ES-1947 Rev.0
LSMT4F
Power Transducer Series
HIGH-SPEED RESPONSE MULTI POWER TRANSDUCER
Functions & Features
• 30 msec. high-speed response
• By connecting just one circuit of the power system, AC current can be measured.
• 10-point analog and 2-point energy pulse output
• Various parameters can be configured using the front buttons or the configurator.
Typical Applications
• Multi-functional power measurement in electric device or in switching boards
MODEL: LSMT4F–[1][2][3]1–AD4[4]
ORDERING INFORMATION
• Code number: LSMT4F-[1][2][3]1-AD4[4]
Specify a code from below for each of [1] through [4].
(e.g. LSMT4F-12A1-AD4/Q)
• Specify the specification for option code /Q
(e.g. /C01)
• Non-specified orders will be shipped at default factory settings (No. ESU-1947). However, the power suffix code must
be specified.
Measured variables can be reconfigured with front panel or PC configurator software.
[1] CONFIGURATION
1
: Single phase / 2-wire and 3-wire, 3-phase / 3-wire
2
: Single phase / 2-wire and 3-wire,
3-phase / 3-wire and 4-wire
[2] INPUT
1
: 480 V / 1 A AC
2
: 480 V / 5 A AC
[3] OUTPUT
Current
A
: 4 – 20 mA DC
Voltage
4
: 0 – 10 V DC
5
: 0 – 5 V DC
6
: 1 – 5 V DC
DISCRETE OUTPUT
1
: Do 2-point
AUXILIARY POWER SUPPLY
AD4
: Universal
100 – 240 V AC (Operational range 85 – 264 V, 47 – 66 Hz) /
110 – 240 V DC (Operational range 99 – 264 V,
ripple 10 %p-p max)
[4] OPTIONS
blank
: none
/Q
: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
EX-FACTORY SETTING
/SET
: Preset according to the Ordering Information Sheet
(No. ESU-1947)
RELATED PRODUCTS
• PC Configurator cable (model: COP-US)
• PC configurator software (model: LSCFG)
Downloadable at our web site.
GENERAL SPECIFICATIONS
Construction
: Stand-alone; terminal access at the front
Degree of protection
: IP 20 (Terminal block, housing)
Connection
Voltage input
: M4 screw terminals (torque 1.4 N·m)
Current input
: M4 screw terminals (torque 1.4 N·m)
Output
: M3.5 screw terminals (torque 0.6 N·m)
Power
: M4 screw terminals (torque 1.4 N·m)
Configuration
Code 1
: Single phase/2-wire and 3-wire, 3-phase/3- wire balanced/unbalanced load
Code 2
: Single phase/2-wire and 3-wire, 3-phase/3- wire balanced/unbalanced load, 3-phase/4- wire balanced/unbalanced load
Screw terminal
: Nickel-plated steel
Housing material
: Flame-resistant resin (black)
Isolation
: Voltage input to current input to output signal to discrete output 1 to discrete output 2 to auxiliary power supply to FE
■ Measured variables
Voltage
: 1 – N, 2 – N, 3 – N, 1 – 2, 2 – 3, 3 – 1
Current
: 1, 2, 3, N
Active / reactive / apparent power
: 1, 2, 3, Σ
Power factor
: 1, 2, 3, Σ
Frequency
Active energy
Reactive energy
■
DISPLAY
:
Red LED; for setting and monitoring; signed
5 digits
INPUT SPECIFICATIONS
Frequency
: 50 / 60 Hz (45 – 65 Hz)
•
Voltage Input
Rated voltage
Line-to-line (delta voltage)
: 480 V
Line-neutral (phase voltage)
: 277 V (single phase / 2-wire and 3-wire)
Consumption VA
: ≤ U
LN
2
/ 300 kΩ / phase
Overload capacity
: 200 % of rating for 10 sec., 120 % continuous
Selectable primary voltage range
: 50 – 400 000 V
•
Current Input
Rated current
: 1 A or 5 A
Consumption VA
: ≤ I
2
· 0.01 Ω / phase
Overload capacity
: 4000 % of rating for 1 sec., 2000 % for
4 sec., 120 % continuous
Selectable primary current range
: 1 – 20 000 A
Selectable primary power range
: ≤ 2 G VA
Operational range
Voltage, current, apparent power
: ≤ 120 % of the rating
Active / reactive power
: -120 to +120 % of the rating
Frequency
: 45 – 65 Hz
Power factor
: -1 to +1
OUTPUT SPECIFICATIONS
■
DC Output
Load resistance
(output range)
4 - 20 mA DC: ≤ 600 Ω
0 - 10 V DC: ≥ 5kΩ
0 - 5 V DC: ≥ 1kΩ
1 - 5 V DC: ≥ 1kΩ
■
Open Collector
Energy count output
Max. rated load
: 130 V DC @ 50 mA
Continuous rated load
: 130 V DC @ 30 mA
Saturation voltage
: 1.5 V DC
When driving an inductive load, external contact protection and noise quenching recommended.
INSTALLATION
Auxiliary Power
•
AC
: < 20 VA
•
DC
: < 9 W
Operating temperature
: -10 to +55°C (14 to 131°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Mounting
: Surface or DIN rail
Weight
: 700 g (1.54 lb)
PERFORMANCE in percentage of rating
Accuracy
(at 23°C ±10°C or 73.4°F ±18°F, 45 – 65 Hz)
Voltage
:
±0.5 %
Percentage of 100 V at ≥ 1 V to < 100 V
Percentage of input voltage at ≥ 100 V
Current
: ±0.5 %
Power
: ±0.5 %
Percentage of the span of wattage as listed below
at < 100 V:
173.2 W (1 A) or 866 W (5 A) for 3 ph/3 w
100 W (1 A) or 500 W (5 A) for 1 ph/2 w
200 W (1 A) or 1000 W (5 A) for 1 ph/3 w
300 W (1 A) or 1500 W (5 A) for 3 ph/4 w
Percentage of the span of power based on input voltage and rated current (1 A or 5 A) at ≥ 100 V
PF
: ±0.5 %
Frequency
:
±0.2 %
Energy
:
±1 % (Load current 5 - 120 % PF 1; load current 10 - 120 % PF 0.5)
Response time (input frequency ≥ 50 Hz)
:
• Other than frequency:
≤ 30 msec. (0 – 99 %)
• Frequency:
≤ 50 msec. (0 – 99 %)
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 2000 V AC @ 1 minute
(Voltage input to current input to output signal to discrete output 1 to discrete output 2 to auxiliary power to FE)
STANDARDS & APPROVALS
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
Low Voltage Directive
EN 61010-1
Measurement Category II (input)
Installation Category II (auxiliary power)
Pollution Degree 2
Input to output: Reinforced insulation (480 V)
Output to auxiliary power: Reinforced insulation (300 V)
RoHS Directive
EXTERNAL VIEW
TERMINAL CONNECTIONS
Note: In order to improve EMC performance, bond the FE terminal to ground.
Caution: FE terminal is NOT a protective conductor terminal.
EXTERNAL DIMENSIONS unit: mm [inch]
MOUNTING REQUIREMENTS unit: mm [inch]