ES-7777-B Rev.5

R7G4HH-A-SVF4

Remote I/O R7G4H Series

HI-SPEED LINK SYSTEM I/O MODULE

(HLS-compatible, high-speed DC voltage/current input, 4 points, isolated, screw terminal block)
Functions & Features
• High-speed DC voltage/current input via HLS
• Easy parameter setting of individual channels with the configurator software
HLS is the abbreviation for “Hi-speed Link System” of Step Technica Co., Ltd.

MODEL: R7G4HH-A-SVF4-R[1]

ORDERING INFORMATION

• Code number: R7G4HH-A-SVF4-R[1]
Specify a code from below for [1].
  (e.g. R7G4HH-A-SVF4-R/H/E/Q)
• Specify the specification for option code /Q
  (e.g. /C01/SET)

TERMINAL BLOCK

A: Screw terminal block for power supply
    RJ-45 Modular jack for communication
    Screw terminal block for I/O

I/O TYPE

SVF4: DC voltage /current input (10 V/20 mA), 
  high-speed, 4 points

POWER INPUT

DC power
R: 24 V DC
(Operational voltage range: ±10 %; ripple 10 %p-p max.)

[1] OPTIONS (multiple selections)

Communication Mode
blank: Full-duplex
/H: Half-duplex
Communication Connector Pin Assignment
Blank: 3, 4 - 5, 6 pair wiring
(Our HLS related device standard pin assignment)
/E: 4, 5 - 3, 6 pair wiring (Ethernet cable pin assignment)
Other Options
blank: none
/Q: Option other than the above (specify the specification)

SPECIFICATIONS OF OPTION: Q (multiple selections)

COATING (For the detail, refer to our web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating
EX-FACTORY SETTING
/SET: Preset according to the Ordering Information Sheet
(No. ESU-7777-B)

RELATED PRODUCTS

• PC Configurator cable (model: MCN-CON or COP-US)
• PC configurator software (model: R7CFG)
Downloadable at our web site.

GENERAL SPECIFICATIONS

Connection
  HLS
: RJ-45 modular jack
  Power input, input: M3 separable screw terminals 
  (torque 0.5 N·m)
Screw terminal material: Nickel-plated steel
Solderless terminal: Refer to the drawing at the end of the section.
Recommended manufacturer: J.S.T. Mfg. Co., Ltd.,
  NICHIFU Co., Ltd.
Applicable wire size: 0.25 to 1.65 mm2 (AWG22 to 16)
Housing material: Flame-resistant resin (gray)
Isolation: Input 0 to input 1 to input 2 to input 3 to HLS or FE to power
Input bias adjustment: Configurable via R7CFG
Input gain adjustment: Configurable via R7CFG
Input range: Selectable with the DIP SW on the top of the unit or configurable via R7CFG
Number of times of averaging: Configurable via R7CFG
Status indicator LEDs: PWR and ERR LEDs indicate operating conditions of the unit. (Refer to the insruction manual for detail)
Configurator connection: 2.5 dia. miniature jack
■Recommended solderless terminal

HLS COMMUNICATION

Communication mode: Full-duplex or half-duplex
Network cable
• Shield cable

Full-duplex communication:
ZHY262PS / ZHT262PS (Shinko Seisen Industry Co., Ltd.)
Half-duplex communication:
ZHY221PS (Shinko Seisen Industry Co., Ltd.)
• Dual-shield cable
ZHY262PBA (Shinko Seisen Industry Co., Ltd.)
Transmission distance: 
12 Mbps: 100 meters (328 ft)
6 Mbps: 200 meters (656 ft)
(Baud rate configurable with DIP SW; factory default: 12 Mbps)
Note: The above transmission distance is a reference value when the HLS master unit is one-to-one connected to the HLS slave unit (R7G4HH) with a designated double shielded cable.  The actual distance may differ depending on the system configuration (types of the master/slave units, communication cable, the number of slaves connected, etc.), settings, and/or the installation environment.
Terminating resistor: Built-in (Selected with the DIP SW; factory default: disabled)
Status indicator: RUN
(Refer to the instruction manual for details.)
Station address: Selectable with rotary switch
(Refer to the instruction manual for details.)

