ES-7807-C Rev.0
R7E-RS4
Remote I/O R7 Series
ETHERNET I/O MODULE
(RTD input, 4 points, isolated, Modbus/TCP use)
Functions & Features
• 4 points RTD input module for Modbus/TCP (Ethernet)
• Extension module can be connected
• Input sensor type can be selected with the front DIP switches for all channels.
• Individual channels, zero adjustment, span adjustment, scaling, and temperature unit can be set with the configurator software (model: R7CON)
MODEL:R7E–RS4-R[1]
ORDERING INFORMATION
• Code number: R7E-RS4-R[1]
Specify a code from below for [1].
(e.g. R7E-RS4-R/Q)
• Specify the specification for option code /Q
(e.g. /C01/SET)
I/O TYPE
RS4
: RTD input, 4 points
POWER INPUT
DC Power
R
: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
[1] OPTIONS
blank
: none
/Q
: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
EX-FACTORY SETTING
/SET
: Preset according to the Ordering Information Sheet
(No. ESU-7807-C)
RELATED PRODUCTS
• PC Configurator cable (model: MCN-CON or COP-US)
• PC configurator software (model: R7CON)
Downloadable at our web site.
• Discrete input extension module (model: R7E-EAx)
• Discrete output extension module (model: R7E-ECx)
Note: PC Configurator Software is required to set IP address.
GENERAL SPECIFICATIONS
Connection
Ethernet
: RJ-45 connector
Power, i
nput
: M3 separable screw terminal
(torque 0.5 N·m)
Solderless terminal
: Refer to the drawing at the end of the section.
Recommended manufacturer
: Japan Solderless Terminal MFG. Co., Ltd., Nichifu Co., Ltd.
Applicable wire size
: 0.25 to 1.65 mm
2
(AWG 22 to 16)
Screw terminal
: Nickel-plated steel
Housing material
: Flame-resistant resin (gray)
Isolation
: Input 0 to input 1 to input 2 to input 3 to Ethernet to power to FG
Zero adjustments
: Configurable via R7CON
Span adjustments
: Configurable via R7CON
Extension:
No extension (*), Discrete input 8 or 16 points, Discrete output 8 or 16 points
Selectable with the front DIP SW
(*) Factory default setting
Conversion rate
: Selectable with the front DIP SW
Burnout setting
: Selectable between upscale (*) and downscale with the front DIP switch
(*) Factory default setting
Linearization
: Standard
RTD Setting
: Configurable via the front DIP switch or R7CON
Status indicator LEDs
: PWR, RUN
Configurator connection
: 2.5 dia. miniature jack
■Recommended solderless terminal
ETHERNET COMMUNICATION
Physical layer standard
: IEEE 802.3u
Data link layer
: 10BASE-T / 100BASE-TX
Baud rate
: 10 / 100 Mbps, Auto Negotiation
Protocol
: Modbus/TCP
Data
: RTU (binary)
Max. number of socket connections
: Two (2)
Transmission media
: 10BASE-T (STP cable, category 5)
100BASE-TX (STP cable, category 5e)
Max. segment length
: 100 meters
IP address:
Can be set and changed with PC Configurator Software (model: R7CON) (default: 192.168.0.1)
Subnet Mask:
Can be set and changed with PC Configurator Software (model: R7CON) (default: 255.255.255.0)
Default Gateway:
Can be set and changed with PC Configurator Software (model: R7CON) (Ver.2.41 or later) (default: 192.168.0.100)
Port No
.: 502
DHCP available (Ver.3.00 or later)
Ethernet indicator LEDs
: LINK, LINK100, COL
INPUT SPECIFICATIONS
Input resistance
: ≥ 1 MΩ
Maximum leadwire resistance
: 100 Ω per wire
Sensing current
: ≤ 1 mA
INSTALLATION
Current consumption
•
DC
: Approx. 97 mA
Operating temperature
: -10 to +55°C (14 to 131°F)
Storage temperature
: -20 to +65°C (-4 to +149°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Atmosphere
: No corrosive gas or heavy dust
Mounting
: DIN rail (35 mm rail)
Weight
: 200 g (0.44 lb)
PERFORMANCE
Conversion accuracy
: ±1°C (±1.8°F)
(±3°C [±5.4°F] for Cu 10 @ 25°C)
Conversion rate
: 250 msec. (*) or 1 sec. selectable
(*) Factory default setting
Converted data range
:
• Engineering unit value (°C, K) × 10 (integer)
• Engineering unit value (°F)
Temperature coefficient
: ±0.015 %/°C (±0.008 %/°F) of max. span except ±0.150 %/°C (±0.08 %/°F) for Cu 10 @ 25°C
Response time
: Conversion rate × 2 + 50 msec. (0 – 90 %)
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 1500 V AC @ 1 minute (input 0 to input 1 to input 2 to input 3 to Ethernet to power to FG)
STANDARDS & APPROVALS
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
EXTERNAL VIEW
TERMINAL ASSIGNMENTS
■ INPUT TERMINAL ASSIGNMENT
MODBUS FUNCTION CODES & SUPPORTED CODES
MODBUS I/O ASSIGNMENT
DATA CONVERSION
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
Note: In order to improve EMC performance, bond the FG terminal to ground.
Caution: FG terminal is NOT a protective conductor terminal.