ES-7803-T Rev.0
R7M-RR8
Remote I/O R7 Series
MODBUS I/O MODULE
(remote control relay control, 8 points, 115.2 kbps)
Functions & Features
• 8 points remote control relay control module for Modbus
• Extension module can be connected
MODEL:R7M-RR8-[1][2]
ORDERING INFORMATION
• Code number: R7M-RR8-[1][2]
Specify a code from below for each of [1] and [2].
(e.g. R7M-RR8-AR/Q)
• Specify the specification for option code /Q
(e.g. /C01/SET)
I/O TYPE
RR8
: Remote control relay control, 8 points
[1] POWER INPUT
DC Power
R
: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
Universal
AR
: 24 V AC/24 V DC (universal)
(Operational voltage range 24 V AC±10 %, 50 - 60 Hz /
24 V DC±10 %, ripple 10 %p-p max.)
[2] OPTIONS
blank
: none
/Q
: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
EX-FACTORY SETTING
/SET
: Preset according to the Ordering Information Sheet
(No. ESU-7803-T)
RELATED PRODUCTS
• PC Configurator cable (model: MCN-CON or COP-US)
• PC configurator software (model: R7CON)
Downloadable at our web site.
• Discrete input extension module (model: R7M-EAx)
• Discrete output extension module (model: R7M-ECx)
RECOMMENDED PRODUCTS (OPERATION CHECKED)
Remote control relay:
BR-12D, BR-22D (Mitsubishi Electric)
WR6165 (Panasonic)
Remote control transformer:
BRT-10B, BRT-20B (Mitsubishi Electric)
WR2301 (Panasonic)
Remote control switch
WR8501 (Panasonic)
GENERAL SPECIFICATIONS
Connection:
M3 separable screw terminal (torque 0.5 N·m)
Solderless terminal
: Refer to the drawing at the end of the section.
Recommended manufacturer
: Japan Solderless Terminal MFG. Co., Ltd., Nichifu Co., Ltd.
Applicable wire size
: 0.25 to 1.65 mm
2
(AWG 22 to 16)
Screw terminal
: Nickel-plated steel
Housing material
: Flame-resistant resin (gray)
Isolation
: Output to Modbus or FG to power
Output data length
: Selectable between 8-bit (*) and 16-bit with the front DIP switch
(*) Factory default setting
Note: Output data length setting is compatible with Ver.2.01 or later.
Extension:
No extension (*), Discrete input 8 or 16 points, Discrete output 8 or 16 points
Selectable with the front DIP SW
(*) Factory default setting
Status indicator LEDs
: PWR, RUN, ERR, SD, RD
(Refer to the instruction manual)
I/O status indicator
: Feedback input status turns on with the input supplied.
Output status LED turns on with the output ON.
Configurator connection
: 2.5 dia. miniature jack
■Recommended solderless terminal
MODBUS COMMUNICATION
Standard
: Conforms to TIA/EIA-485-A
Transmission distance
: 500 meters max.
Transmission media
: Shielded twisted-pair cable
(CPEV-S 0.9 dia.)
Communication parameter:
With Configurator Software (model: R7CON)
• Data Mode
: RTU (default) or ASCII
• Parity:
NONE (default), ODD or EVEN
• Data bit:
8: RTU (default), 7: ASCII
•
Stop bit:
1 or 2 (default)
Baud rate setting
: With rotary switch
115.2 kbps, 57.6 kbps, 38.4 kbps (default), 28.8 kbps,
19.2 kbps, 14.4 kbps, 9600 bps, 4800 bps, 2400 bps,
1200 bps
Node address setting
: 1 - 99 (with rotary switch) (factory default setting: 00)
Terminating resistor
: Built-in (Selected with the DIP SW; factory setting: disabled)
OUTPUT SPECIFICATIONS
Common
: 1 common per 8 points (8 terminals)
Maximum outputs applicable at once
: No limit
Pulse output time
: 100 msec.
Rated load voltage
: 24 V AC ±10 % (supplied by the remote control transformer)
Load voltage frequency
: 50 / 60 Hz
INSTALLATION
Current consumption
•
AC
: Approx. 140 mA
•
DC
: Approx. 60 mA
Operating temperature
: -10 to +55°C (14 to 131°F)
Storage temperature
: -20 to +65°C (-4 to +149°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Atmosphere
: No corrosive gas or heavy dust
Mounting
: DIN rail (35 mm rail)
Weight
: 200 g (0.44 lb)
PERFORMANCE
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 1500 V AC @ 1 minute (output to Modbus or FG to power)
EXTERNAL VIEW
COMMUNICATION CABLE CONNECTIONS
TERMINAL ASSIGNMENTS
■ OUTPUT TERMINAL ASSIGNMENT
MODBUS FUNCTION CODES & SUPPORTED CODES
MODBUS I/O ASSIGNMENT
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
Caution: FG terminal is NOT a protective conductor terminal.