ES-6105 Rev.14
R5-NC1
Remote I/O R5 Series
CC-Link INTERFACE MODULE
(CC-Link Ver.1.10; for 16-point analog signals)
MODEL: R5-NC1[1]
ORDERING INFORMATION
• Code number: R5-NC1[1]
Specify a code from below for [1].
(e.g. R5-NC1/Q)
• Specify the specification for option code /Q
(e.g. /C01)
[1] OPTIONS
blank
: none
/Q
: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
RELATED PRODUCTS
• PC Configurator cable (model: MCN-CON or COP-US)
• PC configurator software (model: R5CON)
Downloadable at our web site.
PACKAGE INCLUDES...
• Terminating resistor (110 Ω, 0.5 W)
GENERAL SPECIFICATIONS
Connection
CC-Link
: Euro type connector terminal
(applicable wire size: 0.2 – 2.5 mm
2
, stripped length 7 mm)
Internal bus
: Via the Installation Base (model: R5-BS)
Internal power
: Via the Installation Base (model: R5-BS)
Isolation
: CC-Link to internal bus or internal power
RUN indicator:
Bi-color (green/red) LED; Green ON in normal communication; Red ON when receiving data (Function selected with DIP SW)
ERR indicator:
Bi-color (green/red) LED;
Green ON or blinking at communication error; Red ON at transmitting data (Function selected with DIP SW)
Data allocation
: Mode 1 or 2 set with the side DIP switch
Configurator connection
: 2.5 dia. miniature jack
CC-Link COMMUNICATION
CC-Link
: Conforms to Version 1.10
Station address
: Rotary switch; 1 – 64
Station type
: Remote device station
Baud rate setting
: Rotary switch
156kbps, 625kbps, 2.5Mbps, 5Mbps, 10Mbps
Transmission cable
: Approved for CC-Link
INSTALLATION
Operating temperature
: -10 to +55°C (14 to 131°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Atmosphere
: No corrosive gas or heavy dust
Mounting
: Installation Base (model: R5-BS)
Weight
: 100 g (0.22 lb)
PERFORMANCE
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 2000 V AC @ 1 minute (CC-Link to internal bus or internal power)
STANDARDS & APPROVALS
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
EXTERNAL VIEW
COMMUNICATION CABLE CONNECTIONS
TRANSMISSION DATA DESCRIPTIONS
The DIP SW located at the side of the module switches the unit's data allocation mode.
The Data Allocation Mode 1 is used when all analog I/O modules are single-channel types. In this mode, one (1) word is assigned for one I/O module. The second channel on the dual-channel modules cannot be used. Max. 16 I/O modules can be used per station.
The Data Allocation Mode 2 is used when one or more analog I/O modules are dual-channel types. In this mode, two (2) words are assigned for one I/O module regardless of whether the second word area is required or not. For example, discrete I/O modules require only one (1) word, but two (2) words are automatically assigned to these modules.
■
I/O CAPACITY
In Data Allocation Mode 1, a maximum of 16 I/O modules can be mounted per node. If two-channel type analog modules are mixed, the second channel I/O cannot be used.
In Data Allocation Mode 2, a maximum of 8 I/O modules can be mounted per node.
I/O DATA DESCRIPTIONS
The data allocations for typical I/O modules are shown below.
Refer to the manual for each module for detailed data allocations.
■ANALOG 16 BITS DATA
■ 16-POINT DISCRETE DATA
■ 4-POINT DISCRETE DATA
EXTERNAL DIMENSIONS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
Note: In order to improve EMC performance, bond the FG terminal to ground.
Caution: FG terminal is NOT a protective conductor terminal.