ES-9628 Rev.0

R8-YVN4

Remote I/O R8 Series

DC VOLTAGE OUTPUT MODULE

(4 points, isolated, screw terminal block)
Functions & Features
• 4 channels for DC voltage output, compact size remote I/O module
• Isolation between channels
• Output range adjustment with DIP switch or PC configurator

MODEL: R8–YVN4[1]

ORDERING INFORMATION

• Code number: R8-YVN4[1]
Specify a code from below for [1].
  (e.g. R8-YVN4/Q)
• Specify the specification for option code /Q
  (e.g. /C01)

[1] OPTIONS

blank: none
/Q: With options (specify the specification)

SPECIFICATIONS OF OPTION: Q

COATING (For the detail, refer to our web site.)
/C01: Silicone coating
/C02: Polyurethane coating

RELATED PRODUCTS

• PC Configurator cable (model: MCN-CON or COP-US)
• PC configurator software (model: R8CFG)
Downloadable at our web site.

GENERAL SPECIFICATIONS

Connection
Output: M3 screw terminals (torque: 0.6 N·m)
Excitation supply, internal bus:
   Connected to internal bus connector
Internal power: Supplied from internal bus connector
Solderless terminal: Refer to the drawing at the end of the section.
   Recommended manufacturer: Japan Solderless Terminal MFG. Co., Ltd., Nichifu Co., Ltd.
  Applicable wire size: 0.25 to 1.65 mm2 (AWG 22 to 16)
Screw terminal: Nickel-plated steel
Isolation: Output 1 to output 2 to output 3 to output 4 to exc. supply to internal bus or internal power
Output range: Selectable with the side DIP SW
Module address: With DIP switch
Output at the loss of communication: Selectable with the side DIP SW
Terminating resistor: Built-in (DIP Switch, default: disable)
Configuration mode: With DIP switches on the side panel
Status indicator: Bi-color (red/green) LED; Refer to the instruction manual.
Output status indicators: Red LED; Refer to the instruction manual.
■Recommended solderless terminal size - M3

OUTPUT SPECIFICATIONS

Output range: Selectable between -10 – +10 V DC
Operational range: -5 – +105 % (in percentage of output range)
Load resistance: ≥ 20 kΩ

INSTALLATION

Max. current consumption: 110 mA
Operating temperature: -10 to +55°C (14 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: DIN rail
Weight: 120 g (0.26 lb)

PERFORMANCE

Conversion accuracy (in percentage of output range)
±0.05 % (@ output range -10 - +10 V)
Conversion accuracy is inversely proportional to output span.
  Conversion accuracy computation example:
  When output range is 1 - 5 V: conversion accuracy = output span standard value (20 V) ÷ output span (4 V) × 0.05 (%) = 0.25 (%).
output span standard value is the same as the span at output range -10 - +10 V DC.
Conversion rate: 4 msec.
Output circuit time constant: ≤ 5 msec. (0 → 90 %)
Data range: 0 – 10000 of the output range
Data allocation: 2
Module addresses in use: 2
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute
(output 1 to output 2 to output 3 to output 4 to exc. supply to internal bus or internal power to ground)

STANDARDS & APPROVALS

EU conformity:
EMC Directive 
  EMI EN 61000-6-4
  EMS EN 61000-6-2
RoHS Directive

EXTERNAL VIEW

CONNECTION DIAGRAMS

OPERATING MODE SETTING

(*) Factory default setting
Note: Be sure to set unused SW4-3 through 4-5 to OFF.

EXTERNAL DIMENSIONS unit: mm [inch]

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM