ES-6137 Rev.13

R5-NC2

Remote I/O R5 Series

CC-Link INTERFACE MODULE

(CC-Link Ver.1.10; for 32-point analog signals)

MODEL: R5-NC2[1]

ORDERING INFORMATION

• Code number: R5-NC2[1]
Specify a code from below for [1].
  (e.g. R5-NC2/Q)
• Specify the specification for option code /Q
  (e.g. /C01)

[1] OPTIONS

blank: none
/Q: With options (specify the specification)

SPECIFICATIONS OF OPTION: Q

COATING (For the detail, refer to our web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating

RELATED PRODUCTS

• PC Configurator cable (model: MCN-CON or COP-US)
• PC configurator software (model: R5CON)
Downloadable at our web site.

PACKAGE INCLUDES...

• Terminating resistor (110 Ω, 0.5 W)

GENERAL SPECIFICATIONS

Connection
  CC-Link: Euro type connector terminal
  (applicable wire size: 0.2 – 2.5 mm2, stripped length 7 mm)
  Internal bus: Via the Installation Base (model: R5-BS)
  Internal power: Via the Installation Base  (model: R5-BS)
Isolation: CC-Link to internal bus or internal power
RUN indicator: Bi-color (green/red) LED; Green ON in normal communication; Red ON when receiving data (Function selected with DIP SW)
ERR indicator: Bi-color (green/red) LED;
Green ON or blinking at communication error; Red ON at transmitting data (Function selected with DIP SW)
Data allocation: Fixed to Mode 2
Configurator connection: 2.5 dia. miniature jack

CC-Link COMMUNICATION

Transmission cable: Approved for CC-Link
CC-Link: Conforms to Version 1.10
Station address: Rotary switch; 1 – 64
Station type: Remote device station
Number of occupied stations: 8
(This module incorporates two (2) ASICs for four (4) stations (32 I/O, 16 words) to handle 32-word data. Two (2) remote device stations for four stations each must be assigned for this module to the host PLC.)
Baud rate setting: Rotary switch
156kbps, 625kbps, 2.5Mbps, 5Mbps, 10Mbps

INSTALLATION

Operating temperature: -10 to +55°C (14 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Installation Base (model: R5-BS)
Weight: 100 g (0.22 lb)

PERFORMANCE

Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 2000 V AC @ 1 minute (CC-Link to internal bus or internal power)

STANDARDS & APPROVALS

EU conformity:
EMC Directive 
  EMI EN 61000-6-4
  EMS EN 61000-6-2
RoHS Directive

EXTERNAL VIEW

COMMUNICATION CABLE CONNECTIONS

TRANSMISSION DATA DESCRIPTIONS

The DIP SW located at the side of the module must be turned OFF except at SW3.
Data Allogcation Mode 2 is used for the R5-NC2. In this mode, two (2) words are assigned for one I/O module regardless of whether the second word area is required or not. For example, discrete I/O modules require only one (1) word, but two (2) words are automatically assigned to these modules.
I/O CAPACITY
A maximum of 16 I/O modules can be mounted per station.

I/O DATA DESCRIPTIONS

The data allocations for typical I/O modules are shown below.
Refer to the manual for each module for detailed data allocations.
■ANALOG 16 BITS DATA
■ 16-POINT DISCRETE DATA
■ 4-POINT DISCRETE DATA

EXTERNAL DIMENSIONS unit: mm [inch]

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM

Note: In order to improve EMC performance, bond the FG terminal to ground.
Caution: FG terminal is NOT a protective conductor terminal.