ES-7805-E Rev.0

R7ML-YS2

Remote I/O R7 Series

MECHATROLINK I/O MODULE

(DC current output, 2 points, isolated, MECHATROLINK-I / -II use)
Functions & Features
• 2 points DC current output module for MECHATROLINK -I/
-II
• Extension module can be connected
• Individual channels, zero adjustment, span adjustment, and scaling can be set with the configurator software (model: R7CON)
 

MODEL:R7ML–YS2-R[1]

ORDERING INFORMATION

• Code number: R7ML-YS2-R[1]
Specify a code from below for [1].
  (e.g. R7ML-YS2-R/Q)
• Specify the specification for option code /Q
  (e.g. /C01)

I/O TYPE

YS2: DC current output, 2 points

POWER INPUT

DC Power
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)

[1] OPTIONS

blank: none
/Q: With options (specify the specification)

SPECIFICATIONS OF OPTION: Q

COATING (For the detail, refer to our web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating

RELATED PRODUCTS

• PC Configurator cable (model: MCN-CON or COP-US)
• PC configurator software (model: R7CON)
Downloadable at our web site.
• Discrete input extension module (model: R7ML-EAx)
• Discrete output extension module (model: R7ML-ECx)

GENERAL SPECIFICATIONS

Connection
 
MECHATROLINK: MECHATROLINK-I/-II connector 
  Power input, output: M3 separable screw terminal (torque 0.5 N·m)
Solderless terminal: Refer to the drawing at the end of the section.
   Recommended manufacturer: Japan Solderless Terminal MFG. Co., Ltd., Nichifu Co., Ltd.
  Applicable wire size: 0.25 to 1.65 mm2 (AWG 22 to 16)
Screw terminal: Nickel-plated steel
Housing material: Flame-resistant resin (gray)
Isolation: Output 0 to output 1 to MECHATROLINK or FG to power
Zero adjustments: Configurable via R7CON
Span adjustments: Configurable via R7CON
Extension: No extension (*), Discrete input 8 or 16 points, Discrete output 8 or 16 points
Selectable with the front DIP SW
(*) Factory default setting
Output at the loss of communication:
Hold the output (*), Reset the output
Selectable with the front DIP SW
(*) Factory default setting
Status indicator LEDs: PWR, RUN, ERR, SD, RD
(Refer to the instruction manual)
Configurator connection: 2.5 dia. miniature jack
■Recommended solderless terminal

MECHATROLINK COMMUNICATION

MECHATROLINK mode: Set with DIP switches
(MECHATROLINK-I or -II, data length; Factory default setting: MECHATROLINK-II; data length (17 bytes)
(Refer to the instruction manual)
Station address: 60H - 7FH
(Function selected with Rotary SW.  Factory default setting: 60H) (Refer to the instruction manual)

MECHATROLINK-I
Baud rate
: 4 Mbps
Transmission distance: 50 m max.
Distance between stations: 30 cm min.
Transmission media: MECHATROLINK cable (Model JEPMC-W6003-x-E, Yaskawa Controls Co., Ltd.)
Max. number of Subordinate Devices: 15
(The maximum number of Subordinate Devices might change depending on the Main Device unit. Refer to the manual of the Main Device unit)
Transmission cycle: 2 msec. (fixed)
Data length: 17 bytes 

MECHATROLINK-II
Baud rate
: 10 Mbps
Transmission distance: 50 m max.
Distance between stations: 50 cm min.
Transmission media: MECHATROLINK cable (Model JEPMC-W6003-x-E, Yaskawa Controls Co., Ltd.)
Max. number of Subordinate Devices: 30
(The maximum number of Subordinate Devices might change depending on the Main Device unit. Refer to the manual of the Main Device unit)
Transmission cycle: 0.5 msec., 1 msec., 1.5 msec., 2 msec., 4 msec., 8 msec.
Data length: 17 bytes / 32 bytes selectable (Must choose identical data size for all stations on one network)

OUTPUT SPECIFICATIONS

Output range: 4 to 20 mA DC
Load resistance: ≤ 600 Ω
Operational range: -15 to +115 % of output range

INSTALLATION

Current consumption
DC: Approx. 130 mA
Operating temperature: 0 to 55°C (32 to 131°F)
Storage temperature: -20 to +65°C (-4 to +149°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: DIN rail (35 mm rail)
Weight: 200 g (0.44 lb)

PERFORMANCE

Conversion accuracy: ±0.1 %
Data range: 0 – 10000 of the output range
(Scaling of converted data is configurable with the configurator software (model: R7CON))
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)
Response time: 250 msec. (0 – 90 %)
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute
(output 0 to output 1 to power)
500 V AC @ 1 minute (MECHATROLINK or FG to output or power)

FUNCTIONS

Output hold function:
Output at the loss of communication is selectable from output clear (fix the output at -15 %) and output hold (last normally received data) with DIP switch.
At the startup, it outputs -15 % until the communication is established and normal data is received.

EXTERNAL VIEW

COMMUNICATION CABLE CONNECTIONS

TERMINAL ASSIGNMENTS

■OUTPUT TERMINAL ASSIGNMENT

MECHATROLINK RELATED COMMANDS

DATA CONVERSION

I/O DATA DESCRIPTIONS

EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM

Caution: FG terminal is NOT a protective conductor terminal.