ES-7801-AC Rev.1

R7C-RR4

Remote I/O R7 Series

CC-Link I/O MODULE

(CC-Link V.1.10; remote control relay control, 4 points)
Functions & Features
• 4 points remote control relay control module for CC-Link
 

MODEL:R7C–RR4–[1][2]

ORDERING INFORMATION

• Code number: R7C-RR4-[1][2]
Specify a code from below for each of [1] and [2].
  (e.g. R7C-RR4-AR/Q)
• Specify the specification for option code /Q
  (e.g. /C01)
If you need factory setting, use Ordering Information Sheet (No. ESU-7801-AC). 

I/O TYPE

RR4: Remote control relay control, 4 points

[1] POWER INPUT

DC Power
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
Universal
AR: 24 V AC/24 V DC (universal)
(Operational voltage range 24 V AC±10 %, 50 - 60 Hz /
 24 V DC±10 %, ripple 10 %p-p max.)

[2] OPTIONS

blank: none
/Q: With options (specify the specification)

SPECIFICATIONS OF OPTION: Q

COATING (For the detail, refer to our web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating

CAUTION

• Extension modules cannot be connected.

RECOMMENDED PRODUCTS (OPERATION CHECKED)

Remote control relay:
BR-12D, BR-22D (Mitsubishi Electric)
WR6165 (Panasonic)
Remote control transformer:
BRT-10B, BRT-20B (Mitsubishi Electric)
WR2301 (Panasonic)
Remote control switch
WR8501 (Panasonic)

GENERAL SPECIFICATIONS

Connection: M3 separable screw terminal (torque 0.5 N·m)
Solderless terminal: Refer to the drawing at the end of the section.
   Recommended manufacturer: Japan Solderless Terminal MFG. Co., Ltd., Nichifu Co., Ltd.
  Applicable wire size: 0.25 to 1.65 mm2 (AWG 22 to 16)
Screw terminal: Nickel-plated steel
Housing material: Flame-resistant resin (gray)
Isolation: Output to power to CC-Link or FG
Status indicator LED: PWR
I/O status indicator: Feedback input status turns on with the input supplied.
Output status LED turns on with the output ON.
■Recommended solderless terminal

CC-Link COMMUNICATION

CC-Link: Ver.1.10
Connector: M3 screw terminal
Network cable: CC-Link cable designated by Mitsubishi Electric
Station number: 1 - 64 (rotary switch, default: 00)
Station type: Remote I/O device
Data allocation: 1
Baud rate setting: 156 kbps (default), 625 kbps, 2.5 Mbps,
5 Mbps, 10 Mbps (rotary switch)
Terminating resistor: Built-in (side DIP SW, default: disable)
Status indicator LEDs: RUN, ERR, SD, RD

OUTPUT SPECIFICATIONS

Common: 1 common per 4 points (4 terminals)
Maximum outputs applicable at once: No limit
Rated load voltage: 24 V AC ±10 % (supplied by the remote control transformer)
Load voltage frequency: 50 / 60 Hz

INSTALLATION

Current consumption
AC: Approx. 100 mA
DC: Approx. 65 mA
Operating temperature: -10 to +55°C (14 to 131°F)
Storage temperature: -20 to +65°C (-4 to +149°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: DIN rail (35 mm rail)
Weight: 170 g (0.37 lb)

PERFORMANCE

Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute (output to CC-Link or FG to power)

EXTERNAL VIEW

COMMUNICATION CABLE CONNECTIONS

TERMINAL ASSIGNMENTS

■OUTPUT TERMINAL ASSIGNMENT

INDICATOR LED

DATA ALLOCATION

I/O DATA DESCRIPTIONS

EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM

Caution: FG terminal is NOT a protective conductor terminal.