ES-8903 Rev.0

R30NEIP1

Remote I/O R30 Series

NETWORK MODULE

(EtherNet/IP)
Functions & Features
• Interchanges analog or discrete I/O signals with the filedbus (EtherNet/IP)
• Combined with R3 Series I/O modules

MODEL: R30NEIP1[1]

ORDERING INFORMATION

• Code number: R30NEIP1[1]
Specify a code from below for [1].
  (e.g. R30NEIP1/Q)
• Specify the specification for option code /Q
  (e.g. /C01)

[1] OPTIONS

blank: none
/Q: With options (specify the specification)

SPECIFICATIONS OF OPTION: Q

COATING (For the detail, refer to our web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating

CAUTION

• The internal bus communication period for R3 series I/O modules installed on the R30EBS is as follows.
Internal bus communication period = 6 msec. × number of I/O module + 10 msec. (Data update period of main CPU)
    Example: Four R3 I/O modules
        6 msec. × 4 + 10 msec. = 34 msec.
Even when the R30EBS is mounted to the R30BS, the internal bus communication period of R30 series is kept to approx. 1 msec.

RELATED PRODUCTS

• PC configurator software (model: R30CFG)
• PC configurator software (model: R3CON)
• EDS file
The EDS file and configurator software are downloadable at our web site.
For connecting to PC, use commercially available Mini-B type USB cable. (provided by user)
• R3 series I/O modules (except R3-TC2)

GENERAL SPECIFICATIONS

Connection
  EtherNet/IP
: RJ-45 modular jack
  Internal bus: Via the Installation Base (model: R30BS)
  Internal power: Via the Installation Base (model: R30BS)
Isolation: EtherNet/IP to internal bus or internal power
Internal bus communication cycle: Approx. 1 msec.
Status indicator LED: PWR

EtherNet/IP COMMUNICATION

Conformance test version: CT21
Communication standard: IEEE 802.3u
Transmission: 10BASE-T, 100BASE-TX
Baud rate: 10/100 Mbps (Auto Negotiation function)
Max. number of socket connections: 3
Connection type: Exclusive owner, Listen only, Input only
Protocol: EtherNet/IP
Transmission media: 10BASE-T (STP, Category 5)
100BASE-TX (STP, Category 5e)
Max. length of fieldbus segment: 100 meters
IP address: 192.168.0.250 (factory setting); Selectable with PC Configurator Software (model: R30CFG)
Default gateway: 192.168.0.1 (factory setting); Selectable with PC Configurator Software (model: R30CFG)
DLR supported
Port No.: 2222, 44818
I/O data area size: Input and output data area size set with PC Configurator Software (model: R30CFG) 
Required data words
 Input: 38, 70, 134, 252 words
 Output: 38, 70, 134, 252 words (6 words are used only for status)
Ethernet indicator LED: LINK1, LINK2
MS (Module Status) indicator: Bi-color (green/red) LED indicates device status.
NS (Network Status) indicator: Bi-color (green/red) LED indicates status of the communication link.

INSTALLATION

Current consumption: 110 mA
Operating temperature: -10 to +55°C (14 to 131°F)
Storage temperature: -20 to +65°C (-4 to +149°F)
Operating humidity: 10 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Installation Base (model: R30BS)
Weight: 110 g (0.24 lb)

PERFORMANCE

Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute
(EtherNet/IP to internal bus or internal power)
1500 V AC @ 1 minute (power input to FE; isolated on the power supply module)

STANDARDS & APPROVALS

EU conformity:
EMC Directive 
  EMI EN 61000-6-4
  EMS EN 61000-6-2
RoHS Directive

EXTERNAL VIEW

EXTERNAL DIMENSIONS unit: mm [inch]

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM