ES-7781-BI Rev.3
R6S-TS2
Remote I/O R6 Series
THERMOCOUPLE INPUT MODULE
(2 points, tension clamp)
Functions & Features
• Accepts direct input from an thermocouple and provides an isolated, linearized DC signal compact size remote I/O module
MODEL: R6S–TS2[1]
ORDERING INFORMATION
• Code number: R6S-TS2[1]
Specify a code from below for [1].
(e.g. R6S-TS2/Q)
• Specify the specification for option code /Q
(e.g. /C01)
[1] OPTIONS
blank
: none
/Q
: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
RELATED PRODUCTS
• PC Configurator cable (model: MCN-CON or COP-US)
• PC configurator software (model: R6CON)
Downloadable at our web site.
GENERAL SPECIFICATIONS
Connection
Internal bus
: Via the Installation Base (model: R6S-BS)
Input
: Tension clamp
(Applicable wire size: 0.2 to 2.5 mm
2
, stripped length 8 mm)
Internal power
: Via the Installation Base (model: R6S-BS)
Housing material
: Flame-resistant resin (black)
Isolation
: Input 1 to input 2 to internal bus or internal power
Zero adjustments
: PC programming
Span adjustments
: PC programming
Input type
: Selectable with the side DIP SW or PC programming
Burnout detection:
Upscale or downscale selectable with the side DIP SW or PC programming
Linearization
: Standard
Cold Junction Compensation
: CJC sensor incorporated
Module address
: Selectable with DIP and rotary switches on the side
Configuration mode
: With DIP switches on the side panel
Power indicator
: Green LED; Refer to the istruction manual for details.
Status indicator
: Bi-color (red/green) LED;
Refer to the instruction manual for details.
INPUT SPECIFICATIONS
Thermocouple
: K, E, J, T, B, R, S, C, N, U, L, P, PR
Input resistance
: ≥ 30 kΩ
Burnout sensing
: ≤ 0.1 μA
INSTALLATION
Current consumption:
20 mA
Operating temperature
: -10 to +55°C (14 to 131°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Atmosphere
: No corrosive gas or heavy dust
Mounting
: Installation Base (model: R6S-BS)
Weight
: 60 g (2.1 oz)
PERFORMANCE
Conversion accuracy
: ±1°C (±1.8°F) except ±2°C (±3.6°F) for B, R, S, C, PR
Conversion rate
: 250 msec. / 500 msec. (PC programmable. Factory set to 500 msec.)
Converted data range
:
• Engineering unit value (°C, K) × 10 (integer)
• Engineering unit value (°F)
Data allocation
: 2
Cold junction compensation error
:
±3°C at 25 ±10°C
±5.4°F at 77 ±18°F
Temp. coefficient
: ±0.01 %/°C (±0.006 %/°F) of max. span
Response time
: Conversion rate × 2 + 50 msec. or less
Line voltage effect
: ±0.1 % over voltage range
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 1500 V AC @ 1 minute (input 1 to input 2 to internal bus or internal power to ground)
STANDARDS & APPROVALS
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
EXTERNAL VIEW
Refer to the instruction manual for setting procedures.
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM