ES-9744 Rev.4
R8-YS2NJ
Remote I/O R8 Series
DC CURRENT OUTPUT MODULE
(built-in excitation, 2 points, non-isolated)
Functions & Features
• 2 channels for DC current output, compact size remote I/O module
• Output range adjustment with DIP switch or PC configurator
• Excitation supply for sensor available from output connector
MODEL: R8–YS2NJ[1]
ORDERING INFORMATION
• Code number: R8-YS2NJ[1]
Specify a code from below for [1].
(e.g. R8-YS2NJ/Q)
• Specify the specification for option code /Q
(e.g. /C01)
[1] OPTIONS
blank
: none
/Q
: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
RELATED PRODUCTS
• PC Configurator cable (model: MCN-CON or COP-US)
• PC configurator software (model: R8CFG)
Downloadable at our web site.
GENERAL SPECIFICATIONS
Connection
•
Output
: 4-pin e-CON connector
Unit side connector XN2D-1474-S002 (Omron)
Recommended cable side connector XN2A-1470 (Omron)
Applicable wire size 0.08 - 0.5 mm
2
(AWG28 - 20)
Outer sheath diameter: max. 1.5 dia
(The cable side connector is not included in the package.
Refer to the
specifications of the product.)
•
Excitation supply, internal bus
:
Connected to internal bus connector
•
Internal power
: Supplied from internal bus connector
Isolation
: Output 1 or output 2 to exc. supply to internal bus or internal power
Output range
: Selectable with the side DIP SW
Module address
: With rotary switch
Output at the loss of communication
: Selectable with the side DIP SW
Terminating resistor
: Built-in (DIP Switch, default: disable)
Configuration mode
: With DIP switches on the side panel
Status indicator
: Bi-color (red/green) LED; Refer to the instruction manual.
Output status indicators
: Red LED; Refer to the instruction manual.
OUTPUT SPECIFICATIONS
Output range
: Selectable between 0 – 20mA DC
Operational range
: -5 – +105 % (in percentage of output range) ≤ 0 mA DC
Load resistance
: ≤ 500Ω
INSTALLATION
Max. current consumption
: 70 mA
Exc. supply
: 24 V DC ±10%
Exc. supply
current consumption
: 50 mA
(Power supply for output circuit is generated from exc. supply)
Operating temperature
: -10 to +55°C (14 to 131°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Atmosphere
: No corrosive gas or heavy dust
Mounting
: DIN rail
Weight
: 60 g (2.12 oz)
PERFORMANCE
Conversion accuracy (in percentage of output range)
±0.08 % (@ output range 0 - 20 mA)
Conversion accuracy is inversely proportional to output span.
Conversion accuracy computation example:
When output range is 4 - 20 mA: conversion accuracy = output span standard value (20 mA) ÷ output span (16 mA) × 0.08 (%) = 0.1 (%).
output span standard value is the same as the span at output range 0 - 20 mA DC.
Conversion rate
: 2 msec.
Output circuit time constant
: ≤ 1 msec. (0 → 90 %)
Data range
: 0 – 10000 of the output range
Data allocation
: 2
Module addresses in use
: 1
Power output (between 1 to 4 pin of output
connector
)
: Rated current 0.5 A DC per channel (rated current 3 A for internal fuse (slow blow fuse i
2
t (A
2
sec.) max. 5.04); Total: 1 A DC
Temp. coefficient
: ±0.015 %/°C (±0.008 %/°F)
Insulation resistance
: ≥ 100 MΩ with 250 V DC
Dielectric strength
:
1500 V AC @ 1 minute (output 1 or output 2 or exc. supply to internal bus or internal power to ground)
300 V AC @ 1 minute (output 1 or output 2 to exc.supply)
STANDARDS & APPROVALS
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
EXTERNAL VIEW
SHORT ACROSS GROUNDS
Choose to open or short across grounds of excitation supply and output.
In case of shorting across, insert short-plug in the center pin of JP1 and SHORT side.
In case of opening, insert short-plug in the center pin of JP1 and OPEN side.
Factory default is on SHORT side.
OPERATING MODE SETTING
(*) Factory default setting
Note: Be sure to set unused SW4-2 through 4-6 to OFF.
EXTERNAL DIMENSIONS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM