ES-7781-AY Rev.3

R6S-SS2

Remote I/O R6 Series

DC CURRENT INPUT MODULE

(2 points, tension clamp)
Functions & Features
• 2 channels for DC current input, compact size remote I/O module
• Isolation between channels
• Input range adjustment with DIP switch or PC configurator

MODEL: R6S–SS2[1]

ORDERING INFORMATION

• Code number: R6S-SS2[1]
Specify a code from below for [1].
  (e.g. R6S-SS2/Q)
• Specify the specification for option code /Q
  (e.g. /C01)

[1] OPTIONS

blank: none
/Q: With options (specify the specification)

SPECIFICATIONS OF OPTION: Q

COATING (For the detail, refer to our web site.)
/C01: Silicone coating
/C02: Polyurethane coating

RELATED PRODUCTS

• PC Configurator cable (model: MCN-CON or COP-US)
• PC configurator software (model: R6CON)
Downloadable at our web site.

GENERAL SPECIFICATIONS

Connection
 Internal bus
: Via the Installation Base (model: R6S-BS)
 Input: Tension clamp
(Applicable wire size: 0.2 to 2.5 mm2, stripped length 8 mm) 
 Internal power: Via the Installation Base (model: R6S-BS)
Housing material: Flame-resistant resin (black)
Isolation: Input 1 to input 2 to internal bus or internal power
Zero adjustments: PC programming
Span adjustments: PC programming
Input range: Selectable with the side DIP SW or PC programming
Module address: Selectable with DIP and rotary switches on the side
Configuration mode: With DIP switches on the side panel
Power indicator: Green LED; Refer to the istruction manual for details.
Status indicator: Bi-color (red/green) LED;
Refer to the instruction manual for details.

INPUT SPECIFICATIONS

Narrow Span: 1500 Ω input resistor incorporated
Input range: -1 – +1 mA, 0 – 1 mA DC
Wide Span: 24.9 Ω input resistor incorporated
Input range: -40 – +40 mA, -20 – +20 mA,
0 – 40 mA, 0 – 20 mA, 4 – 20 mA DC

INSTALLATION

Current consumption: 20 mA
Operating temperature: -10 to +55°C (14 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Installation Base (model: R6S-BS)
Weight: 60 g (2.1 oz)

PERFORMANCE

Conversion rate (PC programmable. Factory set to 80 msec.)/conversion accuracy:
10 msec./±0.8 %
20 msec./±0.4 %
40 msec./±0.2 %
80 msec./±0.1 %
Data range: 0 – 10000 of the input range
Data allocation: 2
Temp. coefficient: ±0.01 %/°C (±0.006 %/°F)
Response time: Conversion rate × 2 + 50 msec. or less
Line voltage effect: ±0.1 % over voltage range
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute (input 1 to input 2 to internal bus or internal power to ground)

STANDARDS & APPROVALS

EU conformity:
EMC Directive 
  EMI EN 61000-6-4
  EMS EN 61000-6-2
RoHS Directive

EXTERNAL VIEW

Refer to the instruction manual for setting procedures.

EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM