ES-9745 Rev.5

R8-YS2

Remote I/O R8 Series

DC CURRENT OUTPUT MODULE

(2 points, isolated)
Functions & Features
• 2 channels for DC current output, compact size remote I/O module
• Output range adjustment with DIP switch or PC configurator

MODEL: R8–YS2[1]

ORDERING INFORMATION

• Code number: R8-YS2[1]
Specify a code from below for [1].
  (e.g. R8-YS2/Q)
• Specify the specification for option code /Q
  (e.g. /C01)

[1] OPTIONS

blank: none
/Q: With options (specify the specification)

SPECIFICATIONS OF OPTION: Q

COATING (For the detail, refer to our web site.)
/C01: Silicone coating
/C02: Polyurethane coating

RELATED PRODUCTS

• PC Configurator cable (model: MCN-CON or COP-US)
• PC configurator software (model: R8CFG)
Downloadable at our web site.

GENERAL SPECIFICATIONS

Connection
Output: 4-pin e-CON connector
   Unit side connector XN2D-1474-S002 (Omron)
   Recommended cable side connector XN2A-1470 (Omron)
   Applicable wire size 0.08 - 0.5 mm2 (AWG28 - 20)
   Outer sheath diameter: max. 1.5 dia
   (The cable side connector is not included in the package.
   Refer to the
specifications of the product.)
Excitation supply, internal bus:
   Connected to internal bus connector
Internal power: Supplied from internal bus connector
Isolation: Output 1 to output 2 to exc. supply to internal bus or internal power
Output range: Selectable with the side DIP SW
Module address: With DIP switch
Output at the loss of communication: Selectable with the side DIP SW
Terminating resistor: Built-in (DIP Switch, default: disable)
Configuration mode: With DIP switches on the side panel
Status indicator: Bi-color (red/green) LED; Refer to the instruction manual.
Output status indicators: Red LED; Refer to the instruction manual.

OUTPUT SPECIFICATIONS

Output range: Selectable between 0 – 20mA DC
Operational range: -5 – +105 % (in percentage of output range) ≤ 0 mA DC
Load resistance: ≤ 500Ω

INSTALLATION

Max. current consumption: 80 mA
Exc. supply current consumption: 60 mA
Operating temperature: -10 to +55°C (14 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: DIN rail
Weight: 110 g (0.24 lb)

PERFORMANCE

Conversion accuracy (in percentage of output range)
±0.08 % (@ output range 0 - 20 mA)
Conversion accuracy is inversely proportional to output span.
  Conversion accuracy computation example:
  When output range is 4 - 20 mA: conversion accuracy = output span standard value (20 mA) ÷ output span (16 mA) × 0.08 (%) = 0.1 (%).
output span standard value is the same as the span at output range 0 - 20 mA DC.
Conversion rate: 2 msec.
Output circuit time constant: ≤ 0.5 msec. (0 → 90 %)
Data range: 0 – 10000 of the output range
Data allocation: 2
Module addresses in use: 1
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength:
  1000 V AC @ 1 minute (output 1 to output 2 to exc. supply to internal bus or internal power to ground)

STANDARDS & APPROVALS

EU conformity:
EMC Directive 
  EMI EN 61000-6-4
  EMS EN 61000-6-2
RoHS Directive

EXTERNAL VIEW

OPERATING MODE SETTING

(*) Factory default setting
Note: Be sure to set unused SW2-2 through 2-4 and 2-7 to OFF.

EXTERNAL DIMENSIONS unit: mm [inch]

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM