ES-7802-L Rev.0
R7D-YS2A
Remote I/O R7 Series
DeviceNet® I/O MODULE
(DC current output, 2 points, isolated, external power supply)
Functions & Features
• 2 points DC current output module for DeviceNet
• Extension module can be connected
• Individual channels, zero adjustment, span adjustment, and scaling can be set with the configurator software (model: R7CON)
MODEL:R7D–YS2A[1]
ORDERING INFORMATION
• Code number: R7D-YS2A[1]
Specify a code from below for [1].
(e.g. R7D-YS2A/Q)
• Specify the specification for option code /Q
(e.g. /C01/SET)
I/O TYPE
YS2A
: DC current output, external power supply, 2 points
[1] OPTIONS
blank
: none
/Q
: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
EX-FACTORY SETTING
/SET
: Preset according to the Ordering Information Sheet
(No. ESU-7802-E)
RELATED PRODUCTS
• PC Configurator cable (model: MCN-CON or COP-US)
• PC configurator software (model: R7CON)
• EDS file
The EDS files and configurator software are downloadable at our web site.
(Extension modules are registered in the EDS file as a combination of a basic module)
• Discrete input extension module (model: R7D-EAx)
• Discrete output extension module (model: R7D-ECx)
GENERAL SPECIFICATIONS
Connection
DeviceNet
: Euro type connector terminal
(applicable wire size: 0.2 to 2.5 mm
2
, stripped length 7 mm)
Output
: M3 separable screw terminal (torque 0.5 N·m)
Solderless terminal
: Refer to the drawing at the end of the section.
Recommended manufacturer
: Japan Solderless Terminal MFG. Co., Ltd., Nichifu Co., Ltd.
Applicable wire size
: 0.25 to 1.65 mm
2
(AWG 22 to 16)
Screw terminal
: Nickel-plated steel
Housing material
: Flame-resistant resin (gray)
Isolation
: Output 0 to output 1 to DeviceNet to external power supply
Zero adjustments
: Configurable via R7CON
Span adjustments
: Configurable via R7CON
Extension:
No extension (*), Discrete input 8 or 16 points, Discrete output 8 or 16 points
Selectable with the front DIP SW
(*) Factory default setting
Output at the loss of communication
:
Hold the output (*), Reset the output
Selectable with the front DIP SW
(*) Factory default setting
Configurator connection
: 2.5 dia. miniature jack
■Recommended solderless terminal
DeviceNet COMMUNICATION
Network cable
: Approved for DeviceNet
Baud rate setting
: 125 kbps (default), 250 kbps, 500 kbps, auto-tracking (rotary switch)
(Refer to the instruction manual.)
Status indicator LEDs
: MS, NS
(Refer to the instruction manual for details.)
Node address setting
: 1 - 63 (rotary switch, default:00)
(Refer to the instruction manual.)
Communication:
Supports poll and cyclic
(Bit-strobe and COS (change of state) are not suported)
OUTPUT SPECIFICATIONS
Output supply voltage/current
: 24 V DC ±10 % / approx. 70 mA
Output range
: 4 to 20 mA DC
Load resistance
: ≤ 600 Ω
Operational range
: -15 to +115 % of output range
INSTALLATION
Supply voltage to network
: 11 – 25 V DC supplied through the network terminal block
Current Consumption
:
Approx. 35 mA @ 24 V DC
Approx. 55 mA @ 11 V DC
Supply output current
: Approx. 70 mA
Operating temperature
: -10 to +55°C (14 to 131°F)
Storage temperature
: -20 to +65°C (-4 to +149°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Atmosphere
: No corrosive gas or heavy dust
Mounting
: DIN rail (35 mm rail)
Weight
: 150 g (0.33 lb)
PERFORMANCE
Conversion accuracy
: ±0.1 %
Data range
: 0 – 10000 of the output range
(Scaling of converted data is configurable with the configurator software (model: R7CON))
Temp. coefficient
: ±0.015 %/°C (±0.008 %/°F)
Response time
: 250 msec. (0 – 90 %)
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 1500 V AC @ 1 minute (output 0 to output 1 to DeviceNet to external power supply)
STANDARDS & APPROVALS
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
FUNCTIONS
Output hold function:
Output at the loss of communication is selectable from output clear (fix the output at -15 %) and output hold (last normally received data) with DIP switch.
At the startup, it outputs -15 % until the communication is established and normal data is received.
EXTERNAL VIEW
TERMINAL ASSIGNMENTS
■ OUTPUT TERMINAL ASSIGNMENT
DATA CONVERSION
DATA ALLOCATION
I/O DATA DESCRIPTIONS
TRANSMISSION DATA DESCRIPTIONS
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM