ES-7781-BB Rev.3

R6S-YV2

Remote I/O R6 Series

DC VOLTAGE OUTPUT MODULE

(2 points, tension clamp)
Functions & Features
• 2 channels for DC voltage output, compact size remote I/O module
• Output range adjustment with DIP switch or PC configurator

MODEL: R6S–YV2[1]

ORDERING INFORMATION

• Code number: R6S-YV2[1]
Specify a code from below for [1].
  (e.g. R6S-YV2/Q)
• Specify the specification for option code /Q
  (e.g. /C01)

[1] OPTIONS

blank: none
/Q: With options (specify the specification)

SPECIFICATIONS OF OPTION: Q

COATING
/C01: Silicone coating
/C02: Polyurethane coating

RELATED PRODUCTS

• PC Configurator cable (model: MCN-CON or COP-US)
• PC configurator software (model: R6CON)
Downloadable at our web site.

GENERAL SPECIFICATIONS

Connection
 Internal bus
: Via the Installation Base (model: R6S-BS)
 Output: Tension clamp
(Applicable wire size: 0.2 to 2.5 mm2, stripped length 8 mm) 
 Internal power: Via the Installation Base (model: R6S-BS)
Housing material: Flame-resistant resin (black)
Isolation: Output 1 to output 2 to internal bus or internal power
Zero adjustments: PC programming
Span adjustments: PC programming
Output range: Selectable with the side DIP SW or PC programming
Module address: Selectable with DIP and rotary switches on the side
Output at the loss of communication: Selectable with the side DIP SW
Configuration mode: With DIP switches on the side panel
Power indicator: Green LED; Refer to the istruction manual for details.
Status indicator: Bi-color (red/green) LED;
Refer to the instruction manual for details.

OUTPUT SPECIFICATIONS

Overrange output: -11.5 – +11.5 V DC or -15 to +115 %
Narrow Span: -1 – +1 V, 0 – 1 V, -0.5 – +0.5 V DC
Load resistance: 10 kΩ min.
Wide Span: -10 – +10 V, -5 – +5 V,
0 – 10 V, 0 – 5 V, 1 – 5 V DC
Load resistance: 10 kΩ min.

INSTALLATION

Current consumption: 25 mA
Operating temperature: -10 to +55°C (14 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Installation Base (model: R6S-BS)
Weight: 60 g (2.1 oz)

PERFORMANCE

Conversion accuracy: ±0.1 %
Data range: 0 – 10000 of the output range
Data allocation: 2
Temp. coefficient: ±0.01 %/°C (±0.006 %/°F)
Response time: ≤ 0.25 sec. (0 – 90 %)
Line voltage effect: ±0.1 % over voltage range
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute (output 1 to output 2 to internal bus or internal power to ground)

STANDARDS & APPROVALS

EU conformity:
EMC Directive 
  EMI EN 61000-6-4
  EMS EN 61000-6-2
RoHS Directive

FUNCTIONS

OUTPUT HOLD
The output function in case of a loss of communication is selectable with the side DIP SW: Reset the output (to -15 % or -11.5 V), Hold the output (last normally received data) or Fix the output at a specific value (PC programming).
The output is held at -11.5 V or -15 % of the output range until normal data is received at the startup.

EXTERNAL VIEW

Refer to the instruction manual for setting procedures.

EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM