ES-7801-AD Rev.1

R7C-YV4

Remote I/O R7 Series

CC-Link I/O MODULE

(CC-Link V.1.10; DC voltage output, 4 points, isolated)
Functions & Features
• 4 points DC voltage output module for CC-Link
• Output range can be selected with the front DIP switches for all channels
• Individual channels, zero adjustment, span adjustment, and scaling can be set with the configurator software (model: R7CON)
 

MODEL:R7C–YV4–[1][2]

ORDERING INFORMATION

• Code number: R7C-YV4-[1][2]
Specify a code from below for each of [1] and [2].
  (e.g. R7C-YV4-AR/Q)
• Specify the specification for option code /Q
  (e.g. /C01)
If you need factory setting, use Ordering Information Sheet (No. ESU-7801-AD). 

I/O TYPE

YV4: DC voltage output, 4 points

[1] POWER INPUT

DC Power
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
Universal
AR: 24 V AC/24 V DC (universal)
(Operational voltage range 24 V AC±10 %, 50 - 60 Hz /
 24 V DC±10 %, ripple 10 %p-p max.)
(CE not available)

[2] OPTIONS

blank: none
/Q: With options (specify the specification)

SPECIFICATIONS OF OPTION: Q

COATING (For the detail, refer to our web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating

CAUTION

• Extension modules cannot be connected.

RELATED PRODUCTS

• PC Configurator cable (model: MCN-CON or COP-US)
• PC configurator software (model: R7CON)
• CSP+ file
The configurator software and CSP+ file are downloadable at our web site.
CSP+ file is also downloadable at CC-Link Partner Association's web site.

GENERAL SPECIFICATIONS

Connection: M3 separable screw terminal (torque 0.5 N·m)
Solderless terminal: Refer to the drawing at the end of the section.
   Recommended manufacturer: Japan Solderless Terminal MFG. Co., Ltd., Nichifu Co., Ltd.
  Applicable wire size: 0.25 to 1.65 mm2 (AWG 22 to 16)
Screw terminal: Nickel-plated steel
Housing material: Flame-resistant resin (gray)
Isolation: Output 0 to output 1 to output 2 to output 3 to power to CC-Link or FG
Zero adjustments: Configurable via R7CON
Span adjustments: Configurable via R7CON
Output range: Selectable with the front DIP SW or configurable via R7CON
Output at the loss of communication:
Hold the output (*), Reset the output
Selectable with the front DIP SW
(*) Factory default setting
Status indicator LED: PWR
Configurator connection: 2.5 dia. miniature jack
■Recommended solderless terminal

CC-Link COMMUNICATION

CC-Link: Ver.1.10
Connector: M3 screw terminal
Network cable: CC-Link cable designated by Mitsubishi Electric
Station number: 1 - 64 (rotary switch, default:00)
Station type: Remote device
Data allocation: 1
Baud rate setting: 156 kbps (default), 625 kbps, 2.5 Mbps,
5 Mbps, 10 Mbps (rotary switch)
Terminating resistor: Built-in (side DIP SW, default: disable)
Status indicator LEDs: RUN, ERR, SD, RD

OUTPUT SPECIFICATIONS

Output range: -10 – +10 V DC (*), -5 – +5 V DC, 0 – 10 V DC,
0 – 5 V DC, 1 – 5 V DC
(*) factory default setting
Load resistance: ≥ 20 kΩ
Operational range
Except -10 to +10 V DC
: -15 to +115 % of output range
-10 to +10 V DC: Approx. -11.5 to +11.5 V DC

INSTALLATION

Current consumption
AC: Approx. 180 mA
DC: Approx. 90 mA
Operating temperature: -10 to +55°C (14 to 131°F)
Storage temperature: -20 to +65°C (-4 to +149°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: DIN rail (35 mm rail)
Weight: 180 g (0.40 lb)

PERFORMANCE

Conversion accuracy: ±0.1 %
Data range: 0 – 10000 of the output range
(Scaling of converted data is configurable with the configurator software (model: R7CON))
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)
Response time: 250 msec. (0 – 90 %)
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute (output 0 to output 1 to output 2 to output 3 to power to CC-Link or FG)

STANDARDS & APPROVALS

EU conformity:
EMC Directive 
  EMI EN 61000-6-4
  EMS EN 61000-6-2
RoHS Directive

FUNCTIONS

Output hold function:
Output at the loss of communication is selectable from output clear (fix the output at -15 % or approx. -11.5 V) and output hold (last normally received data) with DIP switch.
At the startup, it outputs -15 %  or approx. -11.5 V until the communication is established and normal data is received.

EXTERNAL VIEW

COMMUNICATION CABLE CONNECTIONS

TERMINAL ASSIGNMENTS

■OUTPUT TERMINAL ASSIGNMENT

INDICATOR LED

DATA CONVERSION

DATA ALLOCATION

I/O DATA DESCRIPTIONS

EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM

Note: In order to improve EMC performance, bond the FG terminal to ground.
Caution: FG terminal is NOT a protective conductor terminal.