ES-6247 Rev.3
R10M-CT4E
Plug-in Remote I/O R10 Series
MODBUS I/O MODULE
(4 points, RMS sensing, clamp-on current sensor input)
Functions & Features
• Plug-in construction
• Modbus-RTU protocol communication
• Easy-to-install clamp-on type current sensor without needing a current transformer
• Wide input range from 5 A up to 600 A
• High-density mounting
MODEL: R10M-CT4E-R[1]
ORDERING INFORMATION
• Code number: R10M-CT4E-R[1]
Specify a code from below for [1].
(e.g. R10M-CT4E-R/Q)
• Specify the specification for option code /Q
(e.g. /C01)
I/O TYPE
CT4E
: Clamp-on current sensor CLSE use 4 points
POWER INPUT
DC Power
R
: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
[1] OPTIONS
blank
: none
/Q
: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
RELATED PRODUCTS
• Installation base (model: R10-BS)
• PC Configurator cable (model: MCN-CON or COP-US)
• PC configurator software (model: R10CFG)
Downloadable at our web site.
• Clamp-on current sensor (model: CLSE)
The clamp-on current sensors, not included in this product package, must be ordered separately. Required number depends upon the system configuration.
PACKAGE INCLUDES...
• Terminating resistor 110 Ω (0.25 W)
GENERAL SPECIFICATIONS
Construction
: Plug-in
Connection
• Connected to base with connector
• Base
M2.6 screw terminals (torque: 0.5 N·m)
Applicable solderless terminal size (M3)
Screw terminal
: Nickel-plated steel
Housing material
: Flame-resistant resin (black)
Isolation
: Input to Modbus to power input to FE1
Input waveform
RMS sensing
: Up to 15 % of 3rd harmonic content
Status indicators
: Power, Run, Error
Configuration
: Select sensors for 4 points (CT1, CT2, CT3, CT4) each with PC Configurator Software (model: R10CFG)
Configurator connection
: 2.5 dia. miniature jack
■Recommended solderless terminal size - M3 (unit: mm)
MODBUS COMMUNICATION
RS-485
Standard
: Conforms to TIA/EIA-485-A
Protocol
: Modbus-RTU, Modbus-ASCII
Transmission distance
: 500 meters max.
Transmission media
: Shielded twisted-pair cable
(CPEV-S 0.9 dia.)
Status indicator LED:
RD, SD
Transmission setting
: PC configurator software
INPUT SPECIFICATIONS
Input setting
: PC configurator software
Clamp-on current sensor
(CT1, CT2, CT3, CT4
)
Input (sensor & range)
CLSE-R5
: 0 – 5 A
CLSE-05
: 0 – 50 A
CLSE-10
: 0 – 100 A
CLSE-20
: 0 – 200 A
CLSE-40
: 0 – 400 A
CLSE-60
: 0 – 600 A
Frequency
: 50 / 60 Hz (45 - 65 Hz)
Operational range
: 0 – 105 % of rating
Overload capacity
CLSE-R5
: 10 A continuous
CLSE-05
: 60 A continuous
CLSE-10
: 120 A continuous
CLSE-20
: 240 A continuous
CLSE-40
: 480 A continuous
CLSE-60
: 720 A continuous
Note: Be sure that the input voltage is of 480 V or less.
INSTALLATION
Current consumption
: ≤ 90 mA
Operating temperature
: -10 to +55°C (14 to 131°F)
Storage temperature
: -10 to +55°C (14 to 131°F)
Operating humidity
: 10 to 90 %RH (non-condensing)
Atmosphere
: No corrosive gas or heavy dust
Mounting
: Installation Base (model: R10-BS)
Weight
: 120 g (0.26 lb) except base
PERFORMANCE
Conversion accuracy
: ±1 % except the sensor accuracy
Conversion rate
: 14 msec.
Data range
CLSE-R5
:
Integer that engineering unit value (A) multiplied by 1000
CLSE-05, CLSE-10, CLSE-20
: Integer that engineering unit value (A) multiplied by 100
CLSE-40, CLSE-60
: Integer that engineering unit value (A) multiplied by 10
(Scaling of converted data is configurable with the configurator software)
Temp. coefficient
: ±0.03 %/°C (±0.02 %/°F)
Response time
: ≤ 2 sec. (0 – 90 %)
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 1500 V AC @ 1 minute (input to Modbus to power input to FE1)
STANDARDS & APPROVALS
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
CONFIGURATOR SOFTWARE SETTING
The following parameters can be set with using PC Configurator Software (model: R10CFG)
Refer to the users manual for the R10CFG for detailed operation of the software program.
EXTERNAL VIEW
MODBUS WIRING CONNECTION
TERMINAL ASSIGNMENTS
* Base does not come with the unit. Please order separately.
MODBUS FUNCTION CODES & SUPPORTED CODES
MODBUS I/O ASSIGNMENT
DATA CONVERSION
EXTERNAL DIMENSIONS unit: mm [inch]
MOUNTING REQUIREMENTS unit: mm [inch]
* Mounting requirements for base.
TERMINAL ASSIGNMENTS
* Base does not come with the unit. Please order separately.
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
Note: In order to improve EMC performance, bond the FE1 terminal to ground.
Caution: FE1 terminal is NOT a protective conductor terminal.