pulse (max. frequency 200 kHz)
3
: 5 V pulse (max. frequency 200 kHz)
4
: 10 V pulse (max. frequency 200 kHz)
5
: 12 V pulse (max. frequency 200 kHz)
6
: RS-422 line driver pulse (max. frequency 200 kHz)
[3] OUTPUT 1 LOGIC
N
: The same as the input
R
: Inverted
[4] OUTPUT 2 LOGIC
N
: The same as the input
R
: Inverted
Y
: None
[5] POWER INPUT
AC Power
M2
: 100 – 240 V AC (Operational voltage range 85 – 264 V,
47 – 66 Hz)
DC Power
R
: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
P
: 110 V DC
(Operational voltage range 85 – 150 V, ripple 10 %p-p max.)
[6] OPTIONS (multiple selections)
Standards & Approvals (must be specified)
/CE
: CE marking
Other Options
blank
: none
/Q
: Option other than the above (specify the specification)
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
TERMINAL SCREW MATERIAL
/S01
: Stainless steel
GENERAL SPECIFICATIONS
Construction
: Plug-in
Connection
: M3 screw terminals (torque 0.8 N·m)
Screw terminal
: Chromated steel (standard) or stainless steel
Housing material
: Flame-resistant resin (black)
Isolation
: Input to output 1 to output 2 to power
Frequency range
: Input and output are the same.
INPUT SPECIFICATIONS
■
RS-422 Line Driver Pulse
Maximum frequency
: 200 kHz
Receiver
: Conforms to RS-422
(No receiving resistor incorporated)
OUTPUT SPECIFICATIONS
■
Open collector
Max. frequency
: 100 kHz
Rating
: 40 V DC @ 100 mA
Saturation voltage
: 0.5 V DC
■
Voltage Pulse
Maximum frequency
: 200 kHz
High level
: Rating (3.3, 5, 10 or 12 V) ±20 %
Low level
: ≤ 0.5V
Load resistance
:
≥ 660 Ω for 3.3 V
≥ 1 kΩ for 5 V
≥ 2.0 kΩ for 10 V
≥ 2.4 kΩ for 12 V
■
RS-422 Line Driver Pulse
: Conforms to RS-422
Max. frequency
: 200 kHz
Output current
: ±20 mA
INSTALLATION
Power Consumption
•
AC
:
≤ 5 VA at 100 V
≤ 6 VA at 200 V
≤ 7 VA at 264 V
•
DC
: ≤ 3 W
Operating temperature
: -5 to +55°C (23 to 131°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Mounting
: Surface or DIN rail
Weight
: 200 g (0.44 lb)
PERFORMANCE
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 2000 V AC @ 1 minute (input to output
1 to output 2 to power to ground)
STANDARDS & APPROVALS
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
Low Voltage Directive
EN 61010-1
Measurement Category II (output)
Installation Category II (power)
Pollution Degree 2
Input or output 1 or output 2 to power input:
Reinforced insulation (300 V)
Input to output 1 to output 2: Basic insulation (300 V)
RoHS Directive
OUTPUT LOGIC
Applicable for both Output 1 and 2.
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM