ES-7801-AD Rev.1
R7C-YV4
Remote I/O R7 Series
CC-Link I/O MODULE
(CC-Link V.1.10; DC voltage output, 4 points, isolated)
Functions & Features
• 4 points DC voltage output module for CC-Link
• Output range can be selected with the front DIP switches for all channels
• Individual channels, zero adjustment, span adjustment, and scaling can be set with the configurator software (model: R7CON)
MODEL:R7C–YV4–[1][2]
ORDERING INFORMATION
• Code number: R7C-YV4-[1][2]
Specify a code from below for each of [1] and [2].
(e.g. R7C-YV4-AR/Q)
• Specify the specification for option code /Q
(e.g. /C01)
If you need factory setting, use Ordering Information Sheet (No. ESU-7801-AD).
I/O TYPE
YV4
: DC voltage output, 4 points
[1] POWER INPUT
DC Power
R
: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
Universal
AR
: 24 V AC/24 V DC (universal)
(Operational voltage range 24 V AC±10 %, 50 - 60 Hz /
24 V DC±10 %, ripple 10 %p-p max.)
(CE not available)
[2] OPTIONS
blank
: none
/Q
: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
CAUTION
• Extension modules cannot be connected.
RELATED PRODUCTS
• PC Configurator cable (model: MCN-CON or COP-US)
• PC configurator software (model: R7CON)
• CSP+ file
The configurator software and CSP+ file are downloadable at our web site.
CSP+ file is also downloadable at CC-Link Partner Association's web site.
GENERAL SPECIFICATIONS
Connection:
M3 separable screw terminal (torque 0.5 N·m)
Solderless terminal
: Refer to the drawing at the end of the section.
Recommended manufacturer
: Japan Solderless Terminal MFG. Co., Ltd., Nichifu Co., Ltd.
Applicable wire size
: 0.25 to 1.65 mm
2
(AWG 22 to 16)
Screw terminal
: Nickel-plated steel
Housing material
: Flame-resistant resin (gray)
Isolation
: Output 0 to output 1 to output 2 to output 3 to power to CC-Link or FG
Zero adjustments
: Configurable via R7CON
Span adjustments
: Configurable via R7CON
Output range
: Selectable with the front DIP SW or configurable via R7CON
Output at the loss of communication
:
Hold the output (*), Reset the output
Selectable with the front DIP SW
(*) Factory default setting
Status indicator LED
: PWR
Configurator connection
: 2.5 dia. miniature jack
■Recommended solderless terminal
CC-Link COMMUNICATION
CC-Link
: Ver.1.10
Connector
: M3 screw terminal
Network cable
: CC-Link cable designated by Mitsubishi Electric
Station number
: 1 - 64 (rotary switch, default:00)
Station type
: Remote device
Data allocation
: 1
Baud rate setting
: 156 kbps (default), 625 kbps, 2.5 Mbps,
5 Mbps, 10 Mbps (rotary switch)
Terminating resistor:
Built-in (side DIP SW, default: disable)
Status indicator LEDs
: RUN, ERR, SD, RD
OUTPUT SPECIFICATIONS
Output range
: -10 – +10 V DC (*), -5 – +5 V DC, 0 – 10 V DC,
0 – 5 V DC, 1 – 5 V DC
(*) factory default setting
Load resistance
: ≥ 20 kΩ
Operational range
Except -10 to +10 V DC
: -15 to +115 % of output range
-10 to +10 V DC
: Approx. -11.5 to +11.5 V DC
INSTALLATION
Current consumption
•
AC
: Approx. 180 mA
•
DC
: Approx. 90 mA
Operating temperature
: -10 to +55°C (14 to 131°F)
Storage temperature
: -20 to +65°C (-4 to +149°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Atmosphere
: No corrosive gas or heavy dust
Mounting
: DIN rail (35 mm rail)
Weight
: 180 g (0.40 lb)
PERFORMANCE
Conversion accuracy
: ±0.1 %
Data range
: 0 – 10000 of the output range
(Scaling of converted data is configurable with the configurator software (model: R7CON))
Temp. coefficient
: ±0.015 %/°C (±0.008 %/°F)
Response time
: 250 msec. (0 – 90 %)
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 1500 V AC @ 1 minute (output 0 to output 1 to output 2 to output 3 to power to CC-Link or FG)
STANDARDS & APPROVALS
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
FUNCTIONS
Output hold function:
Output at the loss of communication is selectable from output clear (fix the output at -15 % or approx. -11.5 V) and output hold (last normally received data) with DIP switch.
At the startup, it outputs -15 % or approx. -11.5 V until the communication is established and normal data is received.
EXTERNAL VIEW
COMMUNICATION CABLE CONNECTIONS
TERMINAL ASSIGNMENTS
■OUTPUT TERMINAL ASSIGNMENT
INDICATOR LED
DATA CONVERSION
DATA ALLOCATION
I/O DATA DESCRIPTIONS
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
Note: In order to improve EMC performance, bond the FG terminal to ground.
Caution: FG terminal is NOT a protective conductor terminal.