ES-8010-G Rev.0

R7F4HPN-DAC16C-4

Remote I/O R7F4H Series

PROFINET I/O MODULE

(NPN discrete input, NPN transistor output, 8 points each, tension clamp terminal block)
Functions & Features
• Remote I/O module to input/output digital I/O signal to field bus (PROFINET)
 

MODEL: R7F4HPN-DAC16C-4-R[1]

ORDERING INFORMATION

• Code number: R7F4HPN-DAC16C-4-R[1]
Specify a code from below for [1].
  (e.g. R7F4HPN-DAC16C-4-R/Q)
• Specify the specification for option code /Q
  (e.g. /C01/SET)

I/O TYPE

DAC16C: NPN discrete input &
  NPN transistor output, 8 points each

TERMINAL BLOCK

4: Tension clamp terminal block for power supply
    RJ-45 Modular jack for communication
    Tension clamp terminal block for I/O

POWER INPUT

DC power
R: 24 V DC
(Operational voltage range: ±10 %; ripple 10 %p-p max.)

[1] OPTIONS

blank: none
/Q: With options (specify the specification)

SPECIFICATIONS OF OPTION: Q (multiple selections)

COATING (For the detail, refer to our web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating
EX-FACTORY SETTING
/SET: Preset according to the Ordering Information Sheet
 (No. ESU-8010-E)

RELATED PRODUCTS

• PC configurator software (model: R7CFG)
• GSDML file
The configurator software and GSDML file are downloadable at our web site.
For connecting to PC, use commercially available Type-C USB cable. (provided by user)

GENERAL SPECIFICATIONS

Connection
 PROFINET
: RJ-45 Modular Jack
 Power supply, exc. supply, I/O: Tension clamp terminal
Housing material: Flame-resistant resin (gray)
Isolation: Input or exc. supply to output or exc. supply to PROFINET or FE to power
Output at the loss of communication: Configurable via R7CFG
Status indicator LEDs: PWR, RUN, ERR, LNK1, LNK2
(Refer to the instruction manual)
Discrete I/O status indicator LED: Green LED turns on with I/O ON
Read rate: Selectable with R7CFG

PROFINET COMMUNICATION

Communication standard: IEEE 802.3
Transmission: 100BASE-TX
Baud rate: 100 Mbps / full duplex
Transmission media: 100BASE-TX (STP, Category 5)
RJ-45 modular jack × 2 ports
Network topology: Line, star, tree and ring
Device class: PROFINET IO device
Conformance class: CC-B (PROFINET RT)
Conformance test version: V2.4
Media redundancy: MRP

INPUT SPECIFICATIONS

Common: Positive common (NPN), 8 points per common
Numbers of input: 8 points
Maximum inputs applicable at once: No limit (at 24 V DC)
Sensor excitation: 24 V DC ±10 %; ripple 5 %p-p max.
ON voltage / current: ≥ 15 V DC (X0 to X7 input terminal – +24V) / ≥ 3.5 mA
OFF voltage / current: ≤ 5 V DC (X0 to X7 input terminal – +24V) / ≤ 1.0 mA
Input current: ≤ 5.5 mA per point at 24 V DC
Input resistance: Approx. 4.4 kΩ
ON delay: ≤ 0.2 msec.
OFF delay: ≤ 0.5 msec.

OUTPUT SPECIFICATIONS

Common: Negative common (NPN), 8 points per common
Number of output: 8 points
Maximum outputs applicable at once: No limit (at 24 V DC)
Sensor excitation: 24 V DC ±10 %, ripple 5 %p-p max.
Rated output current: 0.1 A per point, 0.8 A per common
Residual voltage: ≤ 1.2 V
Leakage current: ≤ 0.1 mA
ON delay: ≤ 0.2 msec.
OFF delay: ≤ 0.5 msec.
Overload current protection function: The current value is limited  when overcurrent is detected.
Overheat protection function: The output is turned off when overheat is detected.
(When driving an inductive load, connect a diode in parallel with the load.)

INSTALLATION

Current consumption
DC (@ 24 V DC): ≤ 55 mA
 (contact I/O load charge is not included)
Operating temperature: -10 to +55°C (14 to 131°F)
Storage temperature: -20 to +65°C (-4 to +149°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Surface or DIN rail (35 mm rail)
Weight: 160 g (0.35 lb)

PERFORMANCE

Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute
(input or exc. supply to output or exc. supply to PROFINET or FE to power)

STANDARDS & APPROVALS

EU conformity:
EMC Directive 
  EMI EN 61000-6-4
  EMS EN 61000-6-2
RoHS Directive

PC CONFIGURATOR

The following parameters can be set with using PC Configurator Software (model: R7CFG)
Refer to the users manual for the R7CFG for detailed operation of the software program.

EXTERNAL VIEW

TERMINAL ASSIGNMENTS

■ SENSOR EXC. / I/O CONNECTION
■ POWER SUPPLY TERMINAL ASSIGNMENT

I/O DATA DESCRIPTIONS

EXTERNAL DIMENSIONS unit: mm [inch]

MOUNTING REQUIREMENTS unit: mm [inch]

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM

Note: In order to improve EMC performance, bond the FE terminal to ground.
Caution: FE terminal is NOT a protective conductor terminal.