ES-7801-E Rev.0
R7C-YS2
Remote I/O R7 Series
CC-Link I/O MODULE
(CC-Link V.1.10; DC current output, 2 points, isolated)
Functions & Features
• 2 points DC current output module for CC-Link
• Extension module can be connected
• Individual channels, zero adjustment, span adjustment, and scaling can be set with the configurator software (model: R7CON)
MODEL:R7C–YS2-R[1]
ORDERING INFORMATION
• Code number: R7C-YS2-R[1]
Specify a code from below for [1].
(e.g. R7C-YS2-R/Q)
• Specify the specification for option code /Q
(e.g. /C01)
If you need factory setting, use Ordering Information Sheet (No. ESU-7801-E).
I/O TYPE
YS2
: DC current output, 2 points
POWER INPUT
DC Power
R
: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
[1] OPTIONS
Standards & Approvals
blank
: CE marking
/UL
: UL approval, CE marking
Other Options
blank
: none
/Q
: Option other than the above (specify the specification)
(UL not available)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
RELATED PRODUCTS
• PC Configurator cable (model: MCN-CON or COP-US)
• PC configurator software (model: R7CON)
Downloadable at our web site.
• Discrete input extension module (model: R7C-EAx)
• Discrete output extension module (model: R7C-ECx)
PACKAGE INCLUDES...
• Terminating resistor (110 Ω, 0.5 W)
GENERAL SPECIFICATIONS
Connection:
M3 separable screw terminal (torque 0.5 N·m)
Solderless terminal
: Refer to the drawing at the end of the section.
Recommended manufacturer
: Japan Solderless Terminal MFG.Co.Ltd, Nichifu Co.,ltd
Applicable wire size
: 0.25 to 1.65 mm
2
(AWG 22 to 16)
Screw terminal
: Nickel-plated steel
Housing material
: Flame-resistant resin (gray)
Isolation
: Output 0 to output 1 to power to CC-Link or FG
Zero adjustments
: Configurable via R7CON
Span adjustments
: Configurable via R7CON
Extension:
No extension (*), Discrete input 8 or 16 points, Discrete output 8 or 16 points
Selectable with the front DIP SW
(*) Factory default setting
Output at the loss of communication
:
Hold the output (*), Reset the output
Selectable with the front DIP SW
(*) Factory default setting
Status indicator LED
: PWR
Configurator connection
: 2.5 dia. miniature jack
■Recommended solderless terminal
CC-Link COMMUNICATION
CC-Link:
Ver.1.10
Connector
: M3 screw terminal
Network cable
: CC-Link cable designated by Mitsubishi Electric
Station number
: 1 - 64 (rotary switch, default:00)
Station Type
: Remote device
Data allocation
: 1
Baud rate setting
: 156 kbps (default), 625 kbps, 2.5 Mbps,
5 Mbps, 10 Mbps (rotary switch)
Status indicator LEDs
: RUN, ERR, SD, RD
OUTPUT SPECIFICATIONS
Output range
: 4 to 20 mA DC
Load resistance
: ≤ 600 Ω
Operational range
: -15 to +115 % of output range
INSTALLATION
Current consumption
•
DC
: Approx. 140 mA
Operating temperature
: -10 to +55°C (14 to 131°F)
Storage temperature
: -20 to +65°C (-4 to +149°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Atmosphere
: No corrosive gas or heavy dust
Mounting
: DIN rail (35 mm rail)
Weight
: 180 g (0.40 lb)
PERFORMANCE
Conversion accuracy
: ±0.1 %
Data range
: 0 – 10000 of the output range
(Scaling of converted data is configurable with the configurator software (model: R7CON))
Temp. coefficient
: ±0.015 %/°C (±0.008 %/°F)
Response time
: 250 msec. (0 – 90 %)
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 1500 V AC @ 1 minute (output 0 to output 1 to power to CC-Link or FG)
STANDARDS & APPROVALS
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
Approval
:
UL/C-UL nonincendive Class I, Division 2,
Groups A, B, C, and D
(ANSI/UL 121201, CAN/CSA-C22.2 No.213-17)
UL/C-UL general safety requirements
(UL 61010-1, CAN/CSA-C22.2 No.61010-1)
Note: This equipment is to be supplied by a Class 2 power supply when using as conformity with UL/C-UL.
FUNCTIONS
Output hold function:
Output at the loss of communication is selectable from output clear (fix the output at -15 %) and output hold (last normally received data) with DIP switch.
At the startup, it outputs -15 % until the communication is established and normal data is received.
EXTERNAL VIEW
COMMUNICATION CABLE CONNECTIONS
TERMINAL ASSIGNMENTS
■OUTPUT TERMINAL ASSIGNMENT
INDICATOR LED
DATA CONVERSION
DATA ALLOCATION
I/O DATA DESCRIPTIONS
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
Note: In order to improve EMC performance, bond the FG terminal to ground.
Caution: FG terminal is NOT a protective conductor terminal.