ES-7812-AB Rev.0
R7HL-SVF4
Remote I/O R7 Series
HI-SPEED LINK SYSTEM I/O MODULE
(high-speed DC voltage/current input, 4 points, non-isolated)
Functions & Features
• 4 points high-speed DC voltage/current input module for HLS
• Input range can be selected with the front DIP switches for all channels
• Individual channels, zero adjustment, span adjustment, and scaling can be set with the configurator software (model: R7CON)
HLS is the abbreviation for “Hi-speed Link System” of Step Technica Co., Ltd.
MODEL: R7HL–SVF4-R[1]
ORDERING INFORMATION
• Code number: R7HL-SVF4-R[1]
Specify a code from below for [1].
(e.g. R7HL-SVF4-R/H/Q)
• Specify the specification for option code /Q
(e.g. /C01/SET)
I/O TYPE
SVF4
: DC voltage /current input high-speed, 4 points
(non-isolated) (10 V/20 mA)
POWER INPUT
DC Power
R
: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
[1] OPTIONS (multiple selections)
Communication Mode
blank
: Full-duplex
/H
: Half-duplex
Other Options
blank
: none
/Q
: Option other than the above (specify the specification)
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
EX-FACTORY SETTING
/SET
: Preset according to the Ordering Information Sheet
(No. ESU-7812-AB)
RELATED PRODUCTS
• PC Configurator cable (model: MCN-CON or COP-US)
• PC configurator software (model: R7CON)
Downloadable at our web site.
GENERAL SPECIFICATIONS
Connection:
M3 separable screw terminal (torque 0.5 N·m)
Solderless terminal
: Refer to the drawing at the end of the section.
•
Communication cable
Recommended manufacture
: J.S.T. Mfg. Co., Ltd.
Applicable wire size
: 0.2 to 0.5 mm
2
(AWG 26 to 22)
•
Others
Recommended manufacture
: J.S.T. Mfg. Co., Ltd.,
NICHIFU Co., Ltd.
Applicable wire size
: 0.25 to 1.65 mm
2
(AWG 22 to 16)
Screw terminal
: Nickel-plated steel
Housing material
: Flame-resistant resin (gray)
Isolation
: Input to HLS to power input to FG
Zero adjustments
: Configurable via R7CON
Span adjustments
: Configurable via R7CON
Input range
: Selectable with the DIP SW on the front of the unit or configurable via R7CON
Number of times of averaging
: No averaging (*), 2 samples, 4 sampes, 8 samples
Configurable via R7CON
(*) Factory default setting
Status indicator LEDs
: PWR, RUN
(Refer to the instruction manual)
Configurator connection
: 2.5 dia. miniature jack
■Recommended solderless terminal
HLS COMMUNICATION
Communication mode
:
Communication mode option code blank: Full-duplex
Communication mode option code /H: half-duplex
Network cable
• Shield cable
Full-duplex communication:
ZHY262PS and ZHT262PS
(Shinko Seisen Industry Co., Ltd.)
Half-duplex communication:
ZHY221PS (Shinko Seisen Industry Co., Ltd.)
• Dual-shield cable:
ZHY262PBA (Shinko Seisen Industry Co., Ltd.)
Transmission distance /
Transfer rate
:
100 meters (328 ft)/12 Mbps (default),
200 meters (656 ft)/6 Mbps
(Selectable with DIP switch)
Station address
: Rotary switch
(Refer to the instruction manual)
Data allocation
: 4
Terminating resistor
: Built-in (Selected with the DIP SW; factory setting: disabled)
INPUT SPECIFICATIONS
■
DC Current
Input resistance
: 50 Ω
Input range
: -20 to +20 mA DC, 0 to 20 mA DC,
4 to 20 mA DC
■
Narrow span voltage
Input resistance
: ≥ 100 kΩ
Input range
: :-1 to +1 V DC, 0 to 1 V DC, -0.5 to +0.5 V DC
■
Wide span voltage
Input resistance
: ≥ 1 MΩ
Input range
: :-10 to +10 V DC (*), -5 to +5 V DC,
0 to 10 V DC, 0 to 5 V DC, 1 to 5 V DC
(*) Factory default setting
INSTALLATION
Current consumption
•
DC
: Approx. 90 mA
Operating temperature
: -10 to +55°C (14 to 131°F)
Storage temperature
: -20 to +65°C (-4 to +149°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Atmosphere
: No corrosive gas or heavy dust
Mounting
: DIN rail (35 mm rail)
Weight
: 200 g (0.44 lb)
PERFORMANCE
Conversion rate / Conversion accuracy
: 2 msec. / ±0.1 %
Data range
: 0 – 10000 of the input range
(Scaling of converted data is configurable with the configurator software (model: R7CON))
Temp. coefficient
: ±0.015 %/°C (±0.008 %/°F)
Response time
: Conversion rate × 2 + scan time (0 – 90 %)
Scan time depends on the Final Satellite (FS) value of Center IC (master) configuration and transfer rate (T
BPS
).
It is calculated with the following formula.
Scan time = 182 × FS × T
BPS
(sec.)
E.g) When "Final satellite value" = 63, transfer rate = 12
Mbps, scan time is = 182 × 63 × 1 ÷ 12 Mbps = 0.9555 msec.
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 1500 V AC @ 1 minute (input to HLS to power to FG)
EXTERNAL VIEW
COMMUNICATION CABLE CONNECTIONS
TERMINAL ASSIGNMENTS
■ INPUT TERMINAL ASSIGNMENT
DATA CONVERSION
I/O DATA DESCRIPTIONS
Scaling of analog input is configurable with the configurator software (model: R7CON). Refer to the software manual for details.
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
Caution: FG terminal is NOT a protective conductor terminal.