ES-7801-AC Rev.1
R7C-RR4
Remote I/O R7 Series
CC-Link I/O MODULE
(CC-Link V.1.10; remote control relay control, 4 points)
Functions & Features
• 4 points remote control relay control module for CC-Link
MODEL:R7C–RR4–[1][2]
ORDERING INFORMATION
• Code number: R7C-RR4-[1][2]
Specify a code from below for each of [1] and [2].
(e.g. R7C-RR4-AR/Q)
• Specify the specification for option code /Q
(e.g. /C01)
If you need factory setting, use Ordering Information Sheet (No. ESU-7801-AC).
I/O TYPE
RR4:
Remote control relay control, 4 points
[1] POWER INPUT
DC Power
R
: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
Universal
AR
: 24 V AC/24 V DC (universal)
(Operational voltage range 24 V AC±10 %, 50 - 60 Hz /
24 V DC±10 %, ripple 10 %p-p max.)
[2] OPTIONS
blank
: none
/Q
: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
CAUTION
• Extension modules cannot be connected.
RECOMMENDED PRODUCTS (OPERATION CHECKED)
Remote control relay:
BR-12D, BR-22D (Mitsubishi Electric)
WR6165 (Panasonic)
Remote control transformer:
BRT-10B, BRT-20B (Mitsubishi Electric)
WR2301 (Panasonic)
Remote control switch
WR8501 (Panasonic)
GENERAL SPECIFICATIONS
Connection:
M3 separable screw terminal (torque 0.5 N·m)
Solderless terminal
: Refer to the drawing at the end of the section.
Recommended manufacturer
: Japan Solderless Terminal MFG. Co., Ltd., Nichifu Co., Ltd.
Applicable wire size
: 0.25 to 1.65 mm
2
(AWG 22 to 16)
Screw terminal
: Nickel-plated steel
Housing material
: Flame-resistant resin (gray)
Isolation
: Output to power to CC-Link or FG
Status indicator LED
: PWR
I/O status indicator
: Feedback input status turns on with the input supplied.
Output status LED turns on with the output ON.
■Recommended solderless terminal
CC-Link COMMUNICATION
CC-Link:
Ver.1.10
Connector
: M3 screw terminal
Network cable
: CC-Link cable designated by Mitsubishi Electric
Station number
: 1 - 64 (rotary switch, default: 00)
Station type
: Remote I/O device
Data allocation
: 1
Baud rate setting
: 156 kbps (default), 625 kbps, 2.5 Mbps,
5 Mbps, 10 Mbps (rotary switch)
Terminating resistor:
Built-in (side DIP SW, default: disable)
Status indicator LEDs
: RUN, ERR, SD, RD
OUTPUT SPECIFICATIONS
Common
: 1 common per 4 points (4 terminals)
Maximum outputs applicable at once
: No limit
Rated load voltage
: 24 V AC ±10 % (supplied by the remote control transformer)
Load voltage frequency
: 50 / 60 Hz
INSTALLATION
Current consumption
•
AC
: Approx. 100 mA
•
DC
: Approx. 65 mA
Operating temperature
: -10 to +55°C (14 to 131°F)
Storage temperature
: -20 to +65°C (-4 to +149°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Atmosphere
: No corrosive gas or heavy dust
Mounting
: DIN rail (35 mm rail)
Weight
: 170 g (0.37 lb)
PERFORMANCE
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 1500 V AC @ 1 minute (output to CC-Link or FG to power)
EXTERNAL VIEW
COMMUNICATION CABLE CONNECTIONS
TERMINAL ASSIGNMENTS
■OUTPUT TERMINAL ASSIGNMENT
INDICATOR LED
DATA ALLOCATION
I/O DATA DESCRIPTIONS
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
Caution: FG terminal is NOT a protective conductor terminal.