ES-7781-BC Rev.4

R6S-DA4

Remote I/O R6 Series

DISCRETE INPUT MODULE, 4 points

(tension clamp)
Functions & Features
• Discrete input module (positive or negative common) with 4 channels

MODEL: R6S–DA4[1]

ORDERING INFORMATION

• Code number: R6S-DA4[1]
Specify a code from below for [1].
  (e.g. R6S-DA4/Q)
• Specify the specification for option code /Q
  (e.g. /C01)

[1] OPTIONS

blank: none
/Q: With options (specify the specification)

SPECIFICATIONS OF OPTION: Q

COATING (For the detail, refer to our web site.)
/C01: Silicone coating
/C02: Polyurethane coating

RELATED PRODUCTS

• PC Configurator cable (model: MCN-CON or COP-US)
• PC configurator software (model: R6CON)
Downloadable at our web site.

GENERAL SPECIFICATIONS

Connection
 Internal bus
: Via the Installation Base (model: R6S-BS)
 Input: Tension clamp
(Applicable wire size: 0.2 to 2.5 mm2, stripped length 8 mm) 
 Internal power: Via the Installation Base (model: R6S-BS)
Housing material: Flame-resistant resin (black)
Isolation: Input to internal bus or internal power
Module address: Selectable with DIP and rotary switches on the side
Power indicator: Green LED; Refer to the istruction manual for details.
Status indicator: Bi-color (red/green) LED;
Refer to the instruction manual for details.
Discrete input status indicators: Red LED;
Refer to the instruction manual for details.

INPUT

Common: Positive or negative common (NPN/PNP) per 2 points
Number of I/O: Input, 4 points
Rated input voltage: 24 V DC ±10 %; ripple 5 %p-p max.
ON voltage / current: ≥ 15 V DC (input – COM) / ≥ 3.5 mA
OFF voltage / current: ≤ 5 V DC (input – COM) / ≤ 1 mA
Input current: ≤ 5.5 mA per point at 24 V DC
Input resistance: Approx. 4.4 kΩ
ON delay: ≤ 2.0 msec.
OFF delay: ≤ 2.0 msec.

INSTALLATION

Current consumption: 10 mA
Operating temperature: -10 to +55°C (14 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Installation Base (model: R6S-BS)
Weight: 60 g (2.1 oz)

PERFORMANCE

Data allocation: 1
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute
(input to internal bus or internal power to ground)

STANDARDS & APPROVALS

EU conformity:
EMC Directive 
  EMI EN 61000-6-4
  EMS EN 61000-6-2
RoHS Directive

EXTERNAL VIEW

Refer to the instruction manual for setting procedures.

EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM