ES-7799-I Rev.0

R7F4DH-2-DA16A

Remote I/O R7F4D Series

HI-SPEED LINK SYSTEM I/O MODULE

(NPN discrete input, 16 points, MIL connector (type 1))
Functions & Features
• 16 points NPN discrete input module for HLS
HLS is the abbreviation for “Hi-speed Link System” of Step Technica Co., Ltd.
 

MODEL: R7F4DH-2-DA16A-R[1]

ORDERING INFORMATION

• Code number: R7F4DH-2-DA16A-R[1]
Specify a code from below for [1].
  (e.g. R7F4DH-2-DA16A-R/H/Q)
• Specify the specification for option code /Q
  (e.g. /C01)

TERMINAL BLOCK

2: Tension clamp terminal block for power supply
   RJ-45 Modular jack for communication
   MIL connector (type 1) for I/O

I/O TYPE

DA16A: NPN discrete input, 16 points

POWER INPUT

DC Power
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)

[1] OPTIONS (multiple selections)

Communication Mode
blank: Full-duplex
/H: Half-duplex
Other Options
blank: none
/Q: Option other than the above (specify the specification)

SPECIFICATIONS OF OPTION: Q

COATING (For the detail, refer to our web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating

GENERAL SPECIFICATIONS

Connection
  HLS
: RJ-45 Modular Jack
  Power & Sensor excitation: Separable screwless spring
  terminal
  Input: MIL connector
Housing material: Flame-resistant resin (gray)
Isolation: Input or sensor excitation to HLS to power input to FE
Status indicator LED: Power (green) turns on while the power is supplied
Discrete input status indicator LED: Red LED turns on with input ON

HLS COMMUNICATION

Communication mode: Full-duplex or half-duplex
Network cable
Shielded cable
:
Full-duplex communication:
ZHY262PS and ZHT262PS (Shinko Seisen Industry Co., Ltd.) 
Half-duplex communication:
ZHY221PS (Shinko Seisen Industry Co., Ltd.)
Dual shielded cable:
ZHY262PBA (Shinko Seisen Industry Co., Ltd.)
Transmission distance: 
12 Mbps: 100 meters (328 ft)
6 Mbps: 200 meters (656 ft)
3 Mbps: 300 meters (984 ft)
(Configurable with DIP SW; factory setting: 12 Mbps)
Data allocation: 1
Terminating resistor: Built-in (Selected with the DIP SW; factory setting: disabled)
Status indicator LED: Run LED on in normal communication
Station address: Set with rotary switch
(Refer to the instruction manual for details)

INPUT SPECIFICATIONS

Common: Positive common (NPN) per 16 points
Numbers of input: 16 points
Maximum inputs applicable at once: No limit (at 24V DC)
Sensor excitation: 24 V DC ±10 %; ripple 5 %p-p max.,
≤ 2 A (including discrete input load charge); rated current 8 A
ON voltage / current: ≥ 15 V DC (X0 through XF to +24V) / ≥ 3.5 mA
OFF voltage / current: ≤ 5 V DC (X0 through XF to +24V) / ≤ 1 mA
Input current: ≤ 5.5 mA per point at 24 V DC
Input resistance: Approx. 4.4 kΩ
ON delay: ≤ 0.5 msec.
OFF delay: ≤ 0.5 msec.

INSTALLATION

Current consumption
DC: Approx. 25 mA (rated current 8 A)
 (contact I/O load charge is not included)
Operating temperature: -10 to +55°C (14 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Surface or DIN rail (35 mm rail)
Weight: 100 g (0.22 lb)

PERFORMANCE

Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute (input or sensor excitation to HLS to power to FE)

STANDARDS & APPROVALS

Refer to the manuals to comply with the standards.
EU conformity:
EMC Directive 
  EMI EN 61000-6-4
  EMS EN 61000-6-2
RoHS Directive

EXTERNAL VIEW

TERMINAL ASSIGNMENTS

■ INPUT TERMINAL ASSIGNMENT

I/O DATA DESCRIPTIONS

EXTERNAL DIMENSIONS unit: mm [inch]

MOUNTING REQUIREMENTS unit: mm [inch]

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM

Note: In order to improve EMC performance, bond the FE terminal to ground.
Caution: FE terminal is NOT a protective conductor terminal.