DC CURRENT INPUT MODULE

(4 points, isolated, screw terminal block)
Functions & Features
• 4 channels for DC current input, compact size remote I/O module
• Isolation between channels
• Input range adjustment with DIP switch or PC configurator

MODEL: R8–SSN4[1]

ORDERING INFORMATION

• Code number: R8-SSN4[1]
Specify a code from below for [1].
  (e.g. R8-SSN4/Q)
• Specify the specification for option code /Q
  (e.g. /C01)

[1] OPTIONS

blank: none
/Q: With options (specify the specification)

SPECIFICATIONS OF OPTION: Q

COATING (For the detail, refer to our web site.)
/C01: Silicone coating
/C02: Polyurethane coating

RELATED PRODUCTS

• PC Configurator cable (model: MCN-CON or COP-US)
• PC configurator software (model: R8CFG)
Downloadable at our web site.

GENERAL SPECIFICATIONS

Connection
Input: M3 screw terminals (torque: 0.6 N·m)
Excitation supply, internal bus:
   Connected to internal bus connector
Internal power: Supplied from internal bus connector
Solderless terminal: Refer to the drawing at the end of the section.
   Recommended manufacturer: Japan Solderless Terminal MFG. Co., Ltd., Nichifu Co., Ltd.
  Applicable wire size: 0.25 to 1.65 mm2 (AWG 22 to 16)
Screw terminal: Nickel-plated steel
Isolation: Input 1 to input 2 to input 3 to input 4 to exc. supply to internal bus or internal power
Input range: Selectable with the side DIP SW
Module address: With DIP switch
Terminating resistor: Built-in (DIP Switch, default: disable)
Configuration mode: With DIP switches on the side panel
Status indicator: Bi-color (red/green) LED; Refer to the instruction manual.
Input status indicators: Red LED; Refer to the instruction manual.
■Recommended solderless terminal size - M3

INPUT SPECIFICATIONS

Input range: -20 – +20 mA DC configurable
Operational range: :-5 - +105 % (in percentage of input range)
Input resistance: 100 Ω

INSTALLATION

Max. current consumption: 170 mA
Operating temperature: -10 to +55°C (14 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: DIN rail
Weight: 120 g (0.26 lb)

PERFORMANCE

Conversion accuracy (in percentage of input range)
±0.1 % (@ input range -20 - +20 mA)
Conversion accuracy is inversely proportional to input span.
  Conversion accuracy computation example:
  When input range is 4 - 20 mA: conversion accuracy = nominal input span (40 mA) ÷ input span (16 mA) × 0.1 (%) = 0.25 (%).
Nominal input span is the same as the span at input range 
-20 - +20 mA DC.
Conversion rate: 4 msec.
Input circuit time constant: Approx. 1 msec.
Data range: 0 – 10000 of the input range
Data allocation: 2
Module addresses in use: 2
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute
(input 1 to input 2 to input 3 to input 4 to exc. supply to internal bus or internal power to ground)

STANDARDS & APPROVALS

EU conformity:
EMC Directive 
  EMI EN 61000-6-4
  EMS EN 61000-6-2
RoHS Directive

EXTERNAL VIEW

CONNECTION DIAGRAMS

OPERATING MODE SETTING

(*) Factory default setting
Note: Be sure to set unused SW4-3 through 4-5 and 4-7 to OFF.

EXTERNAL DIMENSIONS unit: mm [inch]

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM