ES-7812-AV Rev.0
R7HL-YV4L
Remote I/O R7 Series
HI-SPEED LINK SYSTEM I/O MODULE
(DC voltage output, 4 points, isolated, 12 bits data)
Functions & Features
• 4 points DC voltage output module for HLS
• Output range can be selected with the front DIP switches for all channels
• Individual channels, zero adjustment, and span adjustment can be set with the configurator software (model: R7CON)
HLS is the abbreviation for “Hi-speed Link System” of Step Technica Co., Ltd.
MODEL: R7HL–YV4L-R[1]
ORDERING INFORMATION
• Code number: R7HL-YV4L-R[1]
Specify a code from below for [1].
(e.g. R7HL-YV4L-R/H/3/Q)
• Specify the specification for option code /Q
(e.g. /C01/SET)
I/O TYPE
YV4L
: DC votage output, 4 points
(isolated, 12 bits data)
POWER INPUT
DC Power
R
: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
[1] OPTIONS (multiple selections)
Communication Mode
blank
: Full-duplex
/H
: Half-duplex
Transfer rate
blank
: 12 Mbps/6 Mbps
/3
: 3 Mbps
Other Options
blank
: none
/Q
: Option other than the above (specify the specification)
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
EX-FACTORY SETTING
/SET
: Preset according to the Ordering Information Sheet
(No. ESU-7812-AV)
RELATED PRODUCTS
• PC Configurator cable (model: MCN-CON or COP-US)
• PC configurator software (model: R7CON)
Downloadable at our web site.
GENERAL SPECIFICATIONS
Connection:
M3 separable screw terminal (torque 0.5 N·m)
Solderless terminal
: Refer to the drawing at the end of the section.
•
Communication cable
Recommended manufacture
: J.S.T. Mfg. Co., Ltd.
Applicable wire size
: 0.2 to 0.5 mm
2
(AWG 26 to 22)
•
Others
Recommended manufacture
: J.S.T. Mfg. Co., Ltd.,
NICHIFU Co., Ltd.
Applicable wire size
: 0.25 to 1.65 mm
2
(AWG 22 to 16)
Screw terminal
: Nickel-plated steel
Housing material
: Flame-resistant resin (gray)
Isolation
: Output 0 to output 1 to output 2 to output 3 to HLS to power to FG
Zero adjustments
: Configurable via R7CON
Span adjustments
: Configurable via R7CON
Output range
: Selectable with the front DIP SW or configurable via R7CON
Output at the loss of communication
:
Hold the output (*), Reset the output
Selectable with the front DIP SW
(*) Factory default setting
Status indicator LEDs
: PWR, RUN
(Refer to the instruction manual)
Configurator connection
: 2.5 dia. miniature jack
■Recommended solderless terminal
HLS COMMUNICATION
Communication mode
:
Communication mode option code blank: Full-duplex
Communication mode option code /H: half-duplex
Network cable
• Shield cable
Full-duplex communication:
ZHY262PS and ZHT262PS
(Shinko Seisen Industry Co., Ltd.)
Half-duplex communication:
ZHY221PS (Shinko Seisen Industry Co., Ltd.)
• Dual-shield cable:
ZHY262PBA (Shinko Seisen Industry Co., Ltd.)
Transfer rate code
:
blank: 100 meters (328 ft)/12 Mbps (default),
200 meters (656 ft)/6 Mbps
/3: 300 meters (984 ft)/3 Mbps
(Selectable with DIP switch)
Station address
: Rotary switch
(Refer to the instruction manual)
Data allocation
: 1
Terminating resistor
: Built-in (Selected with the DIP SW; factory setting: disabled)
OUTPUT SPECIFICATIONS
Output range
: -10 – +10 V DC (*), -5 – +5 V DC, 0 – 10 V DC,
0 – 5 V DC, 1 – 5 V DC
(*) factory default setting
Load resistance
: ≥ 100 kΩ
Operational range
: 0 – 100 % of the output range
INSTALLATION
Current consumption
•
DC
: Approx. 75 mA
Operating temperature
: -10 to +55°C (14 to 131°F)
Storage temperature
: -20 to +65°C (-4 to +149°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Atmosphere
: No corrosive gas or heavy dust
Mounting
: DIN rail (35 mm rail)
Weight
: 180 g (0.40 lb)
PERFORMANCE
Conversion accuracy
: ±0.1 %
Data range
: 0 – 4095 of the output range
Temp. coefficient
: ±0.015 %/°C (±0.008 %/°F)
Response time
: 250 msec. (0 – 90 %)
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 1500 V AC @ 1 minute (output 0 to output 1 to output 2 to output 3 to HLS to power input to FG)
STANDARDS & APPROVALS
Refer to the manuals to comply with the standards.
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
EXTERNAL VIEW
COMMUNICATION CABLE CONNECTIONS
TERMINAL ASSIGNMENTS
■ OUTPUT TERMINAL ASSIGNMENT
DATA CONVERSION
■ 12 BITS DATA CONVERSION
The 12 bits digital data of 0 to 4095 (0 to 100 %) is converted to analog value (0 to 100 %) by each output range.
Output range refers range of the output, when output exceeds this range it is fixed to 0 or 100 %.
I/O DATA DESCRIPTIONS
Scaling of analog output is configurable with the configurator software (model: R7CON). Refer to the software manual for details.
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
Note: In order to improve EMC performance, bond the FG terminal to ground.
Caution: FG terminal is NOT a protective conductor terminal.