ES-7812-E Rev.0
R7HL-YS2
Remote I/O R7 Series
HI-SPEED LINK SYSTEM I/O MODULE
(DC current output, 2 points, isolated)
Functions & Features
• 2 points DC current output module for HLS
• Individual channels, zero adjustment, span adjustment, and scaling can be set with the configurator software (model: R7CON)
HLS is the abbreviation for “Hi-speed Link System” of Step Technica Co., Ltd.
MODEL: R7HL–YS2-R[1]
ORDERING INFORMATION
• Code number: R7HL-YS2-R[1]
Specify a code from below for [1].
(e.g. R7HL-YS2-R/H/Q)
• Specify the specification for option code /Q
(e.g. /C01/SET)
I/O TYPE
YS2
: DC current output, 2 points
POWER INPUT
DC Power
R
: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
[1] OPTIONS (multiple selections)
Communication Mode
blank
: Full-duplex
/H
: Half-duplex
Other Options
blank
: none
/Q
: Option other than the above (specify the specification)
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
EX-FACTORY SETTING
/SET
: Preset according to the Ordering Information Sheet
(No. ESU-7812-E)
RELATED PRODUCTS
• PC Configurator cable (model: MCN-CON or COP-US)
• PC configurator software (model: R7CON)
Downloadable at our web site.
GENERAL SPECIFICATIONS
Connection:
M3 separable screw terminal (torque 0.5 N·m)
Solderless terminal
: Refer to the drawing at the end of the section.
•
Communication cable
Recommended manufacture
: J.S.T. Mfg. Co., Ltd.
Applicable wire size
: 0.2 to 0.5 mm
2
(AWG 26 to 22)
•
Others
Recommended manufacture
: J.S.T. Mfg. Co., Ltd.,
NICHIFU Co., Ltd.
Applicable wire size
: 0.25 to 1.65 mm
2
(AWG 22 to 16)
Screw terminal
: Nickel-plated steel
Housing material
: Flame-resistant resin (gray)
Isolation
: Output 0 to output 1 to power to HLS to FG
Zero adjustments
: Configurable via R7CON
Span adjustments
: Configurable via R7CON
Output at the loss of communication
:
Hold the output (*), Reset the output
Selectable with the front DIP SW
(*) Factory default setting
Status indicator LEDs
: PWR, RUN
(Refer to the instruction manual)
Configurator connection
: 2.5 dia. miniature jack
■Recommended solderless terminal
HLS COMMUNICATION
Communication mode
:
Communication mode option code blank: Full-duplex
Communication mode option code /H: half-duplex
Network cable
• Shield cable
Full-duplex communication:
ZHY262PS and ZHT262PS
(Shinko Seisen Industry Co., Ltd.)
Half-duplex communication:
ZHY221PS (Shinko Seisen Industry Co., Ltd.)
• Dual-shield cable:
ZHY262PBA (Shinko Seisen Industry Co., Ltd.)
Transmission distance /
Transfer rate
:
100 meters (328 ft)/12 Mbps (default),
200 meters (656 ft)/6 Mbps
(Selectable with DIP switch)
Station address
: Rotary switch
(Refer to the instruction manual)
Data allocation
: 2
Terminating resistor
: Built-in (Selected with the DIP SW; factory setting: disabled)
OUTPUT SPECIFICATIONS
Output range
: 4 to 20 mA DC
Load resistance
: ≤ 600 Ω
Operational range
: -15 to +115 % of output range
INSTALLATION
Current consumption
•
DC
: Approx. 140 mA
Operating temperature
: -10 to +55°C (14 to 131°F)
Storage temperature
: -20 to +65°C (-4 to +149°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Atmosphere
: No corrosive gas or heavy dust
Mounting
: DIN rail (35 mm rail)
Weight
: 200 g (0.44 lb)
PERFORMANCE
Conversion accuracy
: ±0.1 %
Data range
: 0 – 10000 of the output range
(Scaling of converted data is configurable with the configurator software (model: R7CON))
Temp. coefficient
: ±0.015 %/°C (±0.008 %/°F)
Response time
: 250 msec. (0 – 90 %)
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 1500 V AC @ 1 minute (output 0 to output 1 to power input to HLS to FG)
STANDARDS & APPROVALS
Refer to the manuals to comply with the standards.
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
FUNCTIONS
Output hold function:
Output at the loss of communication is selectable from output clear (fix the output at -15 %) and output hold (last normally received data) with DIP switch.
At the startup, it outputs -15 % until the communication is established and normal data is received.
EXTERNAL VIEW
COMMUNICATION CABLE CONNECTIONS
TERMINAL ASSIGNMENTS
■ OUTPUT TERMINAL ASSIGNMENT
DATA CONVERSION
I/O DATA DESCRIPTIONS
Scaling of analog output is configurable with the configurator software (model: R7CON). Refer to the software manual for details.
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
Note: In order to improve EMC performance, bond the FG terminal to ground.
Caution: FG terminal is NOT a protective conductor terminal.