ES-7801-R Rev.0

R7C-CT4E

Remote I/O R7 Series

CC-Link I/O MODULE

(CC-Link V.1.10; AC current input, 4 points, isolated, RMS sensing, clamp-on current sensor CLSE use)
Functions & Features
• 4 points AC current I/O module for CC-Link
• Extension module can be connected
• Input range can be selected with the front DIP switches for all channels.
• Individual channels, zero adjustment, span adjustment, and scaling can be set with the configurator software (model: R7CON)
 

MODEL:R7C–CT4E-R[1]

ORDERING INFORMATION

• Code number: R7C-CT4E-R[1]
Specify a code from below for [1].
  (e.g. R7C-CT4E-R/Q)
• Specify the specification for option code /Q
  (e.g. /C01)
If you need factory setting, use Ordering Information Sheet (No. ESU-7801-R). 

I/O TYPE

CT4E: AC current input, 4 points,
clamp-on current sensor CLSE use

POWER INPUT

DC Power
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)

[1] OPTIONS

blank: none
/Q: With options (specify the specification)

SPECIFICATIONS OF OPTION: Q

COATING (For the detail, refer to our web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating

RELATED PRODUCTS

• PC Configurator cable (model: MCN-CON or COP-US)
• PC configurator software (model: R7CON)
• CSP+ file
The configurator software and CSP+ file are downloadable at our web site.
CSP+ file is also downloadable at CC-Link Partner Association's web site.
• Clamp-on current sensor (model: CLSE)
The clamp-on current sensors, not included in this product package, must be ordered separately. Required number depends upon the system configuration.
• Discrete input extension module (model: R7C-EAx)
• Discrete output extension module (model: R7C-ECx)

PACKAGE INCLUDES...

• Terminating resistor (110 Ω, 0.5 W)

GENERAL SPECIFICATIONS

Connection: M3 separable screw terminal (torque 0.5 N·m)
Solderless terminal: Refer to the drawing at the end of the section.
   Recommended manufacturer: Japan Solderless Terminal MFG.Co.Ltd, Nichifu Co.,ltd 
  Applicable wire size: 0.25 to 1.65 mm2 (AWG 22 to 16)
Screw terminal: Nickel-plated steel
Housing material: Flame-resistant resin (gray)
Isolation: Input 0 to input 1 to input 2 to input 3 to power to CC-Link or FG
Input waveform
  RMS sensing: Up to 15 % of 3rd harmonic content
Zero adjustments: Configurable via R7CON
Span adjustments: Configurable via R7CON
Input range: Selectable with the DIP SW on the front of the unit or configurable via R7CON
Extension: No extension (*), Discrete input 8 or 16 points, Discrete output 8 or 16 points
Selectable with the front DIP SW
(*) Factory default setting
Conversion rate: Selectable with the front DIP SW
Status indicator LED: PWR
Configurator connection: 2.5 dia. miniature jack
■Recommended solderless terminal

CC-Link COMMUNICATION

CC-Link: Ver.1.10
Connector: M3 screw terminal
Network cable: CC-Link cable designated by Mitsubishi Electric
Station number: 1 - 64 (rotary switch, default:00)
Station Type: Remote device
Data allocation: 1
Baud rate setting: 156 kbps (default), 625 kbps, 2.5 Mbps,
5 Mbps, 10 Mbps (rotary switch)
Status indicator LEDs: RUN, ERR, SD, RD

INPUT SPECIFICATIONS

Input range (Optional)
  CLSE-R5: 0 – 5 A AC
  CLSE-05: 0 – 50 A AC
  CLSE-10: 0 – 100 A AC
  CLSE-20: 0 – 200 A AC
  CLSE-40: 0 – 400 A AC
  CLSE-60: 0 – 600 A AC (*)
(*) Factory setting
Frequency: 50 / 60 Hz (45 - 65 Hz)
Operational range: 5 – 115 % of rating (Operational range for the CLSE-60 is limited up to approx. 109 % (65535).)
Overload capacity: 120 % of rating (continuous)
Note: Use in the circuits below 480 V.

INSTALLATION

Current consumption
DC: Approx. 140 mA
Operating temperature: -10 to +55°C (14 to 131°F)
Storage temperature: -20 to +65°C (-4 to +149°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: DIN rail (35 mm rail)
Weight: 200 g (0.44 lb)

PERFORMANCE

Conversion rate / conversion accuracy:
10 msec./±2.0 %, 20 msec./±1.0 %, 40 msec./±0.5 %,
80 msec./±0.5 % (*)
(*) Factory setting
(The conversion accuracy does not include the accuracy of the sensor)
Data range: Engineering unit value (A) × 100 (integer)
 (For CLSE-R5, engineering unit value (A) × 1000 (integer))
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)
Response time: ≤ 1.0 sec. (0 – 90 %)
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute (input 0 to input 1 to input 2 to input 3 to power to CC-Link or FG)

STANDARDS & APPROVALS

EU conformity:
EMC Directive 
  EMI EN 61000-6-4
  EMS EN 61000-6-2
RoHS Directive

EXTERNAL VIEW

COMMUNICATION CABLE CONNECTIONS

TERMINAL ASSIGNMENTS

■ INPUT TERMINAL ASSIGNMENT

INDICATOR LED

DATA CONVERSION

■ ENGINEERING UNIT CONVERSION
Integer obtained by multiplying engineering unit value (A) by 100 is represebted in 16-bit.
(For CLSE-R5, integer obtained by multiplying engineering unit value (A) by 1000.)

DATA ALLOCATION

I/O DATA DESCRIPTIONS

EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM

Note: In order to improve EMC performance, bond the FG terminal to ground.
Caution: FG terminal is NOT a protective conductor terminal.