ES-7812-AF Rev.0
R7HL-DAC16ES
Remote I/O R7 Series
HI-SPEED LINK SYSTEM I/O MODULE
(discrete input & NPN transistor output, 8 points each, independent I/O common, tension clamp terminal block)
Functions & Features
• 8 points discrete input and 8 points NPN transistor output module for HLS
HLS is the abbreviation for “Hi-speed Link System” of Step Technica Co., Ltd.
MODEL:R7HL–DAC16ES-R[1]
ORDERING INFORMATION
• Code number: R7HL-DAC16ES-R[1]
Specify a code from below for [1].
(e.g. R7HL-DAC16ES-R/H/Q)
• Specify the specification for option code /Q
(e.g. /C01/SET)
I/O TYPE
DAC16ES
: Discrete input, 8 points
NPN transistor output, 8 points (independent I/O common)
POWER INPUT
DC Power
R
: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
[1] OPTIONS (multiple selections)
Communication Mode
blank
: Full-duplex
/H
: Half-duplex
Other Options
blank
: none
/Q
: Option other than the above (specify the specification)
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
EX-FACTORY SETTING
/SET
: Preset according to the Ordering Information Sheet
(No. ESU-7812-V)
GENERAL SPECIFICATIONS
Connection:
Tension clamp terminal block
Housing material
: Flame-resistant resin (gray)
Isolation
: Input to output to HLS to power to FG
Output at the loss of communication
:
Hold the output (*), Reset the output
Selectable with the front DIP SW
(*) Factory default setting
Status indicator LEDs
: PWR, RUN
(Refer to the instruction manual)
Discrete I/O status indicator LED
: LED turns on with I/O ON
HLS COMMUNICATION
Communication mode
:
Communication mode option code blank: Full-duplex
Communication mode option code /H: half-duplex
Network cable
• Shield cable
Full-duplex communication:
ZHY262PS and ZHT262PS
(Shinko Seisen Industry Co., Ltd.)
Half-duplex communication:
ZHY221PS (Shinko Seisen Industry Co., Ltd.)
• Dual-shield cable:
ZHY262PBA (Shinko Seisen Industry Co., Ltd.)
Transmission distance /
Transfer rate
:
100 meters (328 ft)/12 Mbps (default),
200 meters (656 ft)/6 Mbps
(Selectable with DIP switch)
Station address
: Rotary switch
(Refer to the instruction manual)
Data allocation
: 1
Terminating resistor
: Built-in (Selected with the DIP SW; factory setting: disabled)
INPUT SPECIFICATIONS
Common
: Positive or negative common (NPN/PNP) per 8 points
Maximum inputs applicable at once:
No limit (at 24 V DC)
Rated input voltage
: 24 V DC ±10 %; ripple 5 %p-p max.
ON voltage / current
: ≥ 15 V DC (X0 through X7 to COM) / ≥ 3.5 mA
OFF voltage / current
: ≤ 5 V DC (X0 through X7 to COM) / ≤ 1 mA
Input current
: ≤ 5.5 mA per point at 24 V DC
Input resistance
: Approx. 4.4 kΩ
ON delay
: ≤ 0.5 msec.
OFF delay
: ≤ 0.5 msec.
OUTPUT SPECIFICATIONS
Common
: Negative common (NPN) per 8 points
Maximum outputs applicable at once:
No limit (at 24 V DC)
Rated load voltage
: 24 V DC ±10 %
Rated output current
: 0.25 A per point, 2.0 A per common
Residual voltage
: ≤ 1.2 V
Leakage current
: ≤ 0.1 mA
ON delay
: ≤ 0.2 msec.
OFF delay
: ≤ 0.5 msec.
(When driving an inductive load, connect a diode in parallel with the load.)
INSTALLATION
Current consumption
•
DC
: Approx. 40 mA
Operating temperature
: -10 to +55°C (14 to 131°F)
Storage temperature
: -20 to +65°C (-4 to +149°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Atmosphere
: No corrosive gas or heavy dust
Mounting
: DIN rail (35 mm rail)
Weight
: 200 g (0.44 lb)
PERFORMANCE
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 1500 V AC @ 1 minute (input to output to HLS to power input to FG)
STANDARDS & APPROVALS
Refer to the manuals to comply with the standards.
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
EXTERNAL VIEW
COMMUNICATION CABLE CONNECTIONS
TERMINAL ASSIGNMENTS
■ I/O TERMINAL ASSIGNMENT
■ POWER SUPPLY TERMINAL ASSIGNMENT
■ NETWORK TERMINAL ASSIGNMENT
I/O DATA DESCRIPTIONS
EXTERNAL DIMENSIONS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
Note: In order to improve EMC performance, bond the FG terminal to ground.
Caution: FG terminal is NOT a protective conductor terminal.