INPUT SPECIFICATIONS

■ DC Current
Input resistance
: 50 Ω
Input range: -20 to +20 mA DC, 0 to 20 mA DC,
4 to 20 mA DC
■ Narrow span voltage
Input resistance
: ≥ 100 kΩ
Input range: :-1 to +1 V DC, 0 to 1 V DC, -0.5 to +0.5 V DC
■ Wide span voltage
Input resistance
: ≥ 1 MΩ
Input range: :-10 to +10 V DC, -5 to +5 V DC,
0 to 10 V DC, 0 to 5 V DC, 1 to 5 V DC

INSTALLATION

Current consumption
•DC: Approx. 70 mA
Operating temperature: -10 to +55°C (14 to 131°F)
Storage temperature: -20 to +65°C (-4 to +149°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Surface or DIN rail (35 mm rail)
Weight: 210 g (0.46 lb)

PERFORMANCE

Conversion accuracy: ±0.1 %
Conversion rate: 200 μsec. per 4 channels
Data range: 0 – 10000 of the input range
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)
Input delay time: ≤ 1 msec. (0 - 90 %)
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute
(input 0 to input 1 to input 2 to input 3 to HLS or FE to power)

STANDARDS & APPROVALS

EU conformity:
EMC Directive 
  EMI EN 61000-6-4
  EMS EN 61000-6-2
RoHS Directive

PC CONFIGURATOR

The following parameters can be set with using PC Configurator Software (model: R7CFG).
Refer to the users manual for the R7CFG for detailed operation of the software program.

EXTERNAL VIEW

CONNECTION DIAGRAMS

TERMINAL ASSIGNMENTS

■ INPUT TERMINAL ASSIGNMENT
■ POWER SUPPLY TERMINAL ASSIGNMENT

DATA CONVERSION

RESPONSE TIME

Response time of analog input module (R7G4HH-A-SVF4; slave) is time from when 0 to 100 % stepwise signal change is applied to the module until the communication ASIC of the module transmits 90 % of input signal.

TCOM: HLS scan time
HLS scan time varies according to communication method, the number of operating slave stations (FS), transmission rate (TBPS), and the hop count (LF).
• Full-duplex communication
LF = 0     : HLS scan time = 182 x FS x (1 / TBPS) (sec.)
LF = 1 to 7: HLS scan time = (184 + (144 x LF)) x FS x (1 / TBPS) (sec.)
• Half-duplex communication
LF = 0     : HLS scan time = 354 x FS x (1 / TBPS) (sec.)
LF = 1 to 7: HLS scan time = (328 + (144 x LF)) x FS x (1 / TBPS) (sec.)

TINP: Input unit response time ≤ Delay time of input circuit (Ta) + (Conversion rate x Moving average order) (Tb) + Input internal processing time (Tc)  (HLS scan time x 2)

e.g.
Number of moving average: 1,
Communication: Full-duplex,
Number of operating slave station (FS): 63,
Transmission rate (TBPS): 12 Mbps,
the hop count (LF): 0
HLS scan time (TCOM): 182 x 63 x (1 / 12 Mbps) = 0.9555 [msec.]
Input unit response time (TINP): Delay time of input circuit (1 msec.) + Conversion rate (0.2 msec.) x Number of moving average (1 time) + Input internal processing time (0.9555 msec. x 2) = 3.1 [msec.]

I/O DATA DESCRIPTIONS

Scaling of analog input module is configurable with the configurator software (model: R7CFG). Refer to the software manual for details.

EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]

MOUNTING REQUIREMENTS unit: mm [inch]

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM

Note: In order to improve EMC performance, bond the FE terminal to ground.
Caution: FE terminal is NOT a protective conductor terminal.