ES-7781-BP Rev.3
R6S-DS1
Remote I/O R6 Series
4 – 20 mA INPUT MODULE
(tension clamp)
Functions & Features
• Compact size remote I/O module for 2-wire transmitter
MODEL: R6S–DS1[1]
ORDERING INFORMATION
• Code number: R6S-DS1[1]
Specify a code from below for [1].
(e.g. R6S-DS1/Q)
• Specify the specification for option code /Q
(e.g. /C01)
[1] OPTIONS
blank
: none
/Q
: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
RELATED PRODUCTS
• PC Configurator cable (model: MCN-CON or COP-US)
• PC configurator software (model: R6CON)
Downloadable at our web site.
GENERAL SPECIFICATIONS
Connection
Internal bus
: Via the Installation Base (model: R6S-BS)
Input
: Tension clamp
(Applicable wire size: 0.2 to 2.5 mm
2
, stripped length 8 mm)
Internal power
: Via the Installation Base (model: R6S-BS)
Housing material
: Flame-resistant resin (black)
Isolation
: Input to internal bus or internal power
Zero adjustments
: PC programming
Span adjustments
: PC programming
Module address
: Selectable with DIP and rotary switches on the side
Configuration mode
: With DIP switches on the side panel
Power indicator
: Green LED; Refer to the istruction manual for details.
Status indicator
: Bi-color (red/green) LED;
Refer to the instruction manual for details.
SUPPLY OUTPUT
(across the terminals 3 – 4)
Output voltage
: 24 – 28 V DC with no load
19 V DC min. at 20 mA
Current rating
: ≤ 22 mA DC
Permissible leadwire resistance
:
R L ≤ ((19 - min. XMTR Operational Voltage) V ÷ 0.02 A) Ω
•
Shortcircuit Protection
Current limited
: 45 mA max.
Protected time duration
: No limit
INPUT SPECIFICATIONS
■
DC Current
: 4 – 20 mA DC
Input resistance
: 250 Ω resistor incorporated
INSTALLATION
Current consumption:
55 mA
Operating temperature
: -10 to +55°C (14 to 131°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Atmosphere
: No corrosive gas or heavy dust
Mounting
: Installation Base (model: R6S-BS)
Weight
: 60 g (2.1 oz)
PERFORMANCE
Conversion rate (PC programmable. Factory set to 80 msec.)/conversion accuracy
:
10 msec./±0.8 %
20 msec./±0.4 %
40 msec./±0.2 %
80 msec./±0.1 %
Data range
: 0 – 10000
Data allocation
: 1
Temp. coefficient
: ±0.01 %/°C (±0.006 %/°F)
Response time
: Conversion rate × 2 + 50 msec. or less
Line voltage effect
: ±0.1 % over voltage range
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 1500 V AC @ 1 minute
(input to internal bus or internal power to ground)
STANDARDS & APPROVALS
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
EXTERNAL VIEW
Refer to the instruction manual for setting procedures.
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM