ES-7812-AM Rev.0
R7HL-PA4E
Remote I/O R7 Series
HI-SPEED LINK SYSTEM I/O MODULE
(totalized pulse input, 4 points, non-isolated, e-CON connector)
Functions & Features
• 4 points totalized pulse input module for HLS
HLS is the abbreviation for “Hi-speed Link System” of Step Technica Co., Ltd.
MODEL:R7HL–PA4E-R[1]
ORDERING INFORMATION
• Code number: R7HL-PA4E-R[1]
Specify a code from below for [1].
(e.g. R7HL-PA4E-R/H/Q)
• Specify the specification for option code /Q
(e.g. /C01/SET)
I/O TYPE
PA4E
: Totalized pulse input, 4 points (non-isolated)
POWER INPUT
DC Power
R
: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
[1] OPTIONS (multiple selections)
Communication Mode
blank
: Full-duplex
/H
: Half-duplex
Other Options
blank
: none
/Q
: Option other than the above (specify the specification)
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
EX-FACTORY SETTING
/SET
: Preset according to the Ordering Information Sheet
(No. ESU-7812-AM)
GENERAL SPECIFICATIONS
Connection
HLS
: Tension clamp terminal block
Power & Sensor excitation
: Link connector
Input
: e-CON connector
Housing material
: Flame-resistant resin (gray)
Isolation
: Input or sensor excitation to HLS to power
Status indicator LEDs
: PWR, RUN
(Refer to the instruction manual)
Input status indicator LED
: Red LED turns on with contact on (Lo between GND and IN0 through IN3)
HLS COMMUNICATION
Communication mode
:
Communication mode option code blank: Full-duplex
Communication mode option code /H: half-duplex
Network cable
• Shield cable
Full-duplex communication:
ZHY262PS and ZHT262PS
(Shinko Seisen Industry Co., Ltd.)
Half-duplex communication:
ZHY221PS (Shinko Seisen Industry Co., Ltd.)
• Dual-shield cable:
ZHY262PBA (Shinko Seisen Industry Co., Ltd.)
Transmission distance /
Transfer rate
:
100 meters (328 ft)/12 Mbps (default),
200 meters (656 ft)/6 Mbps
(Selectable with DIP switch)
Station address
: Rotary switch
(Refer to the instruction manual)
Data allocation
: 4
Terminating resistor
: Built-in (Selected with the DIP SW; factory setting: disabled)
INPUT SPECIFICATIONS
■
Sensor Excitation (External)
Supply voltage
: 24 V DC ± 10 % (ripple 5 %p-p max. )
Supply current
: 0.4 A per point, 1.6 A per common
■ Totalized
Pulse Input
Common
: Positive common (NPN) per 4 points
Rated input voltage
: 24 V DC ±10 %; ripple 5 %p-p max.
ON voltage / current
: ≥ 16 V DC (input to +24V) / ≥ 7.2 mA
OFF voltage / current
: ≤ 6 V DC (input to +24V) / ≤ 2.5 mA
Input current
: ≤ 11.2 mA per point at 24 V DC
Input resistance
: Approx. 2 kΩ
Max. frequency
: 10 kHz
Min. pulse width requirement
: 20 μsec. for both ON and OFF
■
Counter
Count range
: 0000H to FFFFH (16 bits)
Operating mode
: Ring up counter
Max. ring value
: FFFFH
Pulse detection
: Sink (the output of sensor turns on)
Count reset
: LSB of Do area (set per channel)
0: Count up
1: Reset
INSTALLATION
Current consumption
•
DC
: Approx. 50 mA
Operating temperature
: -10 to +55°C (14 to 131°F)
Storage temperature
: -20 to +65°C (-4 to +149°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Atmosphere
: No corrosive gas or heavy dust
Mounting
: DIN rail (35 mm rail)
Weight
: 130 g (0.29 lb)
PERFORMANCE
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 1500 V AC @ 1 minute (input or sensor excitation to HLS to power input)
STANDARDS & APPROVALS
Refer to the manuals to comply with the standards.
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
EXTERNAL VIEW
COMMUNICATION CABLE CONNECTIONS
TERMINAL ASSIGNMENTS
■ INPUT TERMINAL ASSIGNMENT
■ POWER SUPPLY / SENSOR EXC. TERMINAL ASSIGNMENT
■ NETWORK TERMINAL ASSIGNMENT
I/O DATA DESCRIPTIONS
EXTERNAL DIMENSIONS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM