ES-8419 Rev.12

R3-BA32A

Remote I/O R3 Series

BCD CODE INPUT MODULE

(7-digit BCD)

MODEL: R3–BA32A[1][2]

ORDERING INFORMATION

• Code number: R3-BA32A[1][2]
Specify a code from below for each of [1] and [2].
  (e.g. R3-BA32AW/CE/Q)
• Specify the specification for option code /Q
  (e.g. /C01)

NO. OF CHANNELS

32: BCD code, 7 digits (4 channels/digit)

EXCITATION SUPPLY

A: External excitation, 24 V DC

[1] COMMUNICATION MODE

S: Single
W: Dual

[2] OPTIONS (multiple selections)

Standards & Approvals
blank: Without CE
/CE: CE marking
Other Options
blank: none
/Q: Option other than the above (specify the specification)

SPECIFICATIONS OF OPTION: Q

COATING (For the detail, refer to our web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating
/C04: Polyolefin coating

RELATED PRODUCTS

• Connector terminal block (model: CNT)
• Special cable with 40-pin connector (model: FCN)

GENERAL SPECIFICATIONS

Connection
  Internal bus
: Via the Installation Base (model: R3-BSx)
  Input: 40-pin connector (OTAX N365P040AU
  Fujitsu FCN-365P040-AU...discontinued))
  Internal power: Via the Installation Base (model: R3-BSx)
Isolation: Di 11 thru 28 to Di 31 thru 48 to Di 51 thru 68 to Di 71 thru 88 to internal bus or internal power
Strobe signal control: Selectable with the side DIP switch.
RUN indicator: Bi-color (red/green) LED;
Red when the bus A operates normally;
Green when the bus B operates normally;
Amber when both buses operate normally.
ERR indicator: Green LED turns on in normal operating conditions.
Input status indicator: Red LED; turns on with the input ON.
Group selector: Switches the input status indicator
 A. 1 - 8: Di11 - Di28
     9 - 16: Di31 - Di48
 B. 1 - 8: Di51 - Di68
     9 - 16: Di71 - Di88
Read rate: 5 / 10 / 50 / 100 msec. selectable with DIP SW

INPUT SPECIFICATIONS

Number of digits: 7 with strobe signal, 8 without it
Data: 2 words
Data description example
  Input data
: 1 2 3 4  5 6 7 8
                     4 high digits      4 low digits
  Address 1: 5678 (4 low digits)
  Address 2: 1234 (4 high digits)
Input signal: 24 V DC, 32 points (4 points/digit)
Input resistance: 6 kΩ
Isolation: Optical isolator
Common: 4 positive/negative commons, per 8 points
Contact detecting: 24 V DC ±10 %, approx. 4 mA
ON current/resistance: ≥ 2 mA, ≤ 2 kΩ
OFF current/resistance: ≤ 1 mA, ≥ 18 kΩ

INSTALLATION

Operating temperature: -10 to +55°C (14 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Installation Base (model: R3-BSx)
Weight: 150 g (0.33 lb)

PERFORMANCE

Data allocation: 4
Current consumption: 90 mA
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength:
500 V AC @ 1 minute
(Di 11 thru 28 to Di 31 thru 48 to Di 51 thru 68 to Di 71 thru 88)
2000 V AC @ 1 minute
(Input to internal bus or internal power)
2000 V AC @ 1 minute (power input to FG; isolated on the power supply module)

STANDARDS & APPROVALS

EU conformity:
EMC Directive 
  EMI EN 61000-6-4
  EMS EN 61000-6-2
RoHS Directive

FUNCTIONS

■ STROBE SIGNAL CONTROL
Controls the timing of reading data. Data is read in when the strobe signal is ON. No data read while it is OFF, even if there is a status change.

EXTERNAL VIEW

EXTERNAL DIMENSIONS unit: mm [inch]

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM

INPUT CONNECTOR (40-pin)