ES-8451 Rev.0
R3-NEIP2
Remote I/O R3 Series
EtherNet/IP INTERFACE MODULE
Functions & Features
• Converts analog and discrete I/O data to the open network fieldbus (EtherNet/IP)
Typical Applications
• Remote I/O for DCS and PLC
MODEL:R3–NEIP2-[1][2]
ORDERING INFORMATION
• Code number: R3-NEIP2-[1][2]
Specify a code from below for each of [1] and [2].
(e.g. R3-NEIP2-R/CE/Q)
• Specify the specification for option code /Q
(e.g. /C01)
[1] POWER INPUT
N:
No power supply
AC Power
M2
: 100 – 240 V AC
(Operational voltage range 85 – 264 V, 47 – 66 Hz)*
(CE not available)
DC Power
R:
24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.) *
* Not selectable for use with independent power modules or network modules with the internal power input options.
[2] OPTIONS (multiple selections)
Standards & Approvals
blank
: Without CE
/CE
: CE marking
Other Options
blank
: none
/Q
: Option other than the above (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
RELATED PRODUCTS
• PC configurator software (model: R3CON)
• EDS file
The configurator software and EDS file are downloadable at our web site.
For connecting to PC, use commercially available Type-C USB cable. (provided by user)
GENERAL SPECIFICATIONS
Connection
Ethernet
: RJ-45 Modular Jack
Internal bus
: Via the Installation Base (model: R3-BSx)
Internal p
ower
: Via the Installation Base (model: R3-BSx)
Power input, RUN contact output
: M3 separable screw terminal (torque 0.5 N·m)
Screw terminal
: Nickel-plated steel
Isolation
: EtherNet/IP to internal bus or internal power to power input to RUN contact output to FG
Input error data setting
: Input value setting at input module error with side DIP SW
Dual communication setting
: Set with the side DIP switch
Data allocation setting
: Set with the side DIP switch
■
RUN CONTACT OUTPUT
RUN contact
: Turns ON when both MS and NS LEDs are green (EtherNet/IP in normal communication).
Rated load
: 250 V AC @ 0.5 A (cos ø = 1)
30 V DC @ 0.5 A (resistive load)
(Less than 50 V AC to conform with EU Directive)
Maximum switching voltage
: 250 V AC or 30 V DC
Maximum switching power
: 250 VA or 150 W
Minimum load
: 1 V DC @ 1 mA
Mechanical life
: 2 × 10
7
cycles (300 cycles/min.)
When driving an inductive load, external contact protection and noise quenching recommended.
EtherNet/IP COMMUNICATION
Conformance test version:
CT21
Communication standard
: IEEE 802.3u
Transmission
: 10BASE-T, 100BASE-TX
Baud rate
: 10/100 Mbps (Auto Negotiation function)
Max. number of socket connections
: 3
Connection type
: Exclusive owner, Listen only, Input only
Protocol
: EtherNet/IP
Transmission media
: 10BASE-T (STP, Category 5) 100BASE-TX (STP, Category 5e)
Max. length of fieldbus segment
: 100 meters
IP address
: 192.168.0.1 (factory setting); Selectable with PC Configurator Software (model: R3CON)
Default gateway:
192.168.0.100 (factory setting); Selectable with PC Configurator Software (model: R3CON)
DLR supported
Port No
.: 2222, 44818
I/O data area size
: Input and output data area size set with side DIP SW
Required data words
:
Input
: 35, 67, 131, 252 words
Output
: 35, 67, 131, 252 words (3 words are used only for status)
Ethernet indicator LED
: TX/RX, LINK
MS (Module Status) indicator
: Bi-color (green/red) LED indicates device status.
NS (Network Status) indicator
: Bi-color (green/red) LED indicates status of the communication link.
INSTALLATION
Power consumption
•
AC
:
Approx. 20 VA at 100 V
Approx. 28 VA at 200 V
•
DC
: Approx. 12 W
Current consumption (no power supply)
: 70 mA
Output current (power supply)
: 280 mA continuous at 20 V DC; 430 mA for 10 minutes
Operating temperature
: -10 to +55°C (14 to 131°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Atmosphere
: No corrosive gas or heavy dust
Mounting
: Installation Base (model: R3-BSx)
Weight
: 200 g (0.44 lb)
PERFORMANCE
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 1500 V AC @ 1 minute
(EtherNet/IP to internal bus or internal power to power input to RUN contact output to FG)
STANDARDS & APPROVALS
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
EXTERNAL VIEW
TRANSMISSION DATA DESCRIPTIONS
MODULE STATUS, ERROR STATUS, DATA ERROR STATUS
I/O DATA DESCRIPTIONS
The data allocations for typical I/O modules are shown below.
Refer to the manual for each module for detailed data allocations.
■ ANALOG DATA (16-bit data, models: R3-SV4, YV4, DS4, YS4, US4, etc.)
■ TEMPERATURE DATA (16-bit data, models: R3-RS4, TS4, US4, etc.)
■ ANALOG DATA (16-bit data, models: R3-CT4A, CT4B, etc.)
■ ACCUMULATED COUNT DATA (32-bit data, models: R3-PA2, PA4A, WT1, WT4, etc.)
■ BCD DATA (32-bit data, models: R3-BA32A, BC32A, etc.)
■ 16-POINT DISCRETE DATA (models: R3-DA16, DC16, etc.)
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
Note: In order to improve EMC performance, bond the FG terminal to ground.
Caution: FG terminal is NOT a protective conductor terminal.
SYSTEM CONFIGURATION EXAMPLES