ES-8903 Rev.0
R30NEIP1
Remote I/O R30 Series
NETWORK MODULE
(EtherNet/IP)
Functions & Features
• Interchanges analog or discrete I/O signals with the filedbus (EtherNet/IP)
• Combined with R3 Series I/O modules
MODEL: R30NEIP1[1]
ORDERING INFORMATION
• Code number: R30NEIP1[1]
Specify a code from below for [1].
(e.g. R30NEIP1/Q)
• Specify the specification for option code /Q
(e.g. /C01)
[1] OPTIONS
blank
: none
/Q
: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
CAUTION
• The internal bus communication period for R3 series I/O modules installed on the R30EBS is as follows.
Internal bus communication period = 6 msec. × number of I/O module + 10 msec. (Data update period of main CPU)
Example: Four R3 I/O modules
6 msec. × 4 + 10 msec. = 34 msec.
Even when the R30EBS is mounted to the R30BS, the internal bus communication period of R30 series is kept to approx. 1 msec.
RELATED PRODUCTS
• PC configurator software (model: R30CFG)
• PC configurator software (model: R3CON)
• EDS file
The EDS file and configurator software are downloadable at our web site.
For connecting to PC, use commercially available Mini-B type USB cable. (provided by user)
• R3 series I/O modules (except R3-TC2)
GENERAL SPECIFICATIONS
Connection
EtherNet/IP
: RJ-45 modular jack
Internal bus
: Via the Installation Base (model: R30BS)
I
nternal power
: Via the Installation Base (model: R30BS)
Isolation
: EtherNet/IP to internal bus or internal power
Internal bus
communication cycle
:
Approx. 1 msec.
Status indicator LED
: PWR
EtherNet/IP COMMUNICATION
Conformance test version:
CT21
Communication standard
: IEEE 802.3u
Transmission
: 10BASE-T, 100BASE-TX
Baud rate
: 10/100 Mbps (Auto Negotiation function)
Max. number of socket connections
: 3
Connection type
: Exclusive owner, Listen only, Input only
Protocol
: EtherNet/IP
Transmission media
: 10BASE-T (STP, Category 5)
100BASE-TX (STP, Category 5e)
Max. length of fieldbus segment
: 100 meters
IP address
: 192.168.0.250 (factory setting); Selectable with PC Configurator Software (model: R30CFG)
Default gateway:
192.168.0.1 (factory setting); Selectable with PC Configurator Software (model: R30CFG)
DLR supported
Port No
.: 2222, 44818
I/O data area size
: Input and output data area size set with PC Configurator Software (model: R30CFG)
Required data words
:
Input
: 38, 70, 134, 252 words
Output
: 38, 70, 134, 252 words (6 words are used only for status)
Ethernet indicator LED
: LINK1, LINK2
MS (Module Status) indicator
: Bi-color (green/red) LED indicates device status.
NS (Network Status) indicator
: Bi-color (green/red) LED indicates status of the communication link.
INSTALLATION
Current consumption:
110 mA
Operating temperature
: -10 to +55°C (14 to 131°F)
Storage temperature
: -20 to +65°C (-4 to +149°F)
Operating humidity
: 10 to 90 %RH (non-condensing)
Atmosphere
: No corrosive gas or heavy dust
Mounting
: Installation Base (model: R30BS)
Weight
: 110 g (0.24 lb)
PERFORMANCE
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 1500 V AC @ 1 minute
(EtherNet/IP to internal bus or internal power)
1500 V AC @ 1 minute (power input to FE; isolated on the power supply module)
STANDARDS & APPROVALS
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
EXTERNAL VIEW
EXTERNAL DIMENSIONS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM