ES-7812-AX Rev.0
R7HL-LC2
Remote I/O R7 Series
HI-SPEED LINK SYSTEM I/O MODULE
(strain gauge input, 2 points, isolated, with monitor output)
Functions & Features
• 2 points strain gauge input for HLS
• Individual channels, zero adjustment, span adjustment, and scaling can be set with the configurator software (model: R7CON)
HLS is the abbreviation for “Hi-speed Link System” of Step Technica Co., Ltd.
MODEL: R7HL-LC2–R[1]
ORDERING INFORMATION
• Code number: R7HL-LC2-R[1]
Specify a code from below for [1].
(e.g. R7HL-LC2-R/H/R20/F2K/Q)
• Specify the specification for option code /Q
(e.g. /C01/SET)
I/O TYPE
LC2
: Strain gauge input, 2 points (with monitor output)
POWER INPUT
DC Power
R
: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
[1] OPTIONS (multiple selections)
Communication Mode
blank
: Full-duplex
/H
: Half-duplex
Input Range
(be sure to specify)
/R20
: -2 - +2 mV/V
/R10
: -1 - +1 mV/V
/R05
: -0.5 - +0.5 mV/V
CR Filter
(be sure to specify)
/F2K
: 2 kHz/2 Hz
/F1
: 1 Hz/2 Hz
Other Options
blank
: none
/Q
: Option other than the above (specify the specification)
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
EX-FACTORY SETTING
/SET
: Preset according to the Ordering Information Sheet
(No. ESU-7812-AX)
RELATED PRODUCTS
• PC Configurator cable (model: MCN-CON or COP-US)
• PC configurator software (model: R7CON)
Downloadable at our web site.
GENERAL SPECIFICATIONS
Connection:
M3 separable screw terminal (torque 0.5 N·m)
Solderless terminal
: Refer to the drawing at the end of the section.
•
Communication cable
Recommended manufacture
: J.S.T. Mfg. Co., Ltd.
Applicable wire size
: 0.2 to 0.5 mm
2
(AWG 26 to 22)
•
Others
Recommended manufacture
: J.S.T. Mfg. Co., Ltd.,
NICHIFU Co., Ltd.
Applicable wire size
: 0.25 to 1.65 mm
2
(AWG 22 to 16)
Screw terminal
: Nickel-plated steel
Housing material
: Flame-resistant resin (gray)
Isolation
: Input 0 or output 0 to input 1 or output 1 to HLS to power to FG
Zero adjustments
: Configurable via R7CON
Span adjustments
: Configurable via R7CON
Load coefficient:
Configurable via R7CON
Averaging:
2 (*), 4, 8, 16, 32, 64, 128, 256, 512, 1024
Selectable with the front DIP SW
(*) Factory default setting
Excitation Voltage:
5 V (*), 2.5 V
Selectable with the front DIP SW
(*) Factory default setting
Lowpass filter:
2 kHz (1 Hz for option /F1)(*), 2 Hz
Selectable with the front DIP SW
(*) Factory default setting
Monitor output:
Configurable via R7CON
Status indicator LEDs
: PWR, RUN
(Refer to the instruction manual)
Input status indicator LED
: 0 to F
(Refer to the instruction manual)
Configurator connection
: 2.5 dia. miniature jack
■Recommended solderless terminal
HLS COMMUNICATION
Communication mode
:
Communication mode option code blank: Full-duplex
Communication mode option code /H: half-duplex
Network cable
• Shield cable
Full-duplex communication:
ZHY262PS and ZHT262PS
(Shinko Seisen Industry Co., Ltd.)
Half-duplex communication:
ZHY221PS (Shinko Seisen Industry Co., Ltd.)
• Dual-shield cable:
ZHY262PBA (Shinko Seisen Industry Co., Ltd.)
Transmission distance /
Transfer rate
:
100 meters (328 ft)/12 Mbps (default),
200 meters (656 ft)/6 Mbps
(Selectable with DIP switch)
Station address
: Rotary switch
(Refer to the instruction manual)
Data allocation
: 2
Terminating resistor
: Built-in (Selected with the DIP SW; factory setting: disabled)
INPUT SPECIFICATIONS
■Strain Gauge Input:
•
Strain Gauge
Input range
:
Option code /R20
-2 – +2 mV/V (at 5 V excitation)
-4 – +4 mV/V (at 2.5 V excitation)
Option code /R10
-1 – +1 mV/V (at 5 V excitation)
-2 – +2 mV/V (at 2.5 V excitation)
Option code /R05
-0.5 – +0.5 mV/V (at 5 V excitation)
-1 – +1 mV/V (at 2.5 V excitation)
Max. Input range
:
Option code /R20
-3 – +3 mV/V (at 5 V excitation)
-6 – +6 mV/V (at 2.5 V excitation)
Option code /R10
-1.5 – +1.5 mV/V (at 5 V excitation)
-3 – +3 mV/V (at 2.5 V excitation)
Option code /R05
-0.75 – +0.75 mV/V (at 5 V excitation)
-1.5 – +1.5 mV/V (at 2.5 V excitation)
Zero adjustment
:
Option code /R20
-1 – +1 mV/V (at 5 V excitation)
-2 – +2 mV/V (at 2.5 V excitation)
Option code /R10
-0.5 – +0.5 mV/V (at 5 V excitation)
-1 – +1 mV/V (at 2.5 V excitation)
Option code /R05
-0.25 – +0.25 mV/V (at 5 V excitation)
-0.5 – +0.5 mV/V (at 2.5 V excitation)
Lowpass filter
:
Approx. 2 kHz or approx. 2 Hz (option code /F2K)
Approx. 1 Hz or approx. 2 Hz (option code /F1)
Conversion rate
: min. 2000 samples/sec.
•
Excitation
: 5 V ±10 % or 2.5 V ±10 %
(Input range doubled in the case of 2.5 V excitation)
Maximum current
: max. 60 mA (at 5 V excitation)
max. 100 mA (at 2.5 V excitation)
OUTPUT SPECIFICATIONS
Output range
: -10 – +10 V DC (of -10000 – +10000 (% × 100))
Load resistance
: ≥ 100 kΩ
Operational range
:
-115 - +115 %
INSTALLATION
Current consumption
•
DC
: Approx. 150 mA
Operating temperature
: -10 to +55°C (14 to 131°F)
Storage temperature
: -20 to +65°C (-4 to +149°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Atmosphere
: No corrosive gas or heavy dust
Mounting
: DIN rail (35 mm rail)
Weight
: 220 g (0.49 lb)
PERFORMANCE
Accuracy:
Option code except /R05
±0.04 % (Averaging 128 samples or more)
±0.05 % (Averaging 64 samples)
±0.10 % (Averaging 8, 16, 32 samples)
±0.15 % (Averaging 4 samples)
±0.20 % (Averaging 2 samples)
Option code /R05
±0.05 % (Averaging 512 samples or more)
±0.10 % (Averaging 64, 128, 256 samples)
±0.20 % (Averaging 16, 32 samples)
±0.30 % (Averaging 2, 4, 8 samples)
Monitor output accuracy: ±0.1 %
Data range
: -10000 – +10000 of the input range (% × 100)
Temperature coefficient:
Strain gauge input: ±0.015 %/°C (±0.008 %/°F)
Monitor output: ±0.015 %/°C (±0.008 %/°F)
Input delay time:
Lowpass filter 2 kHz max. 20 msec. (0 - 90 %)
Lowpass filter 2 Hz max. 200 msec. (0 - 90 %)
Lowpass filter 1 Hz max. 400 msec. (0 - 90 %)
Output delay time:
≤ 250 msec. (0 – 90 %)
Resolution
: 1/10000
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 1500 V AC @ 1 minute (input 0 or output 0 to Input 1 or output 1 to HLS to power input to FG)
STANDARDS & APPROVALS
Refer to the manuals to comply with the standards.
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
EXTERNAL VIEW
COMMUNICATION CABLE CONNECTIONS
TERMINAL ASSIGNMENTS
■ I/O TERMINAL ASSIGNMENT
DATA CONVERSION
I/O DATA DESCRIPTIONS
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
Note: In order to improve EMC performance, bond the FG terminal to ground.
Caution: FG terminal is NOT a protective conductor terminal.