ES-7781-BC Rev.4
R6S-DA4
Remote I/O R6 Series
DISCRETE INPUT MODULE, 4 points
(tension clamp)
Functions & Features
• Discrete input module (positive or negative common) with 4 channels
MODEL: R6S–DA4[1]
ORDERING INFORMATION
• Code number: R6S-DA4[1]
Specify a code from below for [1].
(e.g. R6S-DA4/Q)
• Specify the specification for option code /Q
(e.g. /C01)
[1] OPTIONS
blank
: none
/Q
: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
RELATED PRODUCTS
• PC Configurator cable (model: MCN-CON or COP-US)
• PC configurator software (model: R6CON)
Downloadable at our web site.
GENERAL SPECIFICATIONS
Connection
Internal bus
: Via the Installation Base (model: R6S-BS)
Input
: Tension clamp
(Applicable wire size: 0.2 to 2.5 mm
2
, stripped length 8 mm)
Internal power
: Via the Installation Base (model: R6S-BS)
Housing material
: Flame-resistant resin (black)
Isolation
: Input to internal bus or internal power
Module address
: Selectable with DIP and rotary switches on the side
Power indicator
: Green LED; Refer to the istruction manual for details.
Status indicator
: Bi-color (red/green) LED;
Refer to the instruction manual for details.
Discrete input status indicators
: Red LED;
Refer to the instruction manual for details.
INPUT
Common
: Positive or negative common (NPN/PNP) per 2 points
Number of I/O
: Input, 4 points
Rated input voltage
: 24 V DC ±10 %; ripple 5 %p-p max.
ON voltage / current
: ≥ 15 V DC (input – COM) / ≥ 3.5 mA
OFF voltage / current
: ≤ 5 V DC (input – COM) / ≤ 1 mA
Input current
: ≤ 5.5 mA per point at 24 V DC
Input resistance
: Approx. 4.4 kΩ
ON delay
: ≤ 2.0 msec.
OFF delay
: ≤ 2.0 msec.
INSTALLATION
Current consumption:
10 mA
Operating temperature
: -10 to +55°C (14 to 131°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Atmosphere
: No corrosive gas or heavy dust
Mounting
: Installation Base (model: R6S-BS)
Weight
: 60 g (2.1 oz)
PERFORMANCE
Data allocation
: 1
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 1500 V AC @ 1 minute
(input to internal bus or internal power to ground)
STANDARDS & APPROVALS
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
EXTERNAL VIEW
Refer to the instruction manual for setting procedures.
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM