ES-7801-N Rev.0

R7C-EA8

Remote I/O R7 Series

CC-Link I/O MODULE

(CC-Link V.1.10; discrete input for extension, 8 points)
Functions & Features
• 8 points discrete input extension module connected to CC-Link I/O module (model: R7C)
 

MODEL:R7C–EA8[1]

ORDERING INFORMATION

• Code number: R7C-EA8[1]
Specify a code from below for [1].
  (e.g. R7C-EA8/Q)
• Specify the specification for option code /Q
  (e.g. /C01)

I/O TYPE

EA8: Discrete input for extension, 8 points

[1] OPTIONS

blank: none
/Q: With options (specify the specification)

SPECIFICATIONS OF OPTION: Q

COATING (For the detail, refer to our web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating

GENERAL SPECIFICATIONS

Connection: M3 separable screw terminal (torque 0.5 N·m)
Solderless terminal: Refer to the drawing at the end of the section.
   Recommended manufacturer: Japan Solderless Terminal MFG.Co.Ltd, Nichifu Co.,ltd 
  Applicable wire size: 0.25 to 1.65 mm2 (AWG 22 to 16)
Screw terminal: Nickel-plated steel
Housing material: Flame-resistant resin (gray)
Isolation: Input to internal circuits
Discrete input status indicator LED: LED turns on with input ON
■Recommended solderless terminal

INPUT SPECIFICATIONS

Common: Positive or negative common (NPN/PNP) per 8 points
Maximum inputs applicable at once: No limit (at 24 V DC)
Rated input voltage: 24 V DC ±10 %; ripple 5 %p-p max.
ON voltage / current: ≥ 15 V DC (input – COM) / ≥ 3.5 mA
OFF voltage / current: ≤ 5 V DC (input – COM) / ≤ 1 mA
Input current: ≤ 5.5 mA per point at 24 V DC
Input resistance: Approx. 4.4 kΩ
ON delay: ≤ 2.0 msec.
OFF delay: ≤ 2.0 msec.

INSTALLATION

Current consumption
DC: Approx. 10 mA
Operating temperature: -10 to +55°C (14 to 131°F)
Storage temperature: -20 to +65°C (-4 to +149°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: DIN rail (35 mm rail)
Weight: 90 g (0.2 lb)

PERFORMANCE

Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute (input to internal circuits)

STANDARDS & APPROVALS

EU conformity:
EMC Directive 
  EMI EN 61000-6-4
  EMS EN 61000-6-2
RoHS Directive

EXTERNAL VIEW

TERMINAL ASSIGNMENTS

■ INPUT TERMINAL ASSIGNMENT

EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]