ES-7781-BD Rev.3
R6S-DC4A
Remote I/O R6 Series
NPN TRANSISTOR OUTPUT MODULE, 4 points
(tension clamp)
Functions & Features
• 4-channel discrete output, compact size remote I/O module
MODEL: R6S–DC4A[1]
ORDERING INFORMATION
• Code number: R6S-DC4A[1]
Specify a code from below for [1].
(e.g. R6S-DC4A/Q)
• Specify the specification for option code /Q
(e.g. /C01)
[1] OPTIONS
blank
: none
/Q
: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
RELATED PRODUCTS
• PC Configurator cable (model: MCN-CON or COP-US)
• PC configurator software (model: R6CON)
Downloadable at our web site.
GENERAL SPECIFICATIONS
Connection
Internal bus
: Via the Installation Base (model: R6S-BS)
Output
: Tension clamp
(Applicable wire size: 0.2 to 2.5 mm
2
, stripped length 8 mm)
Internal power
: Via the Installation Base (model: R6S-BS)
Housing material
: Flame-resistant resin (black)
Isolation
: Output to internal bus or internal power
Module address
: Selectable with DIP and rotary switches on the side
Output at the loss of communication
: Selectable with the side DIP SW
Configuration mode
: With DIP switches on the side panel
Power indicator
: Green LED; Refer to the istruction manual for details.
Status indicator
: Bi-color (red/green) LED;
Refer to the instruction manual for details.
Discrete output status indicators
: Red LED;
Refer to the instruction manual for details.
OUTPUT
Common
: Negative common (NPN) per 4 points
Number of I/O
: Output, 4 points
Maximum outputs applicable at once
: No limit (at 24 V DC)
Rated load voltage
: 24 V DC ±10 %
Rated output current
: 0.25 A per point, 2.0 A per common
Residual voltage
: ≤ 1.2 V
Leakage current
: ≤ 0.1 mA
ON delay
: ≤ 0.5 msec.
OFF delay
: ≤ 1.5 msec.
(When driving an inductive load, connect a diode in parallel with the load.)
INSTALLATION
Current consumption:
20 mA
Operating temperature
: -10 to +55°C (14 to 131°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Atmosphere
: No corrosive gas or heavy dust
Mounting
: Installation Base (model: R6S-BS)
Weight
: 60 g (2.1 oz)
PERFORMANCE
Data allocation
: 1
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 1500 V AC @ 1 minute
(output to internal bus or internal power to ground)
STANDARDS & APPROVALS
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
EXTERNAL VIEW
Refer to the instruction manual for setting procedures.
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM