ES-8269 Rev.0
R3-NE2
Remote I/O R3 Series
ETHERNET INTERFACE MODULE
(Modbus/TCP, for master gateway module)
MODEL: R3-NE2-[1][2]
ORDERING INFORMATION
• Code number: R3-NE2-[1][2]
Specify a code from below for each of [1] and [2].
(e.g. R3-NE2-R/CE/Q)
• Specify the specification for option code /Q
(e.g. /C01/S01/SET)
[1] POWER INPUT
N
: No power supply
(Use with Ver.2.00 or higher versions of Power Supply Module
(model: R3-PSx) to conform with CE marking.)
AC Power
M2
: 100 – 240 V AC, 50 – 60 Hz
*
(Operational voltage range 85 – 264 V, 47 – 66 Hz)
DC Power
R:
24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.) *
* Not selectable for use with independent power modules or network modules with the internal power input options.
[2] OPTIONS (multiple selections)
Standards & Approvals
blank
: Without CE
/CE
: CE marking
Other Options
blank
: none
/Q
: Option other than the above (specify the specification)
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
/C04
: Polyolefin coating
TERMINAL SCREW MATERIAL
/S01
: Stainless steel
EX-FACTORY SETTING
/SET
: Preset according to the Ordering Information Sheet
(No. ESU-8269)
CAUTION
This unit cannot be used in combination with any device other than the gateway module with master function (model: R3-GMM1).
Note that if any device other than R3-GMM1 is mounted, the device will not operate properly.
Modbus I/O data is not assigned to the unit. For compatible Modbus function codes and Modbus I/O assignment, refer to the specifications or instruction manual of R3-GMM1.
RELATED PRODUCTS
• PC Configurator cable (model: MCN-CON or COP-US)
• PC configurator software (model: R3CON)
Downloadable at our web site.
GENERAL SPECIFICATIONS
Connection
Ethernet
: RJ-45 modular jack
Internal bus
: Via the Installation Base (model: R3-BSx)
Internal p
ower
: Via the Installation Base (model: R3-BSx)
Power input, RUN contact output
: M3 separable screw terminal (torque 0.5 N·m)
Screw terminal
: Nickel-plated steel (standard) or stainless steel
Number of connected devices
: Max. 4
(Available address range is fixed. Refer to the R3-GMM1 specifications for the available address range.)
Isolation
: Ethernet to internal bus or internal power to power supply to RUN contact output to FG
RUN indicator:
Green
Green LED turns on in normal communication.
ERR indicator:
Green
Green LED turns on in abnormal communication.
■
RUN CONTACT OUTPUT
RUN contact
: Turns ON while the green RUN LED is ON (Ethernet in normal communication).
Rated load
: 250 V AC @ 0.5 A (cos ø = 1)
30 V DC @ 0.5 A (resistive load)
Maximum switching voltage
: 250 V AC or 30 V DC
Maximum switching power
: 250 VA or 150 W
Minimum load
: 1 V DC @ 1 mA
Mechanical life
: 2 × 10
7
cycles (300 cycles/min.)
When driving an inductive load, external contact protection and noise quenching recommended.
ETHERNET COMMUNICATION
Communication Standard
: IEEE 802.3u
Transmission
: 10BASE-T, 100BASE-TX
Baud rate
: 10/100 Mbps (Auto Negotiation function)
Protocol
: Modbus/TCP
Data
: RTU (Binary)
Max. number of socket connections
: 2
Transmission media
: 10BASE-T (STP, Category 5) 100BASE-TX (STP, Category 5e)
Max. length of fieldbus segment
: 100 meters
Ethernet indicator LED
: LINK, DPLX, LINK10, LINK100
IP address
: 192.168.0.1 (factory setting);
Selectable with PC Configurator Software (model: R3CON)
Subnet mask
: Configurable via the PC configurator software (model: R3CON). (Factory setting: 255.255.255.0)
Default gateway
: Configurable via the PC configurator software (model: R3CON).
(Factory setting: 192.168.0.100)
Port No
.: 502
INSTALLATION
Power consumption
•
AC
:
Approx. 20 VA at 100 V
Approx. 28 VA at 200 V
Approx. 30 VA at 240 V
•
DC
: Approx. 13 W
Current consumption (no power supply):
60 mA
Output current (power supply)
: 290 mA continuous at 20 V DC; 440 mA for 10 minutes
Operating temperature
: -10 to +55°C (14 to 131°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Atmosphere
: No corrosive gas or heavy dust
Mounting
: Installation Base (model: R3-BSx)
Weight
: 200 g (0.44 lb)
PERFORMANCE
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 1500 V AC @ 1 minute (Ethernet to internal bus or internal power to power input to RUN contact output to FG)
STANDARDS & APPROVALS
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
Low Voltage Directive
EN 61010-1, EN 61010-2-201
Installation Category II (power input)
Pollution Degree 2
Power input or RUN contact output to
internal power or internal bus or Modbus/TCP:
Reinforced insulation (300 V)
Power input to RUN contact output:
Reinforced insulation (300 V)
RoHS Directive
EXTERNAL VIEW
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
Note: In order to improve EMC performance, bond the FG terminal to ground.
Caution: FG terminal is NOT a protective conductor terminal.
SYSTEM CONFIGURATION EXAMPLES