ES-9644 Rev.0

R8Y-FSZH8N

Remote I/O R8 Series

DC VOLTAGE/CURRENT INPUT MODULE

(built-in excitation, 8 points, non-isolated)
Functions & Features
• DC current input and DC voltage input compact size remote I/O module
• Switching between current input and voltage input with  PC configurator (model: R8CFG) 
• Accepts direct input from power output as sensor power and outputs from terminals
• 20 pins (10 pins × 2) ZH connector (J.S.T. Mfg. Co., Ltd.)

MODEL: R8Y-FSZH8N[1]

ORDERING INFORMATION

• Code number: R8Y-FSZH8N[1]
Specify a code from below for [1].
  (e.g. R8Y-FSZH8N/Q)
• Specify the specification for option code /Q
  (e.g. /C01)

[1] OPTIONS

blank: none
/Q: With options (specify the specification)

SPECIFICATIONS OF OPTION: Q

COATING (For the detail, refer to our web site.)
/C01: Silicone coating
/C02: Polyurethane coating

RELATED PRODUCTS

• PC Configurator cable (model: MCN-CON or COP-US)
• ZH connector cable (model: ZHCL)
  The use of this cable is not mandatory.
• PC configurator software (model: R8CFG)
Downloadable at our web site.

GENERAL SPECIFICATIONS

Connection
• Input: 10-pin ZH connector
Unit side connector: S10B-ZR (J.S.T. Mfg. Co., Ltd.)
Recommended socket: ZHR-10 (J.S.T. Mfg. Co., Ltd.)
Recommended contact: SZH-002T-P0.5 (J.S.T. Mfg. Co., Ltd.)
Applicable wire size: AWG28 - 26
(The socket and contact are not included in the package. Refer to the specifications of the product)
• Excitation supply, internal bus:
Connected to internal bus connector
• Internal power: Supplied from internal bus connector
Isolation: Input or exc. supply to internal bus or internal power
Module address: With DIP switch
Terminating resistor: Built-in (DIP Switch, default: disable)
Status indicator LED: Bi-color (red/green) LED; Refer to the instruction manual.

INPUT SPECIFICATIONS

■ DC Voltage:
Input range: -10 – +10 V DC
Input setting value: Available to set in the input range
Operational range: -5 - +105 % (% of input setting value)
Input resistance: ≥ 1 MΩ
■ DC Current:
Input range: -20 – +20 mA DC
Input setting value: Available to set in the input range
Operational range: -5 - +105 % (% of input setting value)
Input resistance: 31 Ω
Factory default (Input type and input setting value):
Voltage input, input range -10 - +10 V DC for all 8 points.

INSTALLATION

Max. current consumption: 80 mA
Operating temperature: -10 to +55°C (14 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: DIN rail
Weight: 60 g (2.12 oz)

PERFORMANCE

Conversion accuracy (in percentage of input range)
Voltage input
:±0.05 %
Current input:±0.1 %
Conversion accuracy is inversely proportional to input span.
Conversion rate: 24 msec.
Input circuit time constant: Approx. 1 msec.
Data range: 0 – 10000 of the input range
(Scaling of converted data is configurable with the configurator software)
Data allocation: 2
Module addresses in use: 4
Power output (input connector): Rated current 0.75 A DC per channel (rated current 3 A for internal fuse (slow blow fuse)); Total: 1.5 A DC
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute
(input or exc. supply to internal bus or internal power to ground)

CALCULATION EXAMPLES OF CONVERSION ACCURACY

■ Voltage input:
For input setting value 1 - 5 V DC
Conversion accuracy = Input range span (20 V) ÷ input setting value span (4 V) × 0.05 (%) = 0.25 (%)
■ Current input:
For input setting value 4 - 20 mA DC
Conversion accuracy = Input range span (40 mA) ÷ input setting value span (16 mA) × 0.1 (%) = 0.25 (%)

STANDARDS & APPROVALS

EU conformity:
EMC Directive 
  EMI EN 61000-6-4
  EMS EN 61000-6-2
RoHS Directive

EXTERNAL VIEW

OPERATING MODE SETTING

(*) Factory default setting
Note: Be sure to set unused SW1-7 to OFF.

EXTERNAL DIMENSIONS unit: mm [inch]

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM