ES-9728 Rev.5
R8-SS4N
Remote I/O R8 Series
DC CURRENT INPUT MODULE
(4 points, non-isolated)
Functions & Features
• 4 channels for DC current input, compact size remote I/O module
• Input range adjustment with DIP switch or PC configurator
MODEL: R8–SS4N[1]
ORDERING INFORMATION
• Code number: R8-SS4N[1]
Specify a code from below for [1].
(e.g. R8-SS4N/Q)
• Specify the specification for option code /Q
(e.g. /C01)
[1] OPTIONS
blank
: none
/Q
: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
RELATED PRODUCTS
• PC Configurator cable (model: MCN-CON or COP-US)
• PC configurator software (model: R8CFG)
Downloadable at our web site.
GENERAL SPECIFICATIONS
Connection
•
Input
: 4-pin e-CON connector
Unit side connector XN2D-1474-S002 (Omron)
Recommended cable side connector XN2A-1470 (Omron)
Applicable wire size: 0.08 - 0.5 mm
2
(AWG28 - 20)
Outer sheath diameter: max. 1.5 dia
(The cable side connector is not included in the package.
Refer to the specifications of the product.)
•
Excitation supply, internal bus
:
Connected to internal bus connector
•
Internal power
: Supplied from internal bus connector
Isolation
: Input to exc. supply to internal bus or internal power
Input range
: Selectable with the side DIP SW
Module address
: With rotary switch
Terminating resistor
: Built-in (DIP Switch, default: disable)
Configuration mode
: With DIP switches on the side panel
Status indicator
: Bi-color (red/green) LED; Refer to the instruction manual.
Input status indicators
: Red LED; Refer to the instruction manual.
INPUT SPECIFICATIONS
Input range
: -20 – +20 mA DC configurable
Operational
range
: :-5 - +105 % (in percentage of input range)
Input resistance
: 50 Ω
INSTALLATION
Max. current consumption
: 80 mA
Operating temperature
: -10 to +55°C (14 to 131°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Atmosphere
: No corrosive gas or heavy dust
Mounting
: DIN rail
Weight
: 60 g (2.12 oz)
PERFORMANCE
Conversion accuracy
(in percentage of input range)
±0.1 % (@ input range -20 - +20 mA)
Conversion accuracy is inversely proportional to input span.
Conversion accuracy computation example:
When input range is 4 - 20 mA: conversion accuracy = nominal input span (40 mA) ÷ input span (16 mA) × 0.1 (%) = 0.25 (%).
Nominal input span is the same as the span at input range
-20 - +20 mA DC.
Conversion rate
: 4 msec.
Input circuit time constant
: Approx. 1 msec.
Data range
: 0 – 10000 of the input range
Data allocation
: 2
Module addresses in use
: 2
Max. consumption current
: 80 mA
Temp. coefficient
: ±0.015 %/°C (±0.008 %/°F)
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
:
1500 V AC @ 1 minute (input to exc. supply to internal bus or internal power to ground)
STANDARDS & APPROVALS
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
EXTERNAL VIEW
OPERATING MODE SETTING
(*) Factory default setting
Note: Be sure to set unused SW4-3 through 4-7 to OFF.
EXTERNAL DIMENSIONS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM