ES-8010-B Rev.0
R7F4HPN-DA16B-4
Remote I/O R7F4H Series
PROFINET I/O MODULE
(PNP discrete input, 16 points, tension clamp terminal block)
Functions & Features
• Remote I/O module to input/output digital I/O signal to field bus (PROFINET)
MODEL: R7F4HPN-DA16B-4-R[1]
ORDERING INFORMATION
• Code number: R7F4HPN-DA16B-4-R[1]
Specify a code from below for [1].
(e.g. R7F4HPN-DA16B-4-R/Q)
• Specify the specification for option code /Q
(e.g. /C01/SET)
I/O TYPE
DA16B:
PNP discrete input, 16 points
TERMINAL BLOCK
4
: Tension clamp terminal block for power supply
RJ-45 Modular jack for communication
Tension clamp terminal block for I/O
POWER INPUT
DC power
R
: 24 V DC
(Operational voltage range: ±10 %; ripple 10 %p-p max.)
[1] OPTIONS
blank
: none
/Q
: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
EX-FACTORY SETTING
/SET
: Preset according to the Ordering Information Sheet
(No. ESU-8010-A)
RELATED PRODUCTS
• PC configurator software (model: R7CFG)
• GSDML file
The configurator software and GSDML file are downloadable at our web site.
For connecting to PC, use commercially available Type-C USB cable. (provided by user)
GENERAL SPECIFICATIONS
Connection
PROFINET
: RJ-45 Modular Jack
Power supply, exc. supply, input
: Tension clamp terminal
Housing material
: Flame-resistant resin (gray)
Isolation:
Input or exc. supply to PROFINET or FE to power
Status indicator LEDs
: PWR, RUN, ERR, LNK1, LNK2
(Refer to the instruction manual)
Discrete input status indicator LED
: Green LED turns on with input ON
Read rate:
Selectable with R7CFG
PROFINET COMMUNICATION
Communication standard:
IEEE 802.3
Transmission:
100BASE-TX
Baud rate:
100 Mbps / full duplex
Transmission media:
100BASE-TX (STP, Category 5)
RJ-45 modular jack × 2 ports
Network topology:
Line, star, tree and ring
Device class:
PROFINET IO device
Conformance class:
CC-B (PROFINET RT)
Conformance test version:
V2.4
Media redundancy:
MRP
INPUT SPECIFICATIONS
Common
: Negative common (PNP), 8 points per common
Numbers of input
: 16 points
Maximum inputs applicable at once:
No limit (at 24 V DC)
Sensor excitation
: 24 V DC ±10 %; ripple 5 %p-p max.
ON voltage / current
: ≥ 15 V DC (X0 to X15 input terminal – GND) / ≥ 3.5 mA
OFF voltage / current
: ≤ 5 V DC (X0 to X15 input terminal – GND) / ≤ 1.0 mA
Input current
: ≤ 5.5 mA per point at 24 V DC
Input resistance
: Approx. 4.4 kΩ
ON delay
: ≤ 0.2 msec.
OFF delay
: ≤ 0.5 msec.
INSTALLATION
Current consumption
•
DC (@ 24 V DC)
: ≤ 55 mA
(contact I/O load charge is not included)
Operating temperature
: -10 to +55°C (14 to 131°F)
Storage temperature
: -20 to +65°C (-4 to +149°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Atmosphere
: No corrosive gas or heavy dust
Mounting
: Surface or DIN rail (35 mm rail)
Weight
: 160 g (0.35 lb)
PERFORMANCE
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength:
1500 V AC @ 1 minute
(input or exc. supply to PROFINET or FE to power)
STANDARDS & APPROVALS
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
PC CONFIGURATOR
The following parameters can be set with using PC Configurator Software (model: R7CFG)
Refer to the users manual for the R7CFG for detailed operation of the software program.
EXTERNAL VIEW
TERMINAL ASSIGNMENTS
■SENSOR EXC. / INPUT CONNECTION
■ POWER SUPPLY TERMINAL ASSIGNMENT
I/O DATA DESCRIPTIONS
EXTERNAL DIMENSIONS unit: mm [inch]
MOUNTING REQUIREMENTS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
Note: In order to improve EMC performance, bond the FE terminal to ground.
Caution: FE terminal is NOT a protective conductor terminal.