ES-7781-BS Rev.2

R6S-TS2A

Remote I/O R6 Series

THERMOCOUPLE INPUT MODULE

(high-accuracy, 2 points, tension clamp)
Functions & Features
• Accepts direct input from an thermocouple and provides an isolated, linearized DC signal compact size remote I/O module

MODEL: R6S–TS2A[1]

ORDERING INFORMATION

• Code number: R6S-TS2A[1]
Specify a code from below for [1].
  (e.g. R6S-TS2A/Q)
• Specify the specification for option code /Q
  (e.g. /C01)

[1] OPTIONS

blank: none
/Q: With options (specify the specification)

SPECIFICATIONS OF OPTION: Q

COATING (For the detail, refer to our web site.)
/C01: Silicone coating
/C02: Polyurethane coating

RELATED PRODUCTS

• PC Configurator cable (model: MCN-CON or COP-US)
• PC configurator software (model: R6CON)
Downloadable at our web site.

GENERAL SPECIFICATIONS

Connection
 Internal bus
: Via the Installation Base (model: R6S-BS)
 Input: Tension clamp
(Applicable wire size: 0.2 to 2.5 mm2, stripped length 8 mm) 
 Internal power: Via the Installation Base (model: R6S-BS)
Housing material: Flame-resistant resin (black)
Isolation: Input 1 to input 2 to internal bus or internal power
Zero adjustments: PC programming
Span adjustments: PC programming
Input type: Selectable with the side DIP SW or PC programming
Burnout detection: Upscale or downscale selectable with the side DIP SW or PC programming
Linearization: Standard
Cold junction compensation: CJC sensor attached to the
input terminals
Module address: Selectable with DIP and rotary switches on the side
Configuration mode: With DIP switches on the side panel
Power indicator: Green LED; Refer to the istruction manual for details.
Status indicator: Bi-color (red/green) LED;
Refer to the instruction manual for details.

INPUT SPECIFICATIONS

Thermocouple: K, E, J, T, B, R, S, C, N, U, L, P, PR
Input resistance: ≥ 30 kΩ
Burnout sensing: ≤ 0.1 μA

INSTALLATION

Current consumption: 20 mA
Operating temperature: -10 to +55°C (14 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Installation Base (model: R6S-BS)
Weight: 70 g (2.5 oz)

PERFORMANCE

Conversion accuracy: ±0.5°C (±0.9°F) except ±1°C (±1.8°F) for B, R, S, C, PR
Conversion rate: 250 msec. / 500 msec. (PC programmable. Factory set to 500 msec.)
Converted data range:
• Engineering unit value (°C, K) × 10 (integer)
• Engineering unit value (°F)
Data allocation: 2
Cold junction compensation error:
 ±1°C max. at 25 ±10°C
 ±1.8°F max. at 77 ±18°F
Temp. coefficient: ±0.01 %/°C (±0.006 %/°F) of max. span
Response time: Conversion rate × 2 + 50 msec. or less
Line voltage effect: ±0.1 % over voltage range
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute (input 1 to input 2 to internal bus or internal power to ground)

EXTERNAL VIEW

Refer to the instruction manual for setting procedures.

EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM