ES-4657 Rev.0

PLC8

Controller / Remote I/O PLC8 Series

PLC8 SERIES GENERAL SPECIFICATIONS

Functions & Features
• Analog I/O modules or discrete I/O modules can be freely interchanged.
• Space-saving
• CODESYS is available (conforms to IEC 61131-3)
 

ORDERING INFORMATION

Refer to the specifications of the respective modules for details.

CONTROLLER: PLC8-[1]-R

Refer to the specifications of each module for details.

[1] MODULE TYPE

NE: PLC

POWER INPUT

DC power
R: 24 V DC
(Operational voltage range: ±10 %; ripple 10 %p-p max.)

I/O MODULE: PLC8-[1]

Refer to the specifications of each module for details.

[1] MODULE TYPE

• Discrete I/O
DAC4: Discrete I/O module
(Di 2 points (internal power), Do 2 points (photo MOSFET relay))

END MODULE: PLC8-[1]

Refer to the specifications of each module for details.

[1] MODULE TYPE

END: End module

FUNCTIONS & FEATURES

PLC8 series consists of a controller, I/O modules, and an end module.
■ CONTROLLER
The controller can control the I/O modules. It also generates an internal power for I/O modules.
■ I/O MODULE
I/O modules perform analog input/output, discrete input/output, etc. via the internal bus.
■ END MODULE
The end module is the terminal of internal bus.
When the end module is used with a controller and I/O modules, be sure to connect it after connecting I/O modules.
The end module is not included in the maximum number of connectable devices for the controller.
■ HOT SWAPPING
Hot swapping is not possible since internal communication and supplying the internal power are conducted through the connectors of I/O modules.
■ DIELECTRIC STRENGTH
Dielectric strength varies depending on the model. Check the specifications for each model.

RELATED PRODUCTS

• Programming tool (model: C-CDS35)
• SD card
An SD card is required to store data in the device.
Use the specified model number of SD card.
Available for purchase from us. Consult us.

GENERAL SPECIFICATIONS

Connection: Depends upon the type of modules. Refer to the specifications for the respective modules.
Housing material: Flame-resistant resin (gray)
INTERNAL BUS
Baud rate
: 1 Mbps

INSTALLATION

Operating temperature: -10 to +55°C (14 to 131°F)
Operating humidity: 10 to 90 %RH (non-condensing)
Ambience: No corrosive gas or heavy dust; no strong electric/magnetic field; no direct effect of vibration or physical impact
Mounting: DIN rail
Weight: Refer to the specifications of the respective modules.

CURRENT CONSUMPTION

I/O modules and end module operate by using internal power supplied from the controller and exc. supply.
Therefore, the total current consumption of the I/O modules and the end module must be within the supplied current capacity.
If the controller's power is insufficient, change the combination of I/O modules or reduce the number of I/O modules.

BASIC CONFIGURATIONS

■ CONTROLLER: PLC8-NE
When I/O modules are used, be sure to mount an end module at the terminal of I/O modules. Do not mount other I/O modules at the right of the end module.
When an end module is used, attach the protective cover provided with the controller to the end module for safety.

MOUNTING REQUIREMENTS unit: mm [inch]