ES-7781-BB Rev.3
R6S-YV2
Remote I/O R6 Series
DC VOLTAGE OUTPUT MODULE
(2 points, tension clamp)
Functions & Features
• 2 channels for DC voltage output, compact size remote I/O module
• Output range adjustment with DIP switch or PC configurator
MODEL: R6S–YV2[1]
ORDERING INFORMATION
• Code number: R6S-YV2[1]
Specify a code from below for [1].
(e.g. R6S-YV2/Q)
• Specify the specification for option code /Q
(e.g. /C01)
[1] OPTIONS
blank
: none
/Q
: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING
/C01
: Silicone coating
/C02
: Polyurethane coating
RELATED PRODUCTS
• PC Configurator cable (model: MCN-CON or COP-US)
• PC configurator software (model: R6CON)
Downloadable at our web site.
GENERAL SPECIFICATIONS
Connection
Internal bus
: Via the Installation Base (model: R6S-BS)
Output
: Tension clamp
(Applicable wire size: 0.2 to 2.5 mm
2
, stripped length 8 mm)
Internal power
: Via the Installation Base (model: R6S-BS)
Housing material
: Flame-resistant resin (black)
Isolation
: Output 1 to output 2 to internal bus or internal power
Zero adjustments
: PC programming
Span adjustments
: PC programming
Output range
: Selectable with the side DIP SW or PC programming
Module address
: Selectable with DIP and rotary switches on the side
Output at the loss of communication
: Selectable with the side DIP SW
Configuration mode
: With DIP switches on the side panel
Power indicator
: Green LED; Refer to the istruction manual for details.
Status indicator
: Bi-color (red/green) LED;
Refer to the instruction manual for details.
OUTPUT SPECIFICATIONS
Overrange output
: -11.5 – +11.5 V DC or -15 to +115 %
■
Narrow Span
: -1 – +1 V, 0 – 1 V, -0.5 – +0.5 V DC
Load resistance
: 10 kΩ min.
■
Wide Span
: -10 – +10 V, -5 – +5 V,
0 – 10 V, 0 – 5 V, 1 – 5 V DC
Load resistance
: 10 kΩ min.
INSTALLATION
Current consumption:
25 mA
Operating temperature
: -10 to +55°C (14 to 131°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Atmosphere
: No corrosive gas or heavy dust
Mounting
: Installation Base (model: R6S-BS)
Weight
: 60 g (2.1 oz)
PERFORMANCE
Conversion accuracy
: ±0.1 %
Data range
: 0 – 10000 of the output range
Data allocation
: 2
Temp. coefficient
: ±0.01 %/°C (±0.006 %/°F)
Response time
: ≤ 0.25 sec. (0 – 90 %)
Line voltage effect
: ±0.1 % over voltage range
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 1500 V AC @ 1 minute (output 1 to output 2 to internal bus or internal power to ground)
STANDARDS & APPROVALS
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
FUNCTIONS
■
OUTPUT HOLD
The output function in case of a loss of communication is selectable with the side DIP SW: Reset the output (to -15 % or -11.5 V), Hold the output (last normally received data) or Fix the output at a specific value (PC programming).
The output is held at -11.5 V or -15 % of the output range until normal data is received at the startup.
EXTERNAL VIEW
Refer to the instruction manual for setting procedures.
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